
4/4
CONNECTIONS
A shielded cable must be used: connect the
shield of the cable to the ground in the control
panel only and connect the shield between a
device.
The section of leads can vary according to the
length of the detection line.
A lead section of 1.5 mm2 is advised.
Don’t use cable that exceed these limits:
Maximum resistance = 100 Ω
Maximum capacitance = 2 µF
The electrical connection must be performed by
removing approximately 10 mm of insulating
cover from the main lead and insert it on the
terminal block.
Fig. 3 –Connection diagram
JP1 must be only executed with conventional
control panels that are able to recognize manual
call points from detectors on the same circuit.
TESTING (trained personnel)
Before testing, notify to competent authority that
the system is temporarily out of service due to
maintenance operations.
The manual call point can be tested by pressing
on the operating face and verifying the alarm
condition.
At the end of testing operations, restore the
system to normal operation and notify the status
to the competent authorities.
TECHNICAL SPECIFICATIONS
Power consumption in
alarm condition
(JP1 opened)
Power consumption in
alarm condition
(JP1 closed)
Red steady:
alarm condition
-10 55°C ± 2°C
(14 131°F)
In compliance with EN54-11: 2001/A1:2005
Resettable Manual Call Point
Mod. P440
Urmet S.p.A. 1293-CPD-0344
DoP n. 1293-CPR-0344
Further information are available to the manufacturer.
ELKRON
Tel. +39 011.3986711 - Fax +39 011.3986703
Milano:Tel. +39 02.334491- Fax +39 02.33449213
ELKRON è un marchio commerciale di URMET S.p.A.
ELKRON is a trademark of URMET S.p.A.
Via Bologna, 188/C - 10154 Torino (TO) –Italy
www.urmet.com MADE IN ITALY