Actuators KNX S4-B10 230 V, KNX S2-B6 230 V and KNX S1-B2 230 V 1
Actuators KNX S4-B10 230 V, KNX S2-B6 230 V and KNX S1-B2 230 V • Version: 27.05.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
KNX S4-B10 230 V
KNX S2-B6 230 V
KNX S1-B2 230 V
Multifunctional Actuators
Technical specifications and installation instructions
1. Description
The Actuators KNX S4-B10 230 V, KNX S2-B6 230 V and KNX S1-B2 230
Vwith integrated facade control have multifunctional outputs, pairs of buttons and
monitoring LEDs. Each of the multifunctional outputs can connect to either a drive
with Up/Down control (blinds, awnings, shutters, windows) or two switchable de-
vices (On/Off for light and ventilation). The connected drives and devices can be
operated directly on the actuator or via connected hand switches.
The automation can be specified externally or internally. Internally, there are nu-
merous options available for blocking, locking (e.g. master-slave) and priority defi-
nition (e.g. manual-automatic). Scenes can be saved and called up via the bus
(scene control with 16 scenes per drive).
Binary inputs can be used either for direct operation (e.g. hand switches) or as bus
switches (or also for e.g. alarm notifications). The desired behaviour can be de-
fined precisely through selection of the response times in Standard, Comfort or
Deadman mode.
Functions:
•Multifunctional outputs each for a 230 V drive (shade, window) or for
connecting two switchable devices (light, fan)
KNX S4-B10: 4 outputs | KNX S2-B6: 2 outputs | KNX S1-B2: 1 output
• Keypad with button pairs and status LEDs
•Binary inputs for use as hand switches or as bus switches with variable
voltage (12...80 V DC, 12...240 V AC)
KNX S4-B10: 10 inputs | KNX S2-B6: 6 inputs | KNX S1-B2: 2 inputs
•Automatic runtime measurement of the drives for positioning (including
fault notification object)
• Position feedback (movement position, also slat position for blinds)
• Position storage (movement position) via 1-bit object (storage and call-up
e.g. via button)
• Control via internal or external automation
• Integrated shade control for each drive output (with slat tracking
according to sun position for blinds)
•Scene control for movement position with 16 scenes per drive (also slat
position for blinds)
•Mutuallocking of two drives using zero position sensors prevents
collisions e.g. of shade and window (master–slave)
• Blocking objects and alarm notifications have different priorities, so safety
functions always take precedence (e.g. wind block)
• Manual or automatic priority setting via time or communication object
• 5 Safety objects for each channel
• Short time restriction (movement command blocked) and movement
limitation
Configuration is made using the KNX software ETS 5. The product file can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the “Service” menu.
1.0.1. Scope of delivery
• Actuator
1.1. Technical Data
KNX S4-B10 230 V (No. 70530):
KNX S2-B6 230 V (No. 70531):
KNX S1-B2 230 V (No. 70532):
The products are compliant with the provisions of EU guidelines.
2. Installation and start-up
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
DANGER!
Risk to life from live voltage (mains voltage)!
There are unprotected live components within the device.
• VDE regulations and national regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
• Do not use the device if it is damaged.
• Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for the intended purpose described in this manual.
Any improper modification or failure to follow the operating instructions voids any
and all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when as-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.2. Safety notice for automatic functions
WARNING!
Risk of injury from automatically moving components!
Parts of the system can be started by the automatic controls
and be a danger to persons.
• No persons may remain in the travelling range of parts
driven by an electric motor.
• Adhere to the relevant building regulations.
• Ensure that the return path/access to the building is not blocked
if spending time outside the building (danger of being locked out).
• Correctly decommission the system for maintenance and
cleaning work.
If there is a power outage, the system does not work. Therefore, shadings should
be moved to a save position if there are anticipated weather conditions, for exam-
ple, if this has not already been done by the automatic function (product protecti-
on).
If the power supply is removed, the connected drive switches off. When the power
is restored, the consumer remains switched off until a new movement command
is received by the actuator.
2.3. Connection
Follow the guidelines and standards for SELV electric circuits
while installing and cable laying of the KNX connection and
inputs.
Binary inputs:
The connections of the binary inputs including the auxiliary voltage output meet
the requirements for SELV electrical circuits. Mixed installation with non-SELV
electrical circuits or mixing of different auxiliary voltages is not permitted.
2.3.1. Device Design KNX S4-B10 230 V
The device is designed for series installation on mounting rails and occupies 6
width units.
1) –/N (bridged internally with terminal No. 5). When an external auxiliary voltage
is used (12...80 V DC, 12...240 V AC), one of the –/N terminals is to be assigned
with – or N
2) Free contacts (bridged internally)
3) Programmer LED and programmer buttons (PRG)
4) Bus terminal slot (KNX +/-)
5) –/N (bridged internally with terminal No. 1).
6) Binary inputs 1-6 (1 and 2: two bridged connections)
7) Internal auxiliary voltage + 24 V DC. Only for binary inputs!
Do not assign any external voltage!
8) Binary inputs 7-10
9) Up/Down button pairs and LEDs channel A-D
10)Power LED, Indication of operation mode. See “Indication of operation mode
with the Power LED”.
11)Operating voltage input 230 V AC L/N/PE
12)Output A1 - A2: "Up"-"Down" or "Device1"-"Device2", max. 4 A
13)Output B1 - B2: "Up"-"Down" or "Device1"-"Device2", max. 4 A
14)Output C1 - C2: "Up"-"Down" or "Device1"-"Device2", max. 4 A
15)Output D1 - D2: "Up"-"Down" or "Device1"-"Device2", max. 4 A
Nº 12-15 together max. 10 A
16)All terminals L, N, PE of the lower connection strip are bridged internally with
„Main L, N, PE“.
Housing Plastic
Colour White
Assembly Series installation on mounting rails
Protection Category IP 20
Ambient temperature Operation -20...+45°C, Storage -
55...+90°C
Ambient humidity max. 95% rH, avoid condensation
Operating voltage 230 V AC, 50 Hz
Current on Bus: 10 mA
Maximum load Each terminal contact may be loaded
with a maximum of 10 A.
Minimum current for runtime
measurement
AC effective 200 mA
Item numbers 70530 (KNX S4-B10 230 V), 70531 (KNX S2-B6 230 V), 70532 (KNX S1-B2 230 V)
Max. cable length Binary
inputs
50 m
Data output KNX +/- Bus connector terminal
BCU type own microcontroller
PEI type 0
Goup addresses max. 1024
Assignments max. 1024
Dimensions approx. 107 x 88 x 60 (W × H × D, mm), 6 dividing
units
Weight approx. 360 g
Power consumption Operation max. approx. 3.5 W
Standby max. approx. 0.6 W
Outputs 4 × outputs each with 2 connections for drive up/
down or 2 devices, 230 V (PE/N/1/2),
total. max 10 A and max. 4 A per connection
Inputs 10 × binary inputs, universal voltage
(12...80V DC, 12...240 V AC)
Communication
objects
567
Dimensions approx. 107 x 88 x 60 (W × H × D, mm), 6 dividing
units
Weight ca. 360 g
Power consumption Operation max. approx, 3.5 W
Standby max. ca. 0.6 W
Outputs 2 × outputs
with 2 connections for drive Up/Down or 2
devices,
230 V (PE/N/1/2),
in total max. 10 A and max. 4 A per connection
Inputs 6 × binary inputs, universal voltage
(12...80 V DC, 12...240 V AC)
Communication
objects
295
Dimensions approx. 53 x 88 x 60 (W × H × D, mm), 3 dividing
units
Weight approx. 170 g
Power consumption Operation max. approx, 1.2 W
Output 1 × Output with 2 connections for drive Up/Down
or 2 devices, 230 V (PE/N/1/2),
in total max. 8 A and max. 4 A per connection
Inputs 2 × binary inputs, universal voltage
(12...80 V DC, 12...240 V AC)
Communication
objects
141
3
4
5 7
9
10
1 2
6 8
11
12 13 14 15 16
EN
Actuators KNX S4-B10 230 V, KNX S2-B6 230 V and KNX S1-B2 230 V 2
Actuators KNX S4-B10 230 V, KNX S2-B6 230 V and KNX S1-B2 230 V • Version: 27.05.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • Technical Service: +49 (0) 7033 / 30945-250
2.3.2. Device Design KNX S2-B6 230 V
The device is designed for series installation on mounting rails and occupies 6
width units.
1) –/N (bridged internally with terminal No. 5). When an external auxiliary voltage
is used (12...80 V DC, 12...240 V AC), one of the –/N terminals is to be assigned
with – or N
2) Free contacts (bridged internally)
3) Programming LED and programming buttons (PRG)
4) Bus terminal slot (KNX +/-)
5) –/N (bridged internally with terminals No. 1)
6) Binary inputs 1-2 (two bridged connections)
7) Internal auxiliary voltage + 24 V DC. Only for binary inputs!
Do not assign any external voltage!
8) Binary inputs 3-6
9) Up/Down button pairs and LEDs channel A-B
10)Mains LED (Power), mode status display. See “Indication of operation mode
with the Power LED”.
11)Operating voltage input 230 V AC L/N/PE
12) Output A1 - A2: "Up"-"Down" respectively "Device1"-"Device2", max. 4 A
13) Output B1 - B2: "Up"-"Down" respectively "Device1"-"Device2", max. 4 A
No. 12-13 in total max. 10 A
14) All terminals L, N , PE of the lower connection strip are bridged internally with
„main L, N, PE“.
2.3.3. Device Design KNX S1-B2 230 V
The device is designed for series installation on mounting rails and occupies 3
width units.
2.3.4. Indication of operation mode with the Power LED
2.3.5. Status display by the channel LEDs
2.4. Notes on mounting and commissioning
Device must not be exposed to water (rain). This could result in the electronic
being damaged. A relative air humidity of 95% must not be exceeded. Avoid bede-
wing.
After the operating voltage has been applied, the device will enter an initialisation
phase lasting a few seconds. During this phase no information can be received or
sent via the bus.
For KNX devices with safety functions (e.g. wind or rain blocks), periodical moni-
toring of the safety objects must be set up. The optimal ratio is 1:3 (example: if the
weather station sends a value every 5 minutes, the actuator must be configured for
a monitoring period of 15 minutes).
2.5. Connection examples for binary inputs KNX S4-
B10 and KNX S2-B6
2.5.1. Using the internal auxiliary voltage of the actuator
2.5.2. Using an external voltage
2.6. Connecting example for binary inputs KNX S1-B2
230 V
2.6.1. Using the internal auxiliary voltage of the actuator
2.6.2. Using an external auxiliary voltage
3. Addressing of the device at the bus
The device is supplied with the bus address 15.15.255. You can program another
address into the ETS by overwriting the 15.15.255 address or by teaching via the
programming button.
4. Disposal
After use, the device must be disposed of or recycled in accordance with the legal
regulations. Do not dispose of it with the household waste!
Behaviour Colour
On Green Normal operation.
Bus connection/bus voltage available.
Flashes Green Normal operation.
No bus connection/bus voltage available.
On Orange Device starts up or is beeing programmed via
the ETS.
No automatic functions are executed.
Flashes Green (on)
Orange
(flashing)
Programming mode active.
Behaviour LED
To top Drive in top end position/device on.
To bottom Drive in bottom end position/drive on.
Flashes
slowly
top Drive moves up.
3
4
5 7
9
10
1 2
6 8
11
12 13 1414
1) Programming LED and program-
ming buttons (PRG)
2) Bus terminal slot (KNX +/-)
3) Switch pair Up/Down and LEDs
4) Mains LED (Power), mode status
display. See “Indication of opera-
tion mode with the Power LED”.
5) Operating voltage input 230 V AC L/
N/PE
6) Output A1 - A2: "Up"-"Down" re-
spectively "Device1"-"Device2",
max. 4 A
7) All terminals L, N, PE of the lower
connection strip are bridged inter-
nally with „Main L, N, PE“.
8) Binary inputs 1-2
9) Internal auxiliary voltage + 24 V DC.
Only for binary inputs! Do not as-
sign any external voltage!
10)-/N for external auxiliary voltage
(12...80 V DC, 12...240 V AC)
2
9
4
6
7
10
1
3
5 8
Flashes
slowly
bottom Drive moves down.
Flashes
quickly
top Drive in top end position, blocking
active.
Flashes
quickly
bottom Drive in bottom position, blocking
active.
Flashes
quickly
both
simultaneously
Drive in intermediate position, blocking
active.
Extend both Drive in intermediate position.
Flashes both alternately Automatic runtime determination error.
If the drive can be moved, drive it into
the end position by hand (drive in/drive
out completely or open/close) in order
to restart the runtime determination.
If the drive cannot be moved, check the
connections.
"Runlight"
above all
LEDs
all channels Incorrect application version was
loaded. Use the version compatible
with the device!
Behaviour LED
Other binary inputs corresponding.
External auxiliary voltage
12...80 V DC resp. 12...240 V AC
B1 directly at the phase.
B3 via internally bridged voltage.
Other binary inputs corresponding.
Each terminal contact may be loaded with a maximum of 10 A.
According to additional binary
inputs.
External auxiliary voltage
12...80 V DC or 12...240 V AC
B1 directly at the phase.
According to additional binary
inputs.
Each terminal contact may be
loaded with a maximum of 10
A.

This manual suits for next models

5

Other elsner elektronik Controllers manuals

elsner elektronik KNX S4-B12 DES User manual

elsner elektronik

elsner elektronik KNX S4-B12 DES User manual

elsner elektronik KNX K8 Guide

elsner elektronik

elsner elektronik KNX K8 Guide

elsner elektronik KNX RF-MSG-ST User manual

elsner elektronik

elsner elektronik KNX RF-MSG-ST User manual

elsner elektronik Cala Touch KNX User manual

elsner elektronik

elsner elektronik Cala Touch KNX User manual

elsner elektronik 70711 User manual

elsner elektronik

elsner elektronik 70711 User manual

elsner elektronik KNX S2 User manual

elsner elektronik

elsner elektronik KNX S2 User manual

elsner elektronik KNX R4 16 A Guide

elsner elektronik

elsner elektronik KNX R4 16 A Guide

elsner elektronik KNX K4 User manual

elsner elektronik

elsner elektronik KNX K4 User manual

elsner elektronik KNX RF-MSG2-DST User manual

elsner elektronik

elsner elektronik KNX RF-MSG2-DST User manual

elsner elektronik KNX S1R-B4 compact Guide

elsner elektronik

elsner elektronik KNX S1R-B4 compact Guide

elsner elektronik KNX DALI L4 bc 16 A Guide

elsner elektronik

elsner elektronik KNX DALI L4 bc 16 A Guide

elsner elektronik KNX S1R-B4-UP DES User manual

elsner elektronik

elsner elektronik KNX S1R-B4-UP DES User manual

elsner elektronik Nunio KNX M-T Guide

elsner elektronik

elsner elektronik Nunio KNX M-T Guide

elsner elektronik KNX R1-B4 compact 16 A Guide

elsner elektronik

elsner elektronik KNX R1-B4 compact 16 A Guide

elsner elektronik KNX eTR MultiTouch User manual

elsner elektronik

elsner elektronik KNX eTR MultiTouch User manual

elsner elektronik KNX eTR 205 Light Guide

elsner elektronik

elsner elektronik KNX eTR 205 Light Guide

elsner elektronik KNX RF S1R-B2 compact Guide

elsner elektronik

elsner elektronik KNX RF S1R-B2 compact Guide

elsner elektronik RF-MSG2-DST User manual

elsner elektronik

elsner elektronik RF-MSG2-DST User manual

elsner elektronik KNX RF-MSG-DST Guide

elsner elektronik

elsner elektronik KNX RF-MSG-DST Guide

elsner elektronik KNX S-B2-UP 230 V Instruction manual

elsner elektronik

elsner elektronik KNX S-B2-UP 230 V Instruction manual

elsner elektronik KNX Touch One Style User manual

elsner elektronik

elsner elektronik KNX Touch One Style User manual

elsner elektronik KNX S1R-B4-UP DES Guide

elsner elektronik

elsner elektronik KNX S1R-B4-UP DES Guide

elsner elektronik KNX S1R-BA4-UP Guide

elsner elektronik

elsner elektronik KNX S1R-BA4-UP Guide

elsner elektronik KNX S-B4T-UP 230 V Instruction manual

elsner elektronik

elsner elektronik KNX S-B4T-UP 230 V Instruction manual

Popular Controllers manuals by other brands

Elisa intuition user guide

Elisa

Elisa intuition user guide

Westpow STR.B Series user manual

Westpow

Westpow STR.B Series user manual

DBK EHT-2-220A quick start guide

DBK

DBK EHT-2-220A quick start guide

Lumiax Shine series user manual

Lumiax

Lumiax Shine series user manual

Spirax Sarco LC1350 Installation and maintenance instructions

Spirax Sarco

Spirax Sarco LC1350 Installation and maintenance instructions

Aaeon GES-2200F owner's manual

Aaeon

Aaeon GES-2200F owner's manual

CTEK NANOGRID home user manual

CTEK

CTEK NANOGRID home user manual

Regin RVAZ2-24A Instruction

Regin

Regin RVAZ2-24A Instruction

Lehigh E-Flex 1.2.3 Installation and user manual

Lehigh

Lehigh E-Flex 1.2.3 Installation and user manual

Emerson Unidrive M400 quick start guide

Emerson

Emerson Unidrive M400 quick start guide

Hubbell Euclid Lifting Magnet Controller 4295 Specification sheet

Hubbell

Hubbell Euclid Lifting Magnet Controller 4295 Specification sheet

Omron E5EZ-PRR Series manual

Omron

Omron E5EZ-PRR Series manual

iRobot IR-CT01 user manual

iRobot

iRobot IR-CT01 user manual

Doms PSS 5000 Product guide

Doms

Doms PSS 5000 Product guide

Saga saga1-l4 Installation & operation manual

Saga

Saga saga1-l4 Installation & operation manual

Siemens 5WG1 513-1AB11 Technical product guide

Siemens

Siemens 5WG1 513-1AB11 Technical product guide

Siemens 81000 series manual

Siemens

Siemens 81000 series manual

Conrad Electronic KW-9015 operating instructions

Conrad Electronic

Conrad Electronic KW-9015 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.