S&C Vista SD Owner's manual

Instruction Sheet 695-515
Introduction
Qualified Persons ..............................2
Read this Instruction Sheet.......................2
Retain this Instruction Sheet......................2
Warranty .....................................2
Warranty Qualifications..........................2
Safety Information
Understanding Safety-Alert Messages ..............3
Following Safety Instructions .....................3
Replacement Instructions and Labels...............3
Location of Safety Labels ........................4
Description
General ......................................5
Programming .................................5
Power and Sensing.............................6
Time-Current Characteristics .....................6
Settings ......................................6
Event Recording ...............................7
Self Testing ...................................7
Setting Up for Programming
Connecting a Personal Computer..................8
Setting the Communication Parameters .............8
Programming
Factory-Default Settings .........................9
Fault Interrupters 1 and 2 ........................9
Passwords. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Main Menu ...................................9
View Menu 1 or 2 .............................10
Configure Menu 1 or 2 .........................12
Change User Password ........................14
Group Configure Menu .........................14
Test Trip Menu................................16
Self-Test Report
Viewing of Self-Test Report .....................17
Response to Self-Test Failure ....................17
Self-Test Failures and Warnings ..................18
Specifications
Port Power ..................................19
CT Power ...................................19
Steady State Accuracy .........................19
Time-Overcurrent Pickup Accuracy................19
Time-Overcurrent Response.....................19
Instantaneous Pickup Accuracy ..................19
Instantaneous Response .......................19
Definite-Time Response ........................19
Appendix A
External Connections..........................20
Appendix B
Communication Parameters .....................24
Appendix C
Using Terminal Emulator Programs................25
HyperTerminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
AcSELerator
®QuickSet 5030™..................26
Appendix D
Coordination .................................27
Appendix E
Overcurrent Control Settings.....................32
Programming S&C Overcurrent Control
Section Page Section Page
Table of Contents
© S&C Electric Company 2015-2016, all rights reserved
November 21, 2016
S&C Vista®SD Underground Distribution Switchgear
Outdoor Distribution (17.5 kV and 29 kV)
With Visi-Gap®
Load-Interrupter Switches and
Visi-Gap®Fault Interrupters

Qualified Persons WARNING
The equipment covered by this publication must be operated and maintained by qualified
persons who understand any hazards involved and are thoroughly trained in the operation
and maintenance of electronic control devices which are used in conjunction with power dis-
tribution equipment. These instructions are intended only for such qualified persons. They
are not intended to be a substitute for adequate training and experience in safety proce-
dures for this type of equipment.
Read this
Instruction Sheet NOTICE
Thoroughly and carefully read this instruction sheet before programming, operating,
or maintaining your S&C Overcurrent Control. Familiarize yourself with the Safety Informa-
tion on page 3. The latest version of this instruction sheet is available online in PDF format
at sandc.com/Support/Product-Literature.asp
Retain this
Instruction Sheet
This instruction sheet is a permanent part of your S&C Vista SD Underground Distribu-
tion Switchgear. Designate a location where you can easily retrieve and refer to this
publication.
Warranty The warranty and/or obligations described in S&C’s standard conditions of sale, as set
forth in Price Sheet 150, plus any special warranty provisions, as set forth in the applicable
product-line specication bulletin, are exclusive. The remedies provided in the former
for breach of these warranties shall constitute the immediate purchaser’s or end user’s
exclusive remedy and a fulllment of all seller’s liability. In no event shall the seller’s
liability to immediate purchaser or end user exceed the price of the specic product
that gives rise to the immediate purchaser’s or end user’s claim. All other warranties,
whether express or implied or arising by operation of law, course of dealing, usage of
trade or otherwise, are excluded. The only warranties are those stated in Price Sheet 150,
and THERE ARE NO EXPRESS OR IMPLIED WARRANTIES OF MERCHANTABILITY
OR FITNESS FOR A PARTICULAR PURPOSE. ANY EXPRESS WARRANTY OR
OTHER OBLIGATION PROVIDED IN PRICE SHEET 150 IS GRANTED ONLY TO THE
IMMEDIATE PURCHASER AND END USER, AS DEFINED THEREIN. OTHER THAN AN
END USER, NO REMOTE PURCHASER MAY RELY ON ANY AFFIRMATION OF FACT OR
PROMISE THAT RELATES TO THE GOODS DESCRIBED HEREIN, ANY DESCRIPTION
THAT RELATES TO THE GOODS, OR ANY REMEDIAL PROMISE INCLUDED IN PRICE
SHEET 150.
Warranty
Qualifications
The seller’s standard warranty does not apply to components not of S&C manufacture that
are supplied and installed by the purchaser or to the ability of seller’s equipment to work
with such components.
Introduction
2 S&C Instruction Sheet 695-515

Understanding
Safety-Alert
Messages
Several types of safety-alert messages may appear throughout this instruction sheet and
on labels attached to the S&C Overcurrent Control. Familiarize yourself with these types
of messages and the importance of these various signal words:
DANGER
“DANGER” identifies the most serious and immediate hazards that will likely
result in serious personal injury or death if instructions, including recommended pre-
cautions, are not followed.
WARNING
“WARNING” identifies hazards or unsafe practices that can result in serious per-
sonal injury or death if instructions, including recommended precautions, are
not followed.
CAUTION
“CAUTION” identifies hazards or unsafe practices that can result in minor
personal injury if instructions, including recommended precautions, are not followed.
NOTICE
“NOTICE” identifies important procedures or requirements that can result in product or
property damage if instructions are not followed.
Following Safety
Instructions
If you do not understand any portion of this instruction sheet and need assistance,
contact your nearest S&C Sales Office or S&C Authorized Distributor. Their tele-
phone numbers are listed on S&C’s website sandc.com. Or call the S&C Global Monitoring
and Support Center at 1-888-456-1100.
NOTICE
Thoroughly and carefully read this
instruction sheet before programming
your S&C Overcurrent Control.
Replacement
Instructions
and Labels
If you need additional copies of this instruction sheet, contact your nearest S&C Sales
Ofce, S&C Headquarters, or S&C Electric Canada Ltd.
It is important that any missing, damaged, or faded labels on the equipment be
replaced immediately. Replacement labels are available by contacting your nearest S&C
Sales Office, S&C Headquarters, or S&C Electric Canada Ltd.
Safety Information
S&C Instruction Sheet 695-515 3

Location of Safety Labels
Enclosure for overcurrent control with cover removed to show electronics module.
Electronics module
WARNING
Hazardous voltage inside can shock, burn,
or cause death.
Safety Information
DANGER
Never disconnect current transformer
secondary circuits without de-energizing
the switchgear. Hazardous voltage will
shock, burn, or cause death.
Burden-board module
Electronics module removed to show burden-board module.
4 S&C Instruction Sheet 695-515

Enclosure is mounted on switchgear
(pad-mounted style shown here—a
stainless steel enclosure is provided for
vault-mounted style Vista SD)
Adapter cable connects overcurrent
control to a personal computer
Personal computer is used to input
settings and interrogate event recorder
General The following instructions are for eld and shop programming of the S&C Overcurrent
Control. This microprocessor-based control is designed for use on S&C Vista SD Under-
ground Distribution Switchgear to provide fault detection and operation of the resettable
vacuum fault interrupters. Each overcurrent control operates up to two three-pole fault
interrupters. The control is housed in an enclosure mounted to the operating mechanism
enclosure. For vault-mounted style Vista SD units, the overcurrent control enclosure is
fully submersible. The electronics module is removable for programming in the shop.
Programming A personal computer furnished by the user is to be used to input settings, review
settings, and interrogate the event recorder. The software for programming the overcur-
rent control is contained within the control. Two data ports are provided—one on
the enclosure for programming in the eld and another on the electronics module for
programming in the shop. Adapter cables are available from S&C (see Instruction Sheet
695-515A) to connect the computer to the control.
An external power source is required for programming and interrogating the control.
A source of dc power is available from the mouse or USB port on the personal computer.
The adapter cables contain connectors for data and power to use the power available
from the computer.
Description
S&C Instruction Sheet 695-515 5

Power and Sensing Current transformers are provided for each three-pole fault interrupter. These current
transformers provide primary current sensing ranging from 50 to 12,500 amperes. S&C
Vista SD Underground Distribution Switchgear rated above 12.5 kA short circuit will
respond to fault currents above 12.5 kA, but the event log will only record that a fault above
12.5 kA has occurred. The overcurrent control is capable of sensing and responding to
both phase overcurrents and ground overcurrents.
The power derived from the current transformers is used to operate the control and to
charge the trip capacitors that discharge into magnetic latching solenoids to trip the fault
interrupters during a fault. No external power is required for operation of the control in
the field.
Time-Current
Characteristics
The overcurrent control features time-current characteristic (TCC) curves consisting
of phase-overcurrent curves and ground-overcurrent curves. The families of curves are
included as follows:
• S&C standard speed curves (for use in place of conventional “E” rated power fuses
• S&C “K” speed curves (for use in place of conventional “K” rated power fuses)
• Tap fault interrupter curves
• Main fault interrupter curves
• ANSI U.S. and IEC curves per IEEE Standard C37.112-1996 U1, U2, U3, U4, U5, C1, C2,
C3, C4, and C5
The tap and main fault-interrupter TCC curves can be customized into hundreds
of different curves using a variety of instantaneous-pickup settings (discrete choices
from 0.2 kA through 6 kA) and definite-time delay settings (discrete choices from
32 ms through 128 ms). For even more specialized shapes, an instantaneous-pickup
setting can be combined with a definite-time delay setting. The minimum total
clearing time—from initiation of the fault to total clearing—is 40 milliseconds.▲
Settings
(See Appendix E for a
complete list of settings)
The overcurrent control has a phase-overcurrent pickup setting and an independent
ground-overcurrent pickup setting for each three-pole fault interrupter.
The input parameters for both the phase- and ground-overcurrent curves include
minimum pickup levels, instantaneous-pickup levels, and definite-time delays.
Phase-overcurrent pickup settings and ground-overcurrent pickup settings are made
independently. If desired, the ground-overcurrent curve and the instantaneous-
pickup and definite-time-delay attributes can be disabled. When E-speed or K-speed
curves are selected, the ground-overcurrent pickup setting is disabled as are the
instantaneous-pickup and definite-time-delay attributes. An example of how to select set-
tings for the overcurrent control is shown in Appendix D.
A choice of 50- or 60-hertz operation is also offered.
▲The definite-time delay setting will override the instantaneous setting when the definite-time delay setting is
activated before the instantaneous setting.
Description
6 S&C Instruction Sheet 695-515

Event Recording The overcurrent control features an internal event recorder that captures the last
12 fault operations for each fault interrupter. The event log indicates which poles
have experienced a fault, the magnitude of the fault, and whether a ground over-
current was involved. This information can be accessed via a personal computer
connected to the data port of the control.
Self Testing Whenever the overcurrent control is powered up—and then periodically
thereafter—it automatically goes through a self-test procedure to test vital sub-
systems and ensure proper operation. The control checks the trip capacitors,
power-supply voltage, RAM, EEPROM, integrity of the data, and voltage control. It
then ags whatever fails the self-test.
Description
S&C Instruction Sheet 695-515 7

Connecting a Personal Computer
NOTICE
S&C does not recommend removing the S&C Over-
current Control from its enclosure for workbench
programming. The Overcurrent Control is in a submers-
ible enclosure. Opening the enclosure may damage the
sealing gasket. Contact your local S&C Sales Office for
details.
A data port for communications is provided at the top of
the enclosure that houses the overcurrent control. This
data port, which is connected to the electronics module
inside the enclosure, cannot draw power from the control
and must be powered from an external source while in
use. When the data port is in use, the power-connection
points (Pins 1 and 4) power the control. The allowable
voltage range is 4 – 5 Vdc, and the power consumption is
1.8 W nominal, 2.2 W maximum.
Adapter cables are available from S&C (see Instruction
Sheet 695-515A)for connecting the control to auser- furnished
personal computer in the field. These cables provide for both
communications and power.
For Microsoft Windows® users, no special software is
required to communicate with the control. The user interface
is menu driven within the control. Use the HyperTerminal
program provided with Microsoft Windows or other
terminal emulator program to set or interrogate the control.
Microsoft Windows Vista™, Windows®7, and Windows®8
users will have to install a terminal emulator program. See
Appendix C for further instructions.
Setting the Communication Parameters
Set the communication parameters shown in Appendix B.
Refer to Appendix C for additional instructions regarding
terminal emulation programs.
Adapter cable—connect cable to personal computer, serial
cable with PS/2 power cable shown (USB-style cable not
shown)
Overcurrent control—(Pad-Mounted Style
enclosure shown)
Adapter cable—connect cable to
communications data port on enclosure
Data port
Setting Up for Programming
8 S&C Instruction Sheet 695-515

Factory-Default
Settings
The overcurrent control is provided with the factory-default settings shown here.
TCC curve type = E
Curve selection = 200E
Instantaneous pickup (amps) = NA
Definite-time delay (ms) = NA
Fault Interrupters 1
and 2
Each overcurrent control is capable of operating up to two fault interrupters. To
differentiate between the two fault interrupters, the programming software refers to
Fault Interrupter 1 and Fault Interrupter 2. If the control is operating two fault inter-
rupters, the fault interrupter to the left of the control (as you are facing the front of the
switchgear) is Fault Interrupter 1, and the fault interrupter to the right of the control is
Fault Interrupter 2. If there is only one fault interrupter, it is Fault Interrupter 2.
Passwords Factory-Default Passwords
Type of Password
User
Group Configure
Password
6601
4731
Two passwords—the User and Group Congure Passwords—control access to the sensi-
tive areas of the menu system. The User Password must be entered to change control
settings, test trip the solenoids, and change the User Password.
The Group Configure Password is required to change the global settings, download
firmware, and change the Group Configure Password.
Passwords must contain four numeric characters. Each control is provided with
factory- default passwords. The User and Group Configure Passwords can be changed, but
the default passwords will always allow access.
Main Menu Step 1
To begin communications, open the terminal emulator program and press the Enter but-
ton (refer to Appendix C for additional instructions regarding terminal emulation). The
control will respond with the main menu and an “=” prompt.
Step 2
Select the desired option from the Main Menu and input the corresponding number after
the “=” prompt. Press <ENTER>. (Option 1 is shown as an example.)
Main Menu: <select number>
1. View Menu 1
2. Configure Menu 1
3. View Menu 2
4. Configure Menu 2
5. Change User Password
6. Switch to Group Configure
7. Test Trip Menu
= 1
INTERRUPTER 1
INTERRUPTER 1
INTERRUPTER 2
INTERRUPTER 2
Programming
S&C Instruction Sheet 695-515 9

Step 3
Refer to one of the following sections for further information:
Option Page
View Menu 1 ...................................... 10
Configure Menu 1 .................................. 12
View Menu 2 ...................................... 10
Configure Menu 2 .................................. 12
Change User Password ............................. 14
Group Configure Menu.............................. 14
Test Trip Menu..................................... 16
View Menu 1 or 2 The View Menu option allows review of the settings and status of the control. (The View
Menu option shown below is for Fault Interrupter 1.)
Step 1
Select the desired option from the View Menu screen and enter the corresponding number
after the “ > ” prompt. Press the Enter button. (Option 1 is shown as an example.)
Step 2
Refer to the appropriate subsection below for further information on the selected option.
Step 3
To return to the main menu, enter “9” after the “>” prompt, and press the Enter button.
View Menu INTERRUPTER 1: <select number>
1. View event report (last 12 events)
2. View load current
3. View relay settings
4. View relay self-test
9. Switch to Main Menu
= View FI 1 > 1
View Event Report
The View Event Report option allows viewing of the last 12 recorded events for the
selected fault interrupter. The report includes faulted poles and whether ground was
involved, primary RMS current magnitude, and ground current for each pole at the exact
instant fault current is detected (which values may not always make sense), and the time
since the last event. The time is not displayed if there has been no other event since
power up or if more than 60 seconds has elapsed since the previous report.
New events are inserted at the number 1 position. When the list is full, the oldest event
will drop from the list. Faulted poles are indicated by an “X.”
Programming
10 S&C Instruction Sheet 695-515

The overcurrent control stores a nonvolatile short event report each time it issues a trip
pulse. The short event report contains the following information:
The faulted pole(s) and whether ground was involved. The “target” (X) logic is as
follows:
1. Target any faulted poles that caused a trip.
2. Target any phase faulted pole with current greater than the phase time overcurrent
pickup setting.
INTERRUPTER 1
*Eve* **Faulted Poles** * * * * * Amperes ** * * * Elapsed
**Time**
# 1 2 3 G 1 2 3 G (Seconds)
1 X X X 4 2040 1829 1908 0.019
2 X X 24 1926 18 1908
3 X X 2010 22 18 1992
Press <ENTER> for menu
NOTE: The “X” targets are used under fault conditions. In test mode, fault poles are ran-
domly selected.
3. Target the ground-faulted pole if ground current is greater than the ground pickup
setting or if ground current is greater than or equal to 50A and greater than 10% of the
maximum phase current.
4. If only one target is declared from the previous logic, target the faulted pole (of the
remaining three with the highest current).
The primary RMS magnitude of each pole and ground current. Current greater than
14,500 amperes will be reported as “>14500”.
The event report is reset when the fault-interrupter settings are changed and saved.
View Load Current
The View Load Current option allows viewing a snapshot of the load current sensed by
the current transformers for each pole and ground for the selected fault interrupter.
INTERRUPTER 1
1 2 3 G
Load current (Amperes) 50 49 48 2
Press <ENTER> for menu
View Relay Settings
The View Relay Settings option allows viewing of the time-current characteristic curve
settings, trip mode, and frequency for the selected fault interrupter.
INTERRUPTER 1
PHASE GROUND
TCC curve type E NA
Curve selection 200E NA
Inst. pickup (kA) N/A N/A
Definite-time delay (ms) N/A N/A
Trip mode
Frequency
3
60
Press <ENTER> for menu
Programming
S&C Instruction Sheet 695-515 11

View Relay Self-Test
The View Relay Self-Test option allows viewing of the self-test status report for the
selected fault interrupter. This report includes the status of the trip capacitors, supply
voltage, RAM, integrity of the data, CR-RAM, EEPROM, and voltage control. See “Self-
Test Failures and Warnings” section on page 18 for more information.
INTERRUPTER 1
FID = S&C–1000–R100–970317
SELF TESTS
W = Warn F = Fail
Pole # 1 2 3
Trip Caps OK OK OK
Supply + 5V + 12V
Voltage 4.99 12.26
RAM FLASH CR_RAM EEPROM V_CONTROL
OK OK OK OK OK
Press <ENTER> for menu
Configure Menu 1 or 2 The Congure Menu option allows review and changes to the TCC curve set-
tings for the selected fault interrupter. (The Congure Menu box below is for Fault
Interrupter 1.)
Step 1
Select the desired option from the Congure Menu screen and enter the corresponding
number after the “ > ” prompt. Press the Enter button. (Option 1 is shown as an example.)
Step 2
Refer to the appropriate subsection below for further information on the selected
option.
Step 3
To return to the main menu, enter “9” after the “> ” prompt, and press the Enter button.
Configure Menu INTERRUPTER 1: <select number>
1. Change relay settings
2. View relay settings
9. Switch to main menu
= Config FI 1 > 1
Programming
12 S&C Instruction Sheet 695-515

Change Relay Settings
The Change Relay Settings option allows changes to the TCC curve settings for the selected
fault interrupter. There is a prompt for the input for each setting.
Step 1
After each prompt, enter the new setting and press the Enter button. The available choices
are shown in parenthesis. To retain the previous selection shown after the “= ” , press the
Enter button.
Step 2
After all of the settings have been entered, the new settings will be displayed in a table.
Enter “Y” for the Yes option or “N” for No option after the “Save Changes (Y/N)?” prompt. A
conrmation of the choice will be shown and the settings will be displayed. Note that when
new settings are saved, the event report discussed in “View Event Report” on page 10 will be
reset.
<Press ‘Q’ to return to menu>
Phase TCC Curve (E, K, TAP, MAIN, U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) = E ?tap
Minimum Pickup (Amps) (50, 65, 80, 100, 150, 200, 250, 300, 350, 400) = 50 ?200
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6) = OFF ?5
Denite-Time Delay (ms) @ 60Hz (OFF, 32, 48, 64, 80, 96) = OFF ?32
Ground TCC Curve (OFF, TAP, MAIN) = OFF ?tap
Minimum Pickup (Amps) (50, 65, 80, 100, 150, 200, 250, 300, 350, 400) = 50 ?200
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6) = OFF ?1
Denite-Time Delay (ms) @60Hz (OFF, 32, 48, 64, 80, 96) = OFF ?32
PHASE GROUND
TCC Curve Type TAP TAP
Min. Pickup (Amperes) 200 200
Inst. Pickup (kA) 5 1
Denite-Time Delay (ms) 32 32
Save Changes (Y/N)? y
SETTINGS SAVED
PHASE GROUND
TCC Curve Type TAP TAP
Min. Pickup (Amperes) 200 200
Inst. Pickup (kA) 5 1
Denite-Time Delay (ms) 32 32
Programming
S&C Instruction Sheet 695-515 13

View Relay Settings
The View Relay Settings option allows viewing of the current control settings for the
selected fault interrupter. The trip mode and frequency settings are included.
INTERRUPTER 1
PHASE GROUND
TCC Curve Type TAP TAP
Min. Pickup (Amperes) 200 200
Inst. Pickup (kA) 5 1
Definite-Time Delay (ms) 32 32
Trip Mode
Frequency
3
60
Press <ENTER> for menu
Change User
Password
The Change User Password option allows changing of the user password. After the new
password has been entered, the control will return to the main menu.
Step 1
Enter the current user password after the rst prompt.
Step 2
Enter the new password after the second prompt. The password must have four
numeric characters.
Step 3
To conrm the new password, re-enter it after the third prompt.
USER PASSWORD: ? * * * * *
CHANGE USER PASSWORD
Enter new password (four digits, blank for no change) * * * * *
Re-enter new password * * * * *
Group Configure Menu The Group Congure option allows viewing and changing of the global settings, chang-
ing of the Group Congure Password, and downloading of rmware.
Step 1
Select the desired option from the Group Congure menu and enter the corresponding
number after the “ > ” prompt. Press the Enter button. (Option 1 is shown as an example.)
Step 2
Refer to the appropriate subsection below for further information on the selected option.
Step 3
To return to the main menu, enter “9” after the “> ” prompt and press the Enter button.
Group Configure Menu: <select number>
1. Change global settings
2. View global settings
3. Change group configure password
4. Download firmware
9. Switch to main menu
=Group Config > 1
Programming
14 S&C Instruction Sheet 695-515

Change Global Settings
The Change Global Settings option allows changing of the fault interrupter ID, trip
mode, and frequency.
CAUTION
Do not program three-pole fault interrupters to operate in single-pole trip mode. Single-pole
tripping is not possible with three-pole fault interrupters.
Step 1
After each prompt, enter the new setting and press the Enter button. The available
choices are shown in parenthesis. To retain the previous selection shown after the “= ”,
press the Enter button.
Step 2
After all of the settings have been entered, the new settings will be displayed in a table.
Enter “Y” for the Yes option or “N” for the No option after the “Save Changes (Y/N)?”
prompt. A conrmation of the choice will be shown and the settings will be displayed.
<Press ‘Q’ to return to menu>
ID for Interrupter 1 (20 characters) = INTERRUPTER 1
?interrupter pole 1
ID for Interrupter 2 (20 characters) = INTERRUPTER 2
?interrupter pole 2
1-pole or 3-pole trip mode for Interrupter 1 (1,3) = 1 ?3
1-pole or 3-pole trip mode for interrupter 2 (1, 3) = 1 ?3
50 Hz or 60 Hz Operation (50, 60) = 60 ?
ID Interrupter 1 INTERRUPTER POLE 1
ID Interrupter 2 INTERRUPTER POLE 2
Trip Mode Interrupter 1 3
Trip Mode Interrupter 2 3
Nominal Frequency 60
Save Changes (Y/N)? n
SETTINGS NOT SAVED
ID Interrupter 1 INTERRUPTER 1
ID Interrupter 2 INTERRUPTER 2
Trip Mode Interrupter 1 1
Trip Mode Interrupter 2 1
Nominal Frequency 60
2. View Global Settings
The View Global Settings option allows viewing of the global settings including the fault
interrupter ID, trip mode, and frequency.
ID Interrupter 1 INTERRUPTER 1
ID Interrupter 2 INTERRUPTER 2
Trip Mode Interrupter 1 3
Trip Mode Interrupter 2 3
Nominal Frequency
Press <ENTER> for menu
60
Programming
S&C Instruction Sheet 695-515 15

Change Group Configure Password
The Change Group Congure Password option allows changing of the Group Cong-
ure Password. After the new password has been entered, the control will return to the
Group Congure Menu.
Step 1
Enter the current Group Congure Password after the rst prompt.
Step 2
Enter the new password after the second prompt. The password must have four numeric
characters.
Step 3
To conrm the new password, re-enter it after the third prompt.
CHANGE GROUP PASSWORD
Enter new password (four digits, blank for no change) * * * *
Re-enter new password * * * *
4. Download Firmware
The Download Firmware option allows the control to be disabled for downloading and
uploading of rmware. Refer to the nearest S&C Sales Ofce for instructions.
Test Trip Menu The Test Trip Menu option allows test tripping of the fault interrupters—all three poles or
single poles.
Step 1
Select the desired option from the Test Trip menu and enter the corresponding
number after the “ = ” prompt. Press the Enter button. The selected pole(s) will trip.
(Option 1is shown as an example.)
Step 2
To return to the main menu, enter “9” after the “= ” prompt, and press the Enter button.
Test Trip Menu
1. Trip Mode 3 FI1 All Poles INTERRUPTER 1
2. Trip Mode 3 FI2 All Poles INTERRUPTER 2
3. Trip Mode 1 FI1 Pole 1 INTERRUPTER 1
4. Trip Mode 1 FI1 Pole 2 INTERRUPTER 1
5. Trip Mode 1 FI1 Pole 3 INTERRUPTER 1
6. Trip Mode 1 FI2 Pole 1 INTERRUPTER 2
7. Trip Mode 1 FI2 Pole 2 INTERRUPTER 2
8. Trip Mode 1 FI2 Pole 3 INTERRUPTER 2
9. Switch to Main Menu
= 1
Programming
16 S&C Instruction Sheet 695-515

Self-Test Report
Viewing the Self-Test
Report
The Overcurrent control tests vital subsystems upon power up and periodically there-
after to ensure proper operation. To view the self-test report, select the View Relay
Self-Test option from the View menu for the selected fault interrupter.
INTERRUPTER 1
FID=S&C –1000 –R100 –970317
SELF TESTS
W = Warn F = Fail
Pole # 1 2 3
Trip Caps OK OK OK
Supply + 5V + 12V
Voltage 4.99 12.26
RAM FLASH CR_RAM EEPROM V_CONTROL
OK OK OK OK OK
Press <ENTER> for menu
Response to Self-Test
Failure
The following denes each of the self tests and the control’s response to a self-test
failure. The control displays the above screen example when none of the self-tests have
failed. Actual values may vary.
FID
The FID indicates the model, rmware version, and rmware date code.
Trip Caps
The status of the trip capacitors is reported for each fault-interrupter pole. If the trip
capacitors are not charged to at least 50 volts, a “low” condition is reported. The control
cannot issue a trip until the capacitors are fully charged. The capacitors charge from
either the CTs or port power. If the control indicates “low” when no trip condition exists,
the voltage supplied to the communication port is less than 4 volts or the control is defec-
tive and should be replaced.
Supply Voltage
The control periodically checks the voltage of each power supply and compares the
results with failure thresholds. The self-test report displays the measured values.
Protection is disabled and an “F” is placed next to the displayed value if it falls outside the
failure threshold. This self-test also detects gross A/D converter failures.
Threshold Values
Supply Low Fail High Fail
+ 5V
+ 12V
4.5
11.00
5.35
14.00
S&C Instruction Sheet 695-515 17

Self-Test Report
RAM
The RAM self-test veries proper operation of the read/write memory. This test periodi-
cally performs a nondestructive write/read to successive blocks of RAM to determine
whether a RAM failure has occurred. A failure occurs if the expected data are not read
back from the RAM. In this case, protection is disabled and “fail” is reported.
Flash
The Flash self-test veries the integrity of the data contained in system program Flash. If
Flash is corrupted, protection is disabled and “fail” is reported.
CR-RAM
Areas of RAM containing constant data that have been copied from EEPROM are periodi-
cally examined to verify their integrity. If this critical RAM has been corrupted, protection
is disabled and “fail” is reported.
EEPROM
The EEPROM self-test veries the integrity of data contained in EEPROM. EEPROM self-
test failures are handled differently because self-test failures and control settings are both
stored in EEPROM. Following an EEPROM self-test failure, factory-default settings are
restored and protection is enabled. The message “Relay enabled using default settings” is
displayed at the top of each menu. If the EEPROM failure persists (i.e., if default settings
cannot be stored in EEPROM), a self-test failure is also generated.
Voltage Control
This logic monitors the power shunt circuitry in the power supply. On power up, each
phase magnitude is averaged for 0.5 seconds. If the average is greater than or equal to 50
amperes and the associated trip capacitor is not charged, the CT power circuit is defec-
tive and a failure is declared.
Self-Test Failures
and Warnings
The following screen is an example of a self-test screen. The +5-volt power supply voltage
is agged with an “F”, and “Relay Disabled” appears above each menu.
The control records self-test failures in EEPROM and remains disabled until power
is removed and restored. When power is restored, the self-test is repeated. If no failure
occurs, the failure indication changes to “warn”—or “W” in the case of a power supply—
and protection is enabled.
INTERRUPTER 1
FID=S&C–1000 –R100 –970317
SELF TESTS
W = Warn F = Fail
Pole # 1 2 3
Trip Caps OK OK OK
Supply + 5V + 12V
Voltage 5.35F 12.12
RAM FLASH CR_RAM EEPROM V_CONTROL
OK OK OK OK OK
Press <ENTER> for menu
18 S&C Instruction Sheet 695-515

Specications
Port Power Input Voltage Range: 4.0 to 5.0 Vdc
Input Power: 1.8 W typical
CT Power Minimum current on any phase:
600-A models: 45 A RMS
Maximum current on all phases:
600-A models: 720 A continuous
12 kA for 1 s
25 kA for 0.25 s
Maximum measured current:
600-A models: 14.5 kA
Steady State Accuracy CT: ±0.2% typical
Burden Board: ±0.3% typical
Main Board: ±0.2% typical
Time-Overcurrent
Pickup Accuracy
E, K, Coordinating-Tap, and Coordinating-Main Curves:
−0 to +10%
Nominal pickup setting +5% typical
U.S. and IEC Curves:
±5 A primary and ±5% of setting
Time-Overcurrent
Response
E, K, Coordinating-Tap, and Coordinating-Main Curves:
−0 to +10% in terms of current OR
−0 to +20% in terms of time OR
−0 to +6 ms, whichever gives the greater allowed operating time
4 to 10 ms for currents greater than 2 times the current corresponding
to a 10 ms minimum response
U.S. and IEC Curves:
±1.5 cycles and ±10% of curve time for current between 2 and 30 multiples
of pickup, for faults not exceeding the maximum current rating
Instantaneous Pickup
Accuracy
600-A models: −0 to 10%
Instantaneous
Response
4 to 10 ms for currents greater than 2 times the instantaneous pickup setting
Definite-Time
Response
−0 to +8 ms
S&C Instruction Sheet 695-515 19

Appendix A
External Connections This section describes each of the external connections to the control. Included in
the following tables are terminal numbers, terminal names, mating-connector
part numbers (where applicable), and the pin-out of the data-port connectors.
Terminal numbers are identied by labels on the electronics module or terminal block.
Trip outputs
Electronics module
Trip Outputs
①
Terminal Number (1,2) Pole Mating-Connector Part Number
1, 2 Fault Interrupter 1, Pole 1
Phoenix 17839993, 4 Fault Interrupter 1, Pole 2
5, 6 Fault Interrupter 1, Pole 3
7, 8 Fault Interrupter 2, Pole 1
Phoenix 1876194
9, 10 Fault Interrupter 2, Pole 2
11, 12 Fault Interrupter 2, Pole 3
①Trips are polarized.
20 S&C Instruction Sheet 695-515
Other manuals for Vista SD
4
Table of contents
Other S&C Controllers manuals

S&C
S&C BankGuard PLUS Guide

S&C
S&C 5800 Series User manual

S&C
S&C Micro-AT User manual

S&C
S&C GridMaster User manual

S&C
S&C 6800 Series User manual

S&C
S&C Vista SD Owner's manual

S&C
S&C 6800 Series User manual

S&C
S&C IntelliCap Instruction Manual

S&C
S&C PMH Operation and maintenance manual

S&C
S&C TripSaver II User manual
Popular Controllers manuals by other brands

Epever
Epever MPPT user manual

ZyXEL Communications
ZyXEL Communications NXC-8160 release note

Mitsubishi Electric
Mitsubishi Electric FX3U-2HSY-ADP installation manual

Apex Digital
Apex Digital Cleco mPro4000GC installation instructions

Freescale Semiconductor
Freescale Semiconductor CPU32 Reference manual

PENGWYN
PENGWYN 485-1P-JS Technical manual