
12 • PerformanceAlert Gateway I&O Manual 026-1724 Rev 0 12-MAY-2008
For every board number used by the Perfor-
manceAlert™ Gateway, there will be sixteen rows in the
Input Status table corresponding to "points" 1 through 16
on the Gateway. To make a point ready for use by the E2,
you must set the input name and type from this screen.
Setup for Digital Points (1-12, 16)
1. Use the arrow keys until the cursor highlights
the Application field in the row correspond-
ing to the point you wish to set up.
2. Press A- SETUP
3. When prompted to select the data type, select
- Digital. The Digital Input setup screen
will be displayed.
4. In the Point Name field, enter a unique name
that will help you & others easily know the
function of this point. For example, if setting
up point 1 on board #3, which will be the
High DLT warning for PerformanceAlert™
module #3, an appropriate name would be
HIGH DLT CMP3.
5. Press Jto save the name and return to
the Input Status screen. The point will now
display a "D" (for digital) in the Type col-
umn, and will also display the current value
of the point in the Value field (ON or OFF).
6. Repeat steps 1 through 5 until all digital
points are defined.
Setup for Points 13 and 14 (Current Transducers)
1. Use the arrow keys until the cursor highlights
the Application field in the row correspond-
ing to the point you wish to set up.
2. Press A- SETUP
3. When prompted to select the data type, select
- Analog. The Analog Input setup screen
will be displayed.
4. In the Point Name field, enter a unique name
that will help you & others easily know the
function of this point. For example, if setting
up point 13 on board #3, which will be the T1
current for PerformanceAlert™ module #3,
an appropriate name would be T1 AMPS
CMP3.
5. In the Sensor Type field, press F4 to access
the Look-Up table. Highlight "Linear" as the
sensor type, and press >to select.
6. In the Select Eng. Units field, press F4 to ac-
cess the Look-UP table. Highlight "A" as the
unit type, and press >to select.
7. The Low Eng Units and High Eng Units
fields near the bottom of the screen must be
set to 0 and 655.5 respectively. The Low Eng
Units by default should read 0 and will not re-
quire modification. Move the cursor to the
High Eng Units field and enter 655.5 as the
new value.
8. Press Jto save the name and return to
the Input Status screen. The point will now
display a "A" (for digital) in the Type col-
umn, and will also display the current value
of the point in the Value field (ON or OFF).
9. Repeat steps 1 through 8 until all current
transducer points have been defined.
Setup for Point 15 (Discharge Line Temp)
1. Use the arrow keys until the cursor highlights
the Application field in the row correspond-
ing to the point you wish to set up.
2. Press A- SETUP
3. When prompted to select the data type, select
- Analog. The Analog Input setup screen
will be displayed.
4. In the Point Name field, enter a unique name
that will help you & others easily know the
function of this point. For example, if setting
up point 15 on board #1, an appropriate name
would be DLT CMP1.
5. In the Sensor Type field, press F4 to access
the Look-Up table. Highlight "Linear" as the
sensor type, and press >to select.
6. In the Select Eng. Units field, press F4 to ac-
cess the Look-UP table. Highlight "DF" (if
using °F on this E2) or "DC" (if using °C on
this E2) as the unit type, and press >to se-
lect.
7. Set the Low Eng Units and High Eng Units.
• If using °C (DC) as the unit, enter -50 as
the Low Eng Unit and 130 as the High Eng
Unit.
• If using °F (DF) as the unit, enter -58 as the
Low Eng Unit and 266 as the High Eng
Unit.
8. Press Jto save the name and return to
the Input Status screen. The point will now
display a "D" (for digital) in the Type col-
umn, and will also display the current value
of the point in the Value field (ON or OFF).
When finished, the points are ready for use in E2 appli-
cations. You may wish to use the Gateway points as inputs
for Analog and Digital Sensor control applications, where