ENDA EDP 741C User manual

DIGITAL POTENTIOMETER
ENDA
EDP 741
SET
1/3
OUTPUT
0-20mA output M igitally adjusted
Resolution : 2µA
Fluctuation : Maximum 0,1mA
Rise time from 0 to 20mA is maximum 300ms
aximum 20mA, d potentiometer output.
ENDA EDP 741C DIGITAL POTENTIOMETER
* 72x72mm sized.
* 4 digits display.
* Easy to use by front panel keypad.
* Display scale can be adjusted between -1999 and 8000.
* Decimal point can be adjusted between 1. and 3. digits.
* 0-20mA output with adjustable minimum and maximum values.
* ‘Soft on’ and ‘soft off’ properties can be selected.
* Parameter access protection on 3 levels.
* Easy connection by removable screw terminal.
* CE marked according to European Norms.
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Yukarı Dudullu Barbaros Cad. Kutup Sok. No:20 34775 - ÜMRANİYE/İSTANBUL-TÜRKİYE
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr EDP741C-E-03-R
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
Thank you for choosing ENDA EDP 741C potentiometer.
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
Ambient/storage temperature
Max. relative humidity
0 ... +50 °C/-25 ... +70°C (with no icing)
Rated pollution degree
TECHNICAL SPECIFICATIONS
80 up to 31 decreasing linearly 50 at 40 . % %°C °C
According to EN 60529 Front panel : IP65
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gases.
Supply 230V AC +10% -20%, 50/60Hz or 24V AC ±10%, 50/60Hz or optional 9-30V DC / 7-24V AC ±10% SMPS
Power consumption Max. 7VA
2.5mm² screw-terminal connections
Wiring
Date retention
EMC
Safety requirements
EN 61326-1: 2006
EEPROM (Min. 10 years)
EN 61010-1: 2010 (pollution degree 2, overvoltage category II, measurement category I)
ELECTRICAL CHARACTERISTICS
HOUSING
Housing type Suitable for flush-panel mounting according to DIN 43 700.
Dimensions W72xH72xD97mm
Weight Approx. 350g (after packing)
Enclosure material Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Order Code : EDP741C-
1
Supply Voltage
230VAC...230V AC
24VAC.....24V AC
SM...........9-30V DC / 7-24V AC
Output Type
0-20mA

TERMS
2/3 EDP741C-E-03-R
1) Mains supply cords shall meet the requirements of IEC 60227
or IEC 60245.
2) In accordance with the safety regulations, the power supply
switch shall bring the identification of the relevant instrument
and it should be easily accessible by the operator.
Note:
1) Adjusted potentiometer value is seen in run mode
Parameter name, value or its unit in programming mode.
3) Decrement key during run mode.
Decrement or parameter selection key during programming mode.
2) Increment key during run mode.
Increment or parameter selection key during programming mode.
4) Used for selecting menus in programming mode.
5) Used for selecting run or programming modes and for adjusting parameters.
DIGITAL POTENTIOMETER
ENDA
EDP 741
SET
4 digits 7 segment red LED display
( 2 ),( 3 ),( 4 ),( 5 ) Keypad
( 1 ) Digital display
14.2mm
Micro switch
Character height
ENDA EDP 741 is intended for installation in control panels. Make sure that the device is used only for intended purpose.
grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. The device
must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. All
input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be
close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be
according to the relevant locally applicable regulations.
The shielding must be
10
9
184-253V AC
50/60Hz 7VA
230V AC
Supply
Switch
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Neutral
Line
SUPPLY :
NOTE :
Fuse should
be connected
Holding screw
0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
Panel cut-out
Depth
97mm
75mm
84mm
68 mm
+0.7
68 mm
+0.7
2
Note 1) While panel mounting, additional distance required
for connection cables should be considered.
2) Panel thickness should be maximum 10mm.
3) If there is no 90mm free space at back side of the device,
it would be difficult to remove it from the panel.
- Push the flush-mounting
clamp in direction 1 as
shown in the figure left.
- Then, pull out the clamp in
direction 2.
For removing mounting clamps:
Connection
cables
Rubber packing
Flush mounting
clamp
Panel
1
2
1
72mm
78mm
DIGITAL POTENTIOMETER
ENDA
EDP 741
SET
DIMENSIONS
CONNECTION DIAGRAM
ENDA INDUSTRIAL ELECTRONICS
EDP741C-230VAC
POTENTIOMETER
230V AC +10% -20%
50/60Hz 7VA
SN: XXXXXXXXX
9
10
OUTPUT (0-20mA)
8
+
GND
4
3
8 680407 701872
Made in Turkey
ENDA INDUSTRIAL ELECTRONICS
EDP741C-24VAC
POTENTIOMETER
24V AC ±10%
50/60Hz 7VA
SN: XXXXXXXXX
9
10
OUTPUT (0-20mA)
8
+
GND
4
3
8 680407 701759
Made in Turkey

SET
SET
SET
&
SET
S.Cod.
Uo.sc.
D.Ca.s.
d.Pnt. =
Decimal point can be adjusted between
1. and 3. digits.
See NOTE 1 for programming.
Decimal point. s.Cod. = Access code for safety menu.
This parameter should be 222.
See NOTE 1 for programming.
s.Cod. = Access code for safety menu.
This parameter should be 333.
See NOTE 1 for programming.
Uo.Sc. = U.oPt.
parameter.
nonE = No menu is seen.
P. no = Menu is seen but can not be programmed.
P.yES. = Menu is seen and programming is possible.
See NOTE 1 for programming.
menu protection level
d.Ca.S. = d.CAL.
parameter.
nonE = No menu is seen.
P. no = Menu is seen but can not be programmed.
P.yES. = Menu is seen and programming is possible.
See NOTE 1 for programming.
menu protection level
L.SCL. = Lower value of the scale.
It can be adjusted between -1999 and (H.SCL. -100)
Output becomes 0,1mA at the adjusted value.
See NOTE 1 for programming.
Lo.Li. = Lower limit for preset value.
It can be adjusted between l.SCL. and
See NOTE 1 for programming.
Hi.Li.
H.SCL. = Upper value of the scale
It can be adjusted between (L.SCL. +100) and 8000.
Output becomes 20mA at the adjusted value.
See NOTE 1 for programming.
Hý.Lý. = Upper limit for preset value.
It can be adjusted between Lo.li. and H.SCl.
See NOTE 1 for programming.
S.Cod.
10CA/
First press and hold key. Then, by using keys, preset value can be adjusted.
d.Cal. SeCU.
D.Pnt.
l.sCl.
Lo.LI.
H.sCl.
HI.LI.
U.oPt.
10.CA. = calibration for 0-20mA output.
The device should be calibrated until
20.00mA is obtained at the output.
Calibration procedure is as explained below.
When key is pressed, previous calibration
value is seen. While holding key, calibration
value should be adjusted until 20.00mA is seen
at the output by using keys .
If key is released, calibration is exited. In the
mean time, the new calibration value is saved
in an EEPROM.
Programming mode
3/3
Run mode
Preset
value
1000 1000 1001 1002 1001
EDP741C-E-03-R
For adjusting a selected parameter first press and hold key. Then, by using keys, adjustment can be made.
Parameter adjustment method
NOTE 1
If increment key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly. If waited enough, th eValue increases
100 at each step. After 1 second following the release of the key, initial condition is returned. The same procedure is valid for the decrement key.
If first and then keys are pressed together.
programming mode is entered.
If o.E.t.Y and o.d.t.Y parameters is adjusted to any value except dSAb parameter,
output can be controlled with and buttons.
D.o.sc.
d.o.Sc. = d.oPt.
parameter.
nonE = No menu is seen.
P. no = Menu is seen but can not be programmed.
P.yES. = Menu is seen and programming is possible.
See NOTE 1 for programming.
Menu protection level
P.on.C.
o.e.ty.
R.ti.
o.d.ty.
D.tI.
D.oPt.
P.on.C. = Control parameter when first energized
ofF= When first energized, output is the current
that lower limit value is indicated.
Attention: If this parameter is selected,
the set value that was adjusted before is seen
when set button is pressed at first. In addition,
if increasing or decreasing that value is wanted
the set value is equalized to lower limit value and
then adjustment can be done.
on= When first energized, output is the current
that the set value is indicated.
S.Str.= When first energized, output is increased
slowly from the current that lower limit value
is indicated to the current that set value is indicated
during r.ti.
See NOTE 1 for programming.
.
D.ti. = decreasing time for output.
It is adjusted between 1 and 250 seconds.
Output current is decreased slowly to the lower limit value during
adjusted time.
See NOTE 1 for programming.
P.on.C.
o.d.ty.
o.E.ty.
Lo.lý.
Lo.lý.
off
Dsab.
Dsab.
on
Enb.
R.ti.
R.ti.
Enb.
S.str.
S.off.
S.on.
PRESET
PRESET
Control isn’t done
with buttons. by pressing
the button
0,1mA
Power
Out
Out
On
D.ti.
o.e.ty. = Adjusted type of the output to
with button.
dSAb. = Output cannot be adjusted to preset value with
button.
Enb. = Output can be adjusted to preset value with
button.
S.on. = Output is increased to voltage that set value is
displayed with button during r.ti. .
See NOTE 1 for programming.
preset value
o.d.ty. = Adjusted type of the output to lower limit value
with button.
dSAb. = Output cannot be adjusted to lower limit value with
button.
Enb. = Output can be adjuested to lower limit value with
button.
S.oFF. = Output is increased to voltage that lower limit
value is displayed with button during d.ti. .
See NOTE 1 for programming.
R.ti. = increasing time for output.
It is adjusted between 1 and 250 seconds.
Output current is incerased slowly to the set value during adjusted time.
See NOTE 1 for programming.
by pressing
the button
by pressing
the button
by pressing
the button
P.I.d.t.
P.i/d/t/ = increasing and decreasing speed of preset value.
It is adjusted between 1 and 3. P.i.d.t. = 1, set value changes
one by one. P.i.d.t. = 2, set value changes 10 at each step.
P.i.d.t. = 3, set value changes 100 at each step.
See NOTE 1 for programming.
&
SET
SET
SET
&
SET
SET
SET
.
This manual suits for next models
1
Other ENDA Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Apache
Apache STORM Operator's manual

zatech
zatech ZMCE 1.1AD manual

Endress+Hauser
Endress+Hauser Analytik Jena Multi X 2500 operating manual

Fleetminder
Fleetminder MDVR8AHD-4G Installation and user guide

PCB Piezotronics
PCB Piezotronics 357B04 Installation and operating manual

PCE Health and Fitness
PCE Health and Fitness PCE-CP Series user manual