8. USER MENU
Enter the user menu: Select with the joystick.
Maintain the joystick on the left direction for 5 seconds.
Select the parameter you want to adjust with the joystick
Conrm selection by pressing the joystick
The current value is blinking. Now you can adjust the value with the joystick
Save by pressing the joystick
Restore the factory setting for the selected parameter by pressing the return button
Parameter User menu
No Name Parameter description Factory setting Alternative
setting
01 SEnS Sensor selection Sens Air Only
Internal sensor
Sens Flor Only*
External sensor
02 CAL
Air
Calibrate internal sensor.**
Procedure: Before calibration, operate the thermo-
stat with same temperature setting for at least one
day. Put a thermometer at the same height as the
thermostat (approx. 1.5 m above the oor) and give it
enough time to stabilize. Press the joystick and enter
the value that is read out from the thermometer. Save
by pressing the joystick.
Note! The heating element managed by the thermo-
stat must be in operation during the calibration.
no
Not calibrated done
Calibrated
03 CAL
SoL
Calibrate external sensor.
Procedure: Before calibration, operate the thermo-
stat with same temperature setting for at least one
day. If the external sensor is used as oor sensor, put
the thermometer on the oor and give it enough time
to stabilize. Press the joystick and enter the value that
is read out from the thermometer. Save by pressing
the joystick.
Note! The heating element managed by the thermo-
stat must be in operation during the calibration.
no
Not calibrated
done
Calibrated
04 1rst
Heat
Drying function for concrete oors.
When activated, this function starts a drying program
that lasts for 21 days. During the rst 24 hours the
heating is on 2 hours totally. For each following day,
another 1 hour of heating is added. The temperature
is limited to 20 ⁰C during the program. The function is
not stopped due to possible power breaks.
no
Not activated
21
Activated
05 LoAd
Connected load [W] to the thermostat.
Connect max. 2300W load, when the internal sensor
is selected.
If you connect a load 2300W - 3600W, use an exter-
nal power relay (contactor). Adjust the parameter to
“0000”.
1500
Adjustable 0to
2300 in steps
of 50
09 End Exit the user menu.
The program version is displayed. Press the joystick