Erreka VIVO-M203 Operating instructions

9
VIVO-I103(M)/ VIVO-I203(M)
Quick installation and programming guide English
WARNING
This quick guide is a summary of the complete installation manual. The manual contains safety warnings and
other explanations which must be taken into account. The most recent versions of this guide and the
installation manual are available at the "Downloads" section on Erreka's website.
http://www.erreka-automation.com
The options and functions described in this guide apply for the firmware version indicated on the circuit. The
firmware, as part of a process of continuous improvement, is subject to new functionalities or upgrades being
included as a result of new versions which are not necessarily compatible with previous ones. For this reason,
some options or functions may differ or be unavailable if your firmware is older than shown in this guide.
Electrical wiring
A: Main power supply
B/F: Flashing light with antenna
C: Photocells (Rx/Tx)
D:Keyswitch
E:Operator
Elements of the complete installation
NOTE: this control panel is valid for operators
for the following types of door and gate:
swing (C301),
sliding (C302),
up-and-over (C303).
VERY IMPORTANT: the TC closing stopper and the TA
opening stoppers must be installed.
VIVO-I203:
VIVO-I203M:
230V, 50-60Hz
125V, 50-60Hz
S.EXT./
S.CIE.
S.INT./
S.APE.
A.P./C.
A.T./A.
P294Z2
F2
F1
DL27
JP1
3~
M
1~
M
JP1
Pos 1
Pos 2
230V
230V
Power supply and peripheral cabling (valid for all cases)
(resistive)
(resistive)
F1: 3A fuse
F2: 0.5A fuse
DL27: LED Continuous
Bus
EPS1: traffic light card
(with parameter Ab00) or
brake card (with
parameter Ab01, see
connection diagram on
page 12). See other
options on page 16.
See the Display
indications on
page 12.
MSA-115/00 Firmware V0.15 or later

10
VIVO-I203:
VIVO-I203M:
DL27
G2
G1
G3
P294Z3
DS1
DS9
DS4
DS12
Operator connections for swing gates
with single or double leaf (parameter C301)
Operator connection
Single encoder connection
(C701)Limit switches connection
(C702)Dual encoder connection
(C703)Vulcan connection
VUS (C705)
V+:redwire V+: do not connect V+:redwire V+: do not connect
GND: screen GND:common(COM) GND: screen GND:common(COM)
SGN1: green or blue wire SGN1: opening (FCA) SGN1: green or blue wire SGN1: VUS operator safety
micro
SGN2: do not connect SGN2: closing (FCC) SGN2:whitewire SGN2: electrolock micro
(in A1 connector only)
G1: open
G2:close
G3: common
The C704 option is not available for swing gate operators. If C704 is
selected, it will work as C701.
A1: operator 1
A2: operator 2
DS9: SNG1 LED (FCA/encoder) A1
DS12: SNG2 LED (FCC/encoder) A1
DS1: SNG1 LED (FCA/encoder) A2
DS4: SNG2 LED (FCC/encoder) A2
Do NOT
connect the
capacitor in
the motor.

11
VIVO-I203:
VIVO-I203M:
DL27
G2
G1
G3
P294Z4
DS1
DS9
DS4
DS12
Operator connections for sliding gates and up-and-over doors
(parameters C302 and C303)
Operator c onnection
Single encoder
connection (C701)
Limit switches
connection (C702)
Dual encoder
connection (C703)FC and single encoder connection (C704)
Connector E1: Connector E2: Connector E1: Connector E1: Connector E2:
V+:redwire V+: do not connect V+:redwire V+:redwire V+: do not connect
GND: white wire GND:
common (COM)
GND:whitewire GND:whitewire GND:
common (COM)
SGN1: green or blue
wire SGN1: opening (FCA) SGN1: green or blue
wire SGN1: green or blue
wire SGN1: opening (FCA)
SGN2:
do not connect
SGN2: closing (FCC) SGN2:purplewire SGN2:
do not connect
SGN2: closing (FCC)
G1: open
G2: close
G3: common
In sliding gates (C302) and up-and-over doors (C303) it is only possible to use a single
motor (M1), which should be connected to the “MOTOR 1” cable connectors.
When using a single encoder (C701, C704) or dual encoder (C703), always connect it to
the “ENCODER 1” cable connectors.
When using limit switches (C702, C704 or C705), always connect to the “ENCODER 2”
cable connectors.
A1: operator 1
E1:
“ENCODER 1” cable connectors
E2:
“ENCODER 2” cable connectors
ATLAS Connection (ATS) G6xxI (C705)
Connector E2:
V+: do not connect
GND: common (COM)
SGN1: ATS operator safety micro and NA
closing micro (parallel connection)
SGN2: bridge with GND
DS9: SNG1 LED (encoder) E1
DS12: SNG2 LED (encoder) E1
DS1: SNG1 LED (FCA/ATS) E2
DS4: SNG2 LED (FCC/NA) E2
Do NOT
connect the
capacitor in
the motor.

12
P294Z5
Brake connections
DL1: Red LED, FR1 activation
DL2: Green LED, FR2 activation
If the operator is fitted with a brake connected internally to the motor (for example, ORION operators), it is
not necessary to connect the brakes, although slowdown should be cancelled (select CA00).
If the operator is fitted with a brake for
independent connection (for example, CICLON
or MAGIC operators), the EPS1 card should be
used as shown in this diagram, selecting
parameter Ab01.
The display shows a horizontal segment in D4 whenever no
key is pressed for 15 minutes. This will come on when
pressing either of the ESC, ENTER buttons.
D1 and D2 (gate status):
CL (static) Gate closed
CL (flashing) Gate closing
OP (static) Gate open
OP (flashing) Gate opening
PC (flashing) Pedestrian door closing
PO (static) Pedestrian door open
PO (flashing) Pedestrian door opening
XX (countdown) Gate on standby
PA (static) Pause (operation not complete)
rS (static) Gate resetting (searching for closing or
opening position)
HP (static) Dead Man function
Display indications
In swing gates, C4 refers to the interior
photocell and C5 to the exterior photocell
(instead of opening and closing,
respectively).
D3 and D4 (during operation):
88ºÂ8FT1 enabled 888ºÂ FT2 enabled
88º@8
Green traffic light enabled
888º@ Flashing light
88º+8FCA A1 enabled 888º+ FCA A2 enabled
88º?8Radio order (not RSD) 888º? RSD Radio signal (frame)
88º-8FCC A1 enabled 888º- FCC A2 enabled
88º¨8ST1 enabled 888º¨ ST2 enabled
88ºâ8Red traffic light enabled 888ºâ LG enabled
º.888 Inverter 1 module 8º.88 Inverter 2 module
88º.8Operator 1 encoder 888º. Operator 2 encoder
D3 and D4 (error messages):
C4 Opening safety device enabled
C5 Closing safety device enabled
C9 Mechanical or resistive strip enabled
E1 Motor 1 encoder failure
E2 Motor 2 encoder failure
F1 Motor 1 force limit exceeded
F2 Motor 2 force limit exceeded
StOP Operator unlocked
HEAt Excessive heating inverter modules
COç1 Inverter module 1 communication failure
COç2 Inverter module 2 communication failure
M294C
Gate type selection (C3)
P294B
2
P294C
3
P294D
4
P294E
5
P294G
7
P294H
8
6 Select gate type:
C301: swing
C302: sliding
C303: up-and-over
Press ENTER
1 Press ENTER, with the
display showing CL88 or
rSXX (rSºÂ8, rSºâ8,rS8º@,
rS8º?, etc).

13
Operator number selection (C0); in swing gates only (C301)
N294C
3
N294D
4
N294F
6
1 Press ENTER, with the
display showing CL88 or
rSXX (rSºÂ8, rSºâ8,rS8º@,
rS8º?, etc).
P294B
2
P294H
8
N294G
7
N294E
5
Change and check of A1 operator turning direction (C1)
R294C
3
R294D
4
R294E
5
R294K
10
This operation is only necessary if operator A1 closes the leaf instead of opening it when resetting (rS).
In step 7 - 8 , check turning direction using UP (open) and DOWN (close). C1 is used to activate operator 1 and
C2 is used to activate operator 2.
Change and check of A2 operator turning direction (C2)
R294I
9
1 Press ENTER, with the
display showing CL88 or
rSXX (rSºÂ8, rSºâ8,rS8º@,
rS8º?, etc).
P294B
2
R294F
6
R294G
7
R294H
8
This procedure is the same as for operator A1, but using parameter C2 instead of C1.
I
II
S294F
6
Total opening radio code programming P1 (with RSD receiver only, C801)
If a receiver other than RSD is used, see the corresponding instructions.
Select the C801 option (RSD receiver) before starting programming.
Pedestrian opening radio code programming, P2 (with RSD receiver only)
This procedure is the same as for total opening, but using parameter P2 instead of P1.
1 Press ENTER, with the
display showing CL88 or
rSXX (rSºÂ8, rSºâ8,rS8º@,
rS8º?, etc).
S294B
2
S294E
5
S294C
3
S294D
4
S294G
7
P294H
8

14
Gate open/close programming (all cases)
8 Start opening of leaf 1
with ST1:
I
II
U29
4
9 Start slowdown of leaf 1
with ST1
(only with
CA01
or
CA02
):
I
II
U294I
10 Finish opening of leaf 1 with ST1:
In any case, this is carried
out automatically when
the opening stopper
(with C701, C703, C704
or C705) or the FCA
(with C702 or C704) is
reached.
I
II
U294J
11 Start opening of leaf 2
with ST1:
I
II
U294K
12 Start slowdown of leaf 2
with ST1
(only with
CA01
or
CA02
):
I
II
U294L
13 Finish opening of leaf 2 with ST1:
In any case, this is carried
out automatically when
the opening stopper
(with C701, C703, C704
or C705) or the FCA
(with C702 or C704) is
reached.
I
II
U294M
14 Start closing of leaf 2
with ST1:
I
II
U294N
The anti-trapping safety system continues to
run during programming operations.
Pedestrian opening is programmed using F3,
meaning the travel for this pedestrian opening
does not need to be programmed.
If an obstacle is detected during programming
in up-and-over operation with C5 Closing
photocell enabled, this will be considered the
point from which the photocell shadow
function should be enabled. This only works
with Collective Opening (A901).
The opening and closing stopper must be installed before programming the travel (see the
operator manual).
15 Start slowdown of leaf 2
with ST1
(only with
CA01
or
CA03
):
I
II
U294R
16 Finish closing of leaf 2 with ST1:
In any case, this is carried
out automatically when
the closing stopper (with
C701, C703 or C704) or
the FCC (with C702,
C704 or C705) is
reached.
I
II
U294S
17 Start closing of leaf 1
with ST1:
I
II
U294T
18 Start slowdown of leaf 1
with ST1
(only with
CA01
or
CA03
):
I
II
U294U
19 Finish closing of leaf 1 with ST1:
In any case, this is carried
out automatically when
the closing stopper (with
C701, C703 or C704) or
the FCC (with C702,
C704 or C705) is
reached.
I
II
U294V
The procedure with a
swing gate is shown
below.
Proceed in the same
manner for sliding gates or
up-and-over doors.
With encoder and/or obstacle detection
and/or limit switches, the gate carries out
the approach operation (opening for 4
seconds and then closing to programme the
closing point). It also carries out slowdown
in accordance with the value CA.
In other cases, close the gate before starting
programming.
6
1 Press ENTER, with the
display showing CL88 or
rSXX (rSºÂ8, rSºâ8,rS8º@,
rS8º?, etc).
S294B
2
S294C
3
T294D
4
T294E
5
T294H
7
T294R
22
T294P
21
20 The parameter
A6XY is shown
once programming
is complete,
indicating the
suggested currents
for Motor 1 (X) and
Motor 2 (Y). These
can be changed if
required.

15
D1 D2 Parameter D3 D4
Pre-set
option
Options or values
C0Number of operators 01, 201
(VIVO-I103)
02
(VIVO-I203)
01: one operator,
02: two operators (only available with C301)
1Operator 1 turning direction
(operator 2 also changes) 01, 20101: direction A, 02: direction B. Check direction by
pressing UP (open) and DOWN (close)
2Operator 2 turning direction
(operator 1 also changes) 01, 20101: direction A, 02: direction B. Check direction by
pressing UP (open) and DOWN (close)
3Type of gate 01...30101: swing, 02: sliding, 03: up-and-over
4Opening safety device
(photocell) 0,10,10000: not installed,
10: no testing, 11: with testing
5Closing safety device (photocell)
Closing photocell with C520 or
C521, also prevents the start of
gate opening
0...20,10000: not installed,
10: no testing,
11: with testing,
20: no testing,
21: with testing
6Electrolock / electromagnet
C630 and C640 are used to
manage an external relay at
24Vdc, connected to cable
connectors P11-P12. The
electromagnet must be
externally supplied (through this
relay) and sized in line with the
electromagnets used.
0...40...40000: not installed
1X: electrolock without reverse impulse.
Programmable electrolock time: 3 seconds
with X=0(by default), 3.5s with X=1, 4s with
X=2, 4.5s with X=3, 5s with X=4.
2X: electrolock with reverse impulse.
Programmable time (electrolock/motor
reverse): 4.5/1.5 seconds with X=0(by default),
5/2s with X=1, 5.5/2.5s with X=2, 6/3s with
X=3, 6.5/3.5s with X=4.
30: electromagnet without impulse
40: drop electromagnet
7Encoder / Limit switches
The connections depend on the
type of operator selected (C301,
C302 or C303); see the
corresponding wiring diagram)
00...50000: not installed; 01: with single encoder;
02: with limit switches;
03: with dual encoder;
04: with encoder and limit switches (not available
with C301 selected);
05: VULCAN VUS and ATLAS (ATS) G6xxI (only
available with C301 or C303 selected)
8Radio card 01, 20201: RSD card (non-decoding);
02: two-channel decoder card
9Safety strip 01, 20101: mechanical; 02: resistive 8k2
ASlowdown 00...30100: no slowdown;
01: slowdown in opening and closing;
02: slowdown in opening;
03: slowdown in closing
P1
Total opening radio programming
oç Programmes total opening code and channel
2Pedestrian opening radio
programming oç Programmes pedestrian opening code and channel
3Gate open/close programming oç Programmes the operations in accordance with
configuration CA
F1Key command using ST1 and
ST2 pushbuttons.
With
F101
the gate (total or
pedestrian) can be kept open by
keeping ST1 or ST2 pressed down
respectively. This allows the time
scheduler to be used in combination
with
F2
and/or
F4
K
00
.
00...40100: ST1 and ST2 without effect, key commands are
made by radio (channel 1: total opening-
closing, channel 2: pedestrian opening-closing)
01: ST1 total opening-closing, ST2 pedestrian
opening-closing
02: ST1 total opening, ST2 total closing
03: dead-man mode (the display shows HP);
04: dead-man mode in closing
2Automatic or step-by-step
operation mode and standby
time (in seconds) in automatic
mode
0..5.0...90000: step-by-step mode
01: automatic mode and stand-by time 1 second;
...
59: automatic mode and stand-by time 59 sec.;
1.0: 1 min. 0 sec.;
...; maximum 4 minutes
3Pedestrian opening (%) 0...90...94000: pedestrian opening is not carried out,
10: 10% of the total opening, etc
4Pedestrian closing mode 0...50...90000: step-by-step mode
01: automatic mode and stand-by time 1 second;
...
59: automatic mode and stand-by time 59 sec.;
1.0: 1 min. 0 sec.;
...; maximum 4 minutes
Complete programming table (I)

16
Complete programming table (and II)
D1 D2 Parameter D3 D4
Pre-set
option
Options or values
A0Flashing light 01, 20101: without pre-warning
02: with pre-warning
1Garage light time 0...5.0...90303= 3 sec.; 59 = 59 sec.; 2.5= 2 min. 50 sec.;
....; maximum 4 minutes
2Gate speed
The open/close run must be
reprogrammed whenever this
parameter is changed
01...90301: minimum speed (40Hz);
02: 45Hz, 03: 50Hz, 04: 55Hz, ...;
09: maximum speed (80Hz)
3Slowdown speed
The open/close run must be
reprogrammed whenever this
parameter is changed
01...90301: minimum speed (21Hz);
02: 22Hz, 03: 23Hz, 04: 24Hz, ...;
09: maximum speed (29Hz)
5Reverse after closing (prevents the
operator from seizing up on the
stopper)
00...50000: no reverse;
...;
05: maximum reverse
6Maximum entrapment current
(each value equivalent to 0.5A).
This only works in
electromechanical operators.
Digit D3 can be used to set the
current of operator 1;
Digit D4 can be used to set the
current of operator 2
0...90...900
00
: disabled;
01: disabled in operator 1 and 0.5A in operator 2;
10: 0.5A in operator 1 and disabled in operator 2;
….;
65
: 3A in operator 1 and 2.5 in operator 2;
…;
99
: 4.5A in operator 1 and in operator 2
7Crossing over photocell (opening
or closing) during stand-by (in
automatic mode only)
00...20200: does not affect stand-by time
01: immediate close when the photocells are released
02: restarts standby time
8Effect of ST1-ST2 pushbuttons
during stand-by time (in automatic
mode only)
00...20200: have no effect during stand-by
01: produce immediate closing
02: restart stand-by time
9Opening mode 01...30201: collective opening
02: step-by-step alternative stop
03: automatic alternative stop (if F200 is selected,
A903 becomes A902)
ALapse between leaves in opening
and closing 0...90...92200: no lapse in opening or closing (apply only in gates
with no overlap);
XY:Xlapse in opening
(X=1: 1 second, ... , X=9: 9 seconds)
Ylapse in closing
(Y=1: 1 second, ... , Y=9: 9 seconds)
bUsing the EPS1 card connector
For parameters Ab02 and Ab03,
use the EPS1 card and bridge the
network input cable connectors
instead of connecting them to the
network (see “Brake connection”
diagram)
00...30000: use for standard traffic light;
01: use for brakes
02: NC contact with gate open (L1-COM) and gate
closed (L2-COM)
03: impulse 1 second Open (L1-COM) when starting
opening and Close (L2-COM) when starting
closing. Allows another panel to be enabled
CHydraulic pressure maintenance 00
...60000: no pressure maintenance;
01: every 0.5 hours; 02: every 1 hour;
03: every 2 hours; 04: every 6 hours;
05: every 12 hours; 06: every 24 hours
dHammer 00,10000: no hammer; 01: with hammer
ESpecial functions 00...20000: no special function;
01: opening photocell C4 programmed for pedestrian
crossing;
02: industrial;
N0Programming lock key
Be sure to remember any key used,
for future access to the
programming
00,10000The preset option is 0000 (no key). If any figure is
changed, this is considered key.
Select the required key (starting with D1) using UP
and DOWN. Press ESC to cancel or ENTER to confirm
and move to D2, and so on.
1Total operations completed XX Indicates the hundreds of cycles completed (for
example, 68 indicates 6800 cycles completed)
2Partial operations completed XX Indicates the hundreds of cycles completed. It can be
reset by pressing ST1, ST2 and ENTER simultaneously.
t0FTP communication Oç Immediate communication with the server
1GSM signal strength XX Indicates signal strength
Other manuals for VIVO-M203
3
This manual suits for next models
3
Table of contents
Other Erreka Control Panel manuals

Erreka
Erreka CLEVER02 User guide

Erreka
Erreka VIVO-D102 User guide

Erreka
Erreka CLEVER03 Operating instructions

Erreka
Erreka ABC2M-009 User guide

Erreka
Erreka EP1-008 User manual

Erreka
Erreka VIVO-M203 User manual

Erreka
Erreka CLEVER01 User guide

Erreka
Erreka CLEVER01 Operating instructions

Erreka
Erreka SMART-D201 Operating instructions

Erreka
Erreka VIVO-D203 Operating instructions