
EVCO S.p.A. | Code 1043S205E104 | Page 2 of 8 | PT 04/15 | version 1.0
Alternatively:
6.2 Touch the key.
If the evaporator probe is absent (parameter P3 = 0), the
label “Pb2” will not be displayed.
3.5 Condenser temperature display
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Touch the key down for 1 s: the display will
show the first label available.
3. Touch the key or the key to select
“Pb3”.
4. Touch the key.
To exit the procedure:
5. Touch the key or do not operate for
60 sec.
6.1 Touch the key or the key until the
display shows the cell temperature or do not operate
for 60 sec.
Alternatively:
6.2 Touch the key.
If the third input function is that of the digital input (parameter
P4 = 0), the label “Pb3” will not be displayed.
3.6 Defrosting activation in manual mode
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Touch the key down for 4 s.
If the evaporator probe function is that of the defrosting
probe (parameter P3=1) and upon activation of defrosting,
the temperature of the evaporator is higher than that
established with parameter d2, the defrosting function will
not be activated.
3.7 Switch-on/off of the cell light in manual
mode (only if parameter u1
and/or parameter u11 is set at 0)
1. Make sure no procedures are in progress.
2. Touch the key: the “AUX” LED will switch on/
off.
Using the door digital inputs it is also possible to switch on/
off the cell light by remote; see also parameter u2.
If the u1 parameter is set at 0 (or the fourth output manages
the cell light), check that the u11 parameter is set to values
other than 0,1 and 2 (and vice-versa)
3.8 Switch-on of demister resistors (only if
parameter u1 and/or parameter u11 is set at 1)
1. Ensure that the device is switched on and that no other
procedure is in progress.
2. Touch the key down for 2 s: the “AUX” LED will
light up and the resistors will be switched on, both for
the amount of time established with parameter u6.
Manually switching off the demisting resistors is not permit-
ted (that is, before the time established with parameter u6
expires).
If the u1 parameter is set at 1 (or the fourth output manages
the demisting resistors), check that the u11 parameter is set
to values other than 0, 1 and 2 (and vice-versa)
3.9 Switch-on/off of auxiliary output in manual
mode (only if parameter u1 and/or parameter
u11 is set at 2)
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Touch the key: the “AUX” LED will switch on/
off.
Using the digital inputs it is also possible to remotely switch
on/off the auxiliary output.
If the u1 parameter is set at 2 (or the fourth output manages
the auxiliary output), check that the u11 parameter is set to
values other than 0, 1 and 2 (and vice-versa)
If the auxiliary output has been turned on manually, it shall
be possible to turn it off only in the same mode (similarly, if
it was turned on from remote, it shall be possible to turn it
off only from remote); see also parameter u2.
3.10 Locking/unlocking the keyboard
To lock the keyboard:
1. Make sure no procedures are in progress.
2. Do not operate for 30 s: the display shall show “Loc”
for 1 s and the keyboard shall lock automatically.
If the keyboard is locked, the following are not permitted:
- device switch-on/off in manual mode
- display of evaporator temperature (via the procedure
explained in paragraph 3.4)
- display of the condenser temperature (via the proce-
dure indicated in paragraph 3.5)
- manual activation of defrosting
- manual switch on/off of the auxiliary output
- see information regarding the HACCP alarms
- cancellation of HACCP alarm list
- display of compressor operation hours
- cancellation of compressor operation hours
- changing the working set-point (with the procedure
described in 8.1).
The operations cause the display of the label “Loc” per 1
sec.
To unlock the keyboard:
1. Touch a key down for 1 s: the display will show the
message “UnL” for 1 sec.
3.11 Silencing the buzzer
To lock the keyboard:
1. Make sure no procedures are in progress.
2. Touch a key (the first pressing of the key will not cause
the effect associated with that key).
If parameter u1 and/or parameter u11 is set at 3 (or if the
fourth output and/or the fifth output manage the alarm
output) and parameter u4 is set at 1, pressing the key will
also cause the deactivation of the output.
If parameter u9 is set to 0, the buzzer will not be activated.
3.12 Activation/deactivation of “overcooling”
function
1. Make sure that the keyboard is not locked and that no
other operation is in progress, that defrosting and/or
dripping is not in progress and that the evaporator fan
is off.
2. Hold the key down.
During the “overcooling” function the working set-point is
reduced by the temperature established with parameter r5;
the operation lasts for the amount of time established with
parameter r6.
During “overcooling” defrosting is never activated; if the
defrosting interval expires when the function is in progress,
defrosting will be activated at the end of the function.
4 ENERGY SAVING
4.1 Preliminary notes
Once the time you have set with parameter i10 has passed,
without activations of the door microswitch input (after the
cell temperature has reached the work set-point) the “en-
ergy saving” function is activated (until the input is activated
again).
During function “Energy Saving” the working set-point is
increased of the temperature you have set with parameter
r4 and the evaporator fan is turned on cyclically (parameter
F13 sets the time the fan remains turned off and parameter
F14 the time it remains turned on).
It is also possible to activate the “energy saving” function in
remote mode through the digital inputs (with effect only on
the compressor).
5 “HACCP” FUNCTION
5.1 Preliminary notes
The device can memorise the following HACCP alarms:
- minimum temperature alarm (code “AL”)
- maximum temperature alarm (code “AH”)
- door microswitch input alarm (code “id”)
The device supplies the following information for every alarm:
- the critical value
- the duration of the alarm (from 1 min to 99 hours and
59 min, partial if the alarm is in progress).
Code Critical value
AL the minimum temperature of the cell during any
alarm of this type
AH the maximum temperature of the cell during any
alarm of this type
iD the maximum cell temperature during any alarm
of this type; see also parameter i4
The device stored the minimum temperature alarm on con-
dition that the temperature associated to the alarm is that of
the cell (parameter A0 = 0).
if the device is switched off, no alarms will be stored.
The device updates the information regarding the alarms
provided the critical value of the new alarm is more critical
than that stored or provided the information has already
been displayed.
The “HACCP” LED provides information regarding the stor-
age status of the alarms; see paragraph 9.1.
5.2 Display of HACCP alarm information
To begin the procedure:
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Touch the key down for 1 s: the display will
show the first label available.
3. Touch the key or the key to select
“LS”.
4. Touch the key: the display will show one of the
codes included in the table in paragraph 5.1.
If the device does not have any alarms stored, the label
“LS” will not be displayed.
To select an alarm:
5. Touch the key or the key (to select,
for example, “AH”).
To see information regarding the alarm:
6. Touch the key: the HACCP LED will stop flashing
and remain on permanently and the display will show,
for example, the following information in succession
(for example):
Inform. Meaning
8,0 the critical value is 8,0 °C/8 °F
dur the display is about to show the alarm duration
h01 the alarm lasted for 1 hour (other data continues)
n15 the alarm lasted 1 hour and 15 min
AH the alarm selected
the displays each piece of information for 1 s.
To exit the information sequence:
7. Touch the key: the display will show the alarm
selected (in the example “AH”).
To exit the procedure:
8. Exit the information sequence.
9.1 Touch the key or the key until the
display shows the cell temperature or do not operate
for 60 sec.
Alternatively:
9.2 Touch the key.
5.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Touch the key down for 1 s: the display will
show the first label available.
3. Touch the key or the key to select
“rLS”.
4. Touch the key.
5. Touch the key or the key within 15 s to
set “149”.
6. Touch the key or do not operate for 15 sec: the
display will show a flashing “- - - -” for 4 sec and the
“HACCP” LED switches off, after which the device will
exit the procedure.
If the device does not have any alarms stored, the label
“rLS” will not be displayed.
6 COMPRESSOR OPERATING HOURS COUNT
6.1 Preliminary notes
The device can memorise up to 9.990 compressor operating
hours.
The parameter C10 establishes the number of operating
hours is higher than the limit at which the need for mainte-
nance is signalled.
6.2 Display of Compressor Operation Hours
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Touch the key down for 1 s: the display will
show the first label available.
3. Touch the key or the key to select
“CH”.
4. Touch the key.
To exit the procedure:
5. Touch the key or do not operate for
60 sec.
6.1 Touch the key or the key until the
display shows the cell temperature or do not operate
for 60 sec.
Alternatively:
6.2 Touch the key.
6.3 Cancelling the HACCP alarm list
1. Make sure that the keyboard is not locked and that no
procedure is in progress.
2. Touch the key down for 1 s: the display will
show the first label available.
3. Touch the key or the key to select
“rCH”.
4. Touch the key.
5. Touch the key or the key within 15 s to
set “149”.
6. Touch the key or do not operate for 15 sec: the
display will show “- - -” flashing for 4 sec, after which
the device will exit the procedure.
7 DEFROSTING SYNCHRONISATION (ONLY IF
PARAMETER i0 AND/OR PARAMETER i5 ARE
SET AT 6)
7.1 Preliminary notes
Activating the defrost function causes the activation of the
digital input (not for longer than the maximum time set with
parameter d24 or until the end of the pre-dripping).
If the digital input is connected in parallel to the digital input
of other devices configured in the same way, the activation
of the input shall cause the activation of the defrost function
in the other devices.
The devices launch the dripping function at the same time as
last device concludes the pre-dripping.