FAAC KP CONTROLLER User manual

KP
CONTROLLER
q
q
OK

950N 1 732773 - Rev. B
q
q
OK
ENGLISH
The KP-CONTROLLER is used to select the operating
modes, adjust and program the Series 950 automatic doors.
It is divided into two parts: a xed part for selecting the
operating mode using buttons and corresponding LEDs
(Fig. 2 ref. a), and a removable part with LCD and selection
keys for accessing complete programming (Fig.2 ref. c).
The KP-CONTROLLER display can be used as a temporary
programming unit by setting ON the parameter “Maintain
settings” in the ADVANCED MENU: once all programming
and adjustments have been made, the KP-CONTROLLER
can be removed completely as all the settings are stored
on the 950 MPS board.
If the KP-CONTROLLER is installed without a display, a
cover is installed in its place (Fig. 2 ref. b).
1 DESCRIPTION
Fig.1
The KP-CONTROLLER can be inhibited using a key com-
bination (see the special LOCK function) or a switch to
create an internal jumper (Fig. 2 ref. LOCK).
2 INSTALLATION
Refer to Fig. 2 for the installation exploded view. There are
two openings for running the connection cable.
3 CONNECTIONS
The KP-CONTROLLER must be connected to the 950 I/O
board using a 2 x 0.5 mm2 max 50 m cable (Fig. 2). If the
two LOCK terminals are connected to each other, as shown
in Fig. 2, all programmer keys are inhibited.
4 DIAGNOSTICS
The KP-CONTROLLER (even without display) features a
diagnostic function which, in case of fault, interrupts every
2 sec. normal visualisation of the operating mode and si-
gnals for 1 sec. the fault condition through a combination
of ashing LEDs. Refer to the table in gure 3 for the LED
combinations and consequently the type of fault. Should
more than one fault occur simultaneously, the code of the
rst one detected will be visualised.
Manufacturer: FAAC S.p.A.
Address: Via Calari, 10 - 40069 Zola Predosa BOLOGNA - ITALY
Declares that: The KP CONTROLLER device
complies with the essential safety requirements of the following EU Directive
2004/108/EC Electromagnetic Compatibility Directive
And also declares that it is prohibited to put into service the machinery until the machine in which it will be
integrated or of which it will become a component has been identied and declared as conforming to the
conditions of Directive 2006/42/EEC and subsequent amendments.
Bologna, 10-01-2013
The Managing Director
A. Marcellan
CE DECLARATION OF CONFORMITY
KP CONTROLLER

950N 2 732773 - Rev. B
a
2
1
LOCK J3
950 I/0
+
-
b
c
ab c d e
f g h
ENGLISH
FAULT
NUMBER
MEANING LED STATUS:
a b c d e f g h
3Attempt to force door open in progress
7 Emergency input active
8 Obstacle when opening detected three consecutive times. Reset requi-
red
9 Obstacle when closing detected three consecutive times. Reset required
10 Electric lock locked closed
12 No 24V= accessories power
13 failsafe test failed on closing
14 failsafe test failed on opening
15 Set-up prevented
18 Leaf stroke too long
20 Leaf stroke insufcient
22 Leaf too heavy
24 Motor failure
26 950 MPS board failure
28 Set-up cycle requested
29 Encoder failure
30 Motor drive on 950 MPS board failure
31 EEPROM failure
32 Master and slave communication error
KP controller and 950 I/0 board communication error
LED ON: LED OFF:
Fig.2
Fig.3
3V CR1216
LITHIUM BATTERY
2x0.5 mm2
max 50m

950N 3 732773 - Rev. B
ab c d e
q
q
OK
ENGLISH
5 OPERATING MODES
BUTTON
NUMBER
MODE LOGO FUNCTION
aMANUAL The door is free and can be operated manually
b
TWO-WAY Pedestrian passage is permitted in both directions;
the internal and external radars are enabled.
ONE-WAY Pedestrian passage is permitted in only one direction;
the external radar is disabled.
c
PARTIAL OPENING The door opens at reduced capacity (standard 80%).
60% - 90% adjustment of the total stroke.
TOTAL OPENING The door opens completely.
d
AUTOMATIC
The door opens (partially or completely) then closes after a set pause
time.
DOOR OPEN The door opens and stays open, with the motor powered.
eNIGHT
The door closes.
The internal and external radars are disabled.
The key control (Key) causes opening and closing
after the night pause time (standard 7 sec.).
For partial opening in this mode, before selecting “Night” mode, activate
“Partial opening” mode.
6 SPECIAL FUNCTIONS
6.1 SET UP
Set-up is the door initialisation function during which parameter self-learning is performed.
It is activated by simultaneously pressing aand e for 5 sec., until all the LEDs go on.
6.2 RESET
Reset restores normal operating conditions following some types of faults.
It is activated by simultaneously by pressing band c , until the KP controller goes off.
6.3 KP CONTROLLER LOCK ( LOCK )
When activated, the Lock function inhibits operation of the KP-CONTROLLER.
It is activated by simultaneously by pressing cand d for 5 sec.
Fig.4

950N 4 732773 - Rev. B
ENGLISH
7 PROGRAMMING
To enter programming mode, when the monitor is displaying the day-date-time, press either p or q.
Programming is divided into main menus (see Diagram 1) arranged by subject.
Once the menu has been selected using p or q, press OK to access it.
Each menu is divided into various level sub-menus for setting parameters.
Use thep or qkeys to select the submenu or parameter and OK to conrm.
An asterisk on the display indicates the currently active setting.
To exit programming, select “exit” at each level; as an alternative, after approximately 2 minutes the display will
automatically return to standard visualisation.
Following are the ow charts and notes describing the various menus and programming options.
Diagram 1: Main programming menu
DAY TIME
VER DATE
LANGUAGE
SETUP
PROGRAMMING
TIMER
TIMER
CLOCK
ADVANCED MENU
DIAGNOSTICS
LOCK

950N 5 732773 - Rev. B
ENGLISH
NIGHT
PAUSE TIME
PARTIAL
OPENING
SETUP 80%
PAUSE TIME
7 SEC.
EXIT
*
*
2 SEC. *
OBSTACLE
DETECTION
CLOSING
STANDARD
CLOSING
NO STANDARD
*
ITALIANO
ENGLISH
DEUTSCH
FRANCAIS
ESPANOL
LANGUAGE
Diagram 2: Language selection
The language choice can vary depending
on the programming country.
Diagram 3: Setup

950N 6 732773 - Rev. B
ENGLISH
Diagram 4: Lock
OFF
ALWAYS
ONE-WAY+NIGHT
NIGHT
ON
LOCK
KIT
LOCK
EXIT
*
*
Diagram 5: Diagnostics
RESET
DIAGNOSTICS 950 v. NR. of CYCLES
XXXX
FAULT nr.
(fault description)

950N 7 732773 - Rev. B
ENGLISH
PASSWORD
0000
ADVANCED MENU PASSWORD
0000
PASSWORD
0000
PASSWORD
0000
MOTION
PARAMETERS CLOSING SPEED
OPENING SPEED
MAINTAIN
SETTINGS
OFF*
ON
8*
8*
EXIT
IN/OUT SETUP
OTHER
EXIT
CHANGE
PASSWORD
incorrect code
correct code
Diagram 6: Motion parametersDiagram 5: Diagnostics

950N 8 732773 - Rev. B
ENGLISH
ON
ON
ON
Diagram 7: In/Out Setup
PASSWORD
0000
ADVANCED MENU PASSWORD
0000
PASSWORD
0000
PASSWORD
0000
incorrect code
correct code
MOTION
PARAMETERS
IN/OUT SETUP
OTHER
EXIT
CHANGE
PASSWORD
EMERG OPENS
CLOSES*
OUT OP/CL NO*
FAULT
OUT NO*
NC
EXIT
NC
NO
NC*

950N 9 732773 - Rev. B
ENGLISH
Diagram 8: Other, Change password, Prog test
PASSWORD
0000
ADVANCED
MENU
PASSWORD
0000
PASSWORD
0000
PASSWORD
0000
MOTION
PARAMETERS
IN/OUT SETUP
OTHER
EXIT
CHANGE
PASSWORD
STAND SETUP STANDARD
NO STANDARD
INTERLOCK
MASTER*
SLAVE
NO
MEMORY*
WITH MEMORY
EXIT
NEW PASSWORD
0000
restore
standard
configuration
MASTER*
SLAVE
ON
OFF*
ON
OFF*
2 LEAVES
PROG TEST
ON
OFF*
NEW PASSWORD
0000
NEW PASSWORD
0000
NEW PASSWORD
0000
incorrect code
correct code

950N 10 732773 - Rev. B
ENGLISH
SUN 00:00
00/00/00
SUN 00:00
00/00/00
CLOCK SUN 00:00
00/00/00
SUN 00:00
00/00/00
SUN 00:00
00/00/00
SUN 00:00
00/00/00
SUN 00:00
00/00/00
SUN 00:00
00/00/00
SUN 00:00
00/00/00
SUN 00:00
00/00/00
SUN 00:00
00/00/00
Diagram 9: Clock Diagram 10: Timer
TIMER
ON
OFF *

950N 11 732773 - Rev. B
ENGLISH
Diagram 11: Timer programmazione
PROGRAMMING TIMER
EVERY DAY
SUN
MON
WED
TUE
SAT
FRI
THU
EXIT
TIME BAND: 1
FUN: 0 00:00
TIME BAND: 2
FUN: 0 00:00
TIME BAND: 5
FUN: 0 00:00
TIME BAND: 4
FUN: 0 00:00
TIME BAND: 3
FUN: 0 00:00
TIME BAND: 1
FUN: 0 00:00
TIME BAND: 2
FUN: 0 00:00
TIME BAND: 5
FUN: 0 00:00
TIME BAND: 4
FUN: 0 00:00
TIME BAND: 3
FUN: 0 00:00
TIME BAND: 1
FUN: 0 00:00
TIME BAND: 2
FUN: 0 00:00
TIME BAND: 5
FUN: 0 00:00
TIME BAND: 4
FUN: 0 00:00
TIME BAND: 3
FUN: 0 00:00
TIME BAND: 1
FUN: 0 00:00
TIME BAND: 2
FUN: 0 00:00
TIME BAND: 5
FUN: 0 00:00
TIME BAND: 4
FUN: 0 00:00
TIME BAND: 3
FUN: 0 00:00
TIME BAND: 1
FUN: 0 00:00
TIME BAND: 2
FUN: 0 00:00
TIME BAND: 5
FUN: 0 00:00
TIME BAND: 4
FUN: 0 00:00
TIME BAND: 3
FUN: 0 00:00
Diagram 11: Programming timer

950N 12 732773 - Rev. B
ENGLISH
ITALIANO
• 1 LANGUAGE (Diagram 2)
Selects the language in which the messages are displayed.
• 2 SETUP (Diagram 3) -
• 2.1 PARTIAL OPENING
Partial opening percentage
Selects the opening percentage (with reference to total
opening) obtained when in “Partial Opening” mode.
Standard value: 80%
Adjustment: from 60% to 100%
• 2.2 PAUSE TIME
Pause time value
Sets the pause time in automatic operating modes.
Standard value: 2 sec.
Adjustment: from 0 to 30 sec.
• 2.3 NIGHT PAUSE TIME
Night pause time value
Sets the pause time in “night” operating mode.
Standard value: 7 sec.
Adjustment: from 0 to 30 sec.
• 2.4 OBSTACLE DETECTION
Determines the behaviour of the automated system in case
of repeated obstacle detection during the same operation.
Standard: The automated system attempts to complete
the operation.
No Standard: Following the detection of an obstacle for
three consecutive times, the automated system stops. Once
the obstacle has been removed, the door must be closed
manually to restore normal operation
• 3 LOCK (Diagram 4)
• 3.1 LOCK KIT
On: Lock installed
Night: The electric lock locks the door only in “Night” mode.
One-Way+Night: The electric lock locks the door in “Night”
and “One-way” mode.
Always: The electric lock locks the door every time it closes,
regardless of the set operating mode.
Off: Lock not installed.
• 4 DIAGNOSTICS (Diagram 5)
• 4.1 950
Shows the port hardware model and the software version
of the 950 MPS and 950 I/O boards to which the KP-
CONTROLLER is connected.
• 4.2 Nr. of CYCLES
Shows the count (not resettable) of the cycles performed
by the automated system.
• 4.3 FAULT Nr.
Shows the number and description of the fault in progress.
Refer to gure 3 for fault codes and descriptions.
• RESET
Performs the reset procedure and, if the cause of the
previously signalled fault has been eliminated, it restores
normal operation.
• 5 ADVANCED MENU
• PASSWORD
To access the advanced menu, the 4-digit password is
required (default 0000).
• 1 MOTION PARAMETERS (Diagram 6)
• 1.1 CLOSING SPEED
Sets the door speed during closing.
Standard value: level 8
Adjustment: from 0 to 10
• 1.2 OPENING SPEED
Sets the door speed during opening.
Standard value: level 8
Adjustment: from 0 to 10
• 1.3 MAINTAIN SETTINGS
On: The automated system maintains the operating
parameters set using the KP-CONTROLLER even if the
latter is disconnected
Off: If the KP-CONTROLLER is disconnected, the opening
and closing speed and the pause time must be set using
the trimmers.
• 2 IN/OUT SETUP (Diagram 7)
• 2.1 EMERG
Sets the effect of the emergency command
(Emerg input on the 950 I/O board).
Standard setting: Opens/NC
Opens: Activating the command opens the door.
Closes: Activating the command closes the door.
No: Normally open input.
Nc: Normally closed input.
• 2.2 OUT OP/CL
Sets operation of the Open and Closed status outputs of
the 950 I/O board.
Standard setting: N.O.
Nc: Normally closed output.
No: Normally open output
• 2.3 FAULT OUT
Sets operation of the Fault status outputs of the 950 I/O
board.
Standard setting: N.O.
No: Normally open output.
Nc: Normally closed output.
• 3 OTHER (Diagram 8)
• 3.1 STANDARD SET UP
Makes it possible to verify if any non-standard programming
has been performed.
Standard: If no standard programming function has been
modied, an asterisk will be displayed. If the asterisk
is not displayed, press “OK” to restore all the standard
programming settings.
No Standard: If at least one standard programming function
has been modied, an asterisk will be displayed.
• 3.2 INTERLOCK
The interlock function makes it possible to manage two
doors (master and slave) so that opening of one depends
on the closing of the other and vice versa.
Off: Interlock not active
On: Interlock active.
7.1 DIAGRAM DESCRIPTION

950N 13 732773 - Rev. B
ENGLISH
Master:Determines the master door (usually the inside one).
Slave: Determines the slave door.
No Memory: Using interlock, it is necessary to wait for one
door to close before commanding opening of the other: open
pulses sent during the operating cycle of the rst door will
have no effect.
With Memory: Using interlock, it is not necessary to wait
for one door to close before commanding opening of the
other: open pulses sent during the operating cycle of the
rst door will be memorised and the second door will open
automatically as soon as the rst is closed again.
• 3.3 2-LEAF
The “2-LEAF” function makes it possible to manage doors
consisting of two leaves. The two automated systems
(master and slave) manage movement of the door in a
synchronous way. The Master function must be associated
to the door that is the rst to begin opening movement.
Off: “2-LEAF” function not active.
On: Activates the “2-LEAF” function.
Master: Determines the master door (should the leaves
feature an overlap, that must always be the door that begins
moving rst).
Slave: Determines the slave door.
• 4 CHANGE PASSWORD
Sets the new password (4 digits) for accessing the advanced
menu. Default 0000.
• 5 PROG TEST
Performs a functional test of the automated system. If a
fault is detected, the automated system will stop and the
KP-CONTROLLER signals the detected fault status.
Off: Test not active.
On: Activates test.
• 6 CLOCK (Diagram 9)
Set the current day, time and date.
• 7 TIMER (Diagram 10)
Off: Timer not activated.
On: Timer activated: the operation time bands set in “8
- Programming Timer” are enabled. When the timer is
active, a “T” appears beside the time displayed and the
KP-CONTROLLER will not allow operation selection.
The internal battery of the KP-CONTROLLER keeps the
clock running even if there is no power. If the time is lost
(e.g. black-out or discharged battery) a ashing asterisk is
displayed in place of the “T”, the timer is disabled and the
automated system switches automatically to NIGHT mode.
• 8 PROGRAMMING TIMER (Diagram 11)
Makes it possible to create up to 5 different time bands
for each day of the week (setting the band start time) and
give each time band an operative function. When the KP-
CONTROLLER internal clock reaches the start of a time
band, the associated operative function is automatically
set and the door stays in that condition until the following
time band is triggered. To correctly manage the time bands,
a permanent KP-CONTROLLER+Display connection is
required.
Selecting the day. Select the day of the week
to create the time bands.
By selecting “All”, the time bands
chosen afterward will be copied to all the days of the week.
Function Set the operative function to associate
with the time band, using the following table as a reference:
FUNCTION MEANING
0No function
1 Automatic total two-way
2 Automatic total one-way
3 Automatic partial two-way
4 Automatic partial one-way
5 Door open completely
6 Door open partially
7 Manual
8 Night
Time band start
Set the time band activation time. The time frames do not
need to be in chronological order.
- Example of Programming -
You want to program a door to open
•MONDAY to FRIDAY:
- from 08:00 in AUTOMATIC TWO-WAY TOTAL mode
- from 18:00 in AUTOMATIC ONE-WAY
TOTAL
mode:
- from 19:00 in NIGHT mode
•SATURDAY and SUNDAY: NIGHT mode all day
Proceed as follows:
1) Select ALL and set:
TIME BAND1 : FUNC. 1 08:00
TIME BAND2 : FUNC. 2 18:00
TIME BAND3 : FUNC. 8 19:00
TIME BAND4 : FUNC. 0
TIME BAND5 : FUNC. 0
2) Select SATURDAY and set:
TIME BAND1 : FUNC. 0
TIME BAND2 : FUNC. 0
TIME BAND3 : FUNC. 0
TIME BAND4 : FUNC. 0
TIME BAND5 : FUNC. 0
3) Select SUNDAY and set:
TIME BAND1 : FUNC. 0
TIME BAND2 : FUNC. 0
TIME BAND3 : FUNC. 0
TIME BAND4 : FUNC. 0
TIME BAND5 : FUNC. 0
Note: to correctly use the TIMER function, the KP-
CONTROLLER battery must be efficient. In case of
electrical power failure, the battery will keep the clock
running. Should the battery discharge, the clock will
reset and, once electrical power is restored, the KP-
CONTROLLER will automatically switch to NIGHT.
On automated systems that remain without electrical
power for long periods of time (e.g.: 12 hours out of 24
for 365 days a year) it is advisable to replace the battery
at most every 3 years.

950N 14 732773 - Rev. B
ENGLISH
ITALIANO
Door 1 Door 2 Door 1 Door 2
8 SPECIAL APPLICATIONS
8.1 APPLICATION WITH TWO INTERLOCKED LEAVES
The interlock function makes it possible to manage two
doors (master and slave) so that opening of one depends
on the closing of the other and vice versa.
8.1.1 INTERLOCK WITH INTERNAL SENSORS
This application is recommended when the distance
between the two doors is enough to prevent interference
in the detection elds of the two internal sensors
•Connect the 950I/O equipment of the two automated
systems and sensors as shown in g.5.
•Programme the following functions (see advanced prog.):
-”interlock” active on both doors - select “MASTER” on the
inner door and “SLAVE” on the outer one
-for both doors select “interlock no memory” or “interlock
with memory.
Important:
•The sensors must be connected only to the board Key
input;
•The interlock works only if both doors are set to NIGHT
or ONE-WAY mode.
The interlock operating phases are as follows:
1) The person standing outside activates sensor S1 of
door 1;
2) Door 1 opens;
3) The person enters the space between the two doors;
4) Door 1 closes after the night pause time;
5) The person activates sensor S3 of door 2 (If “interlock
with memory” is selected, it is not necessary to wait for the
door to be closed completely to activate the sensor on the
second one);
6) Door 2 opens;
7) The person exits;
8) Door 2 closes after the night pause time.
Operation is similar when coming from the opposite direction.
8.1.2 INTERLOCK WITHOUT INTERNAL SENSORS (buttons)
This application is recommended when the reduced
distance between the two doors does not allow the use of
two internal sensors; outside activation of the doors requires
the installation of two buttons; not designed for use with
presence sensors.
•Connect the 950I/O boards of the two automated systems,
buttons and additional electronic components, as shown
in g. 6.
•Programme the following functions (see advanced prog.):
-”interlock” active on both doors,
-select “MASTER” for the inner door and “SLAVE” for the
outer door and for both doors select “interlock with memory”.
Important:
•The buttons must be connected only to the board Key input;
•The interlock works only if both doors are set to NIGHT
or ONE-WAY mode.
1) The person standing outside activates button B1 of
door A;
2) Door A opens;
3) The person enters the space between the two doors;
4) Door A closes after the night pause time;
5) Door B opens automatically;
7) The person exits;
8) Door B closes after the night pause time.
Operation is similar when coming from the opposite
direction.
Fig.5 Fig.6

950N 15 732773 - Rev. B
Master Slave
Master Slave
ENGLISH
8.2 APPLICATION WITH 2-LEAF DOOR (MASTER AND SLAVE )
The 2-LEAF function makes it possible to manage two opposing doors with synchronised movements and set (not
modiable) delay angles.
The leaf controlled by the master automated system (see g. 7 ) is the rst to start opening and, when it has reached
the opening angle set for the leaf delay, the slave will also begin its movement. In the same way, when closing, the
master will start moving only when the slave has reached the closing angle set for the leaf delay.
Detection of an obstacle by one of the two automated systems causes immediate reversal of both.
The partial opening function makes it possible to control total opening only of the master.
The operating functions must be set only on the master automated system (or on the KP-Controller connected to it).
1. Connect the 950I/O board of the two automated systems as shown in g. 8 .
2. Connect all the sensors and pulse transmitters only to the master.
3. Programme the following functions (see advanced prog.):
• “2-Leaf” active on both doors;
• select “MASTER” for the door that must start the opening movement rst and “SLAVE” for the other;
• set the same motion parameters on both automated systems;
• if you wish to disconnect the KP-Controller from the slave door, the function “MAINTAIN SETTINGS” must be set
to ON;
NOTE: the set-up must be carried out independently
Fig.7 Fig.8


SEDE - HEADQUARTERS
FAAC S.p.A.
Via Calari, 10
40069 Zola Predosa (BO) - ITALY
Tel. +39 051 61724 - Fax +39 051 758518
www.faac.it - www.faacgroup.com
SUBSIDIARIES
AUSTRIA
FAAC GMBH
Salzburg - Austria
tel. +43 662 8533950
www.faac.at
FAAC TUBULAR MOTORS
tel. +49 30 56796645
www.faac.at
AUSTRALIA
FAAC AUSTRALIA PTY LTD
Homebush, Sydney - Australia
tel. +61 2 87565644
www.faac.com.au
BENELUX
FAAC BENELUX NV/SA
Brugge - Belgium
tel. +32 50 320202
www.faacbenelux.com
FAAC TUBULAR MOTORS
tel. +31 475 406014
www.faacbenelux.com
CHINA
FAAC SHANGHAI
Shanghai - China
tel. +86 21 68182970
www.faacgroup.cn
FRANCE
FAAC FRANCE
Saint Priest, Lyon - France
tel. +33 4 72218700
www.faac.fr
FAAC FRANCE - AGENCE PARIS
Massy, Paris - France
tel. +33 1 69191620
www.faac.fr
FAAC FRANCE - DEPARTEMENT
VOLETS
Saint Denis de Pile - Bordeaux - France
tel. +33 5 57551890
www.faac.fr
ASSISTENZA IN ITALIA
SEDE
tel. +39 051 6172501
www.faac.it/ita/assistenza
FIRENZE
tel. +39 055 301194
GERMANY
FAAC GMBH
Freilassing - Germany
tel. +49 8654 49810
www.faac.de
FAAC TUBULAR MOTORS
tel. +49 30 5679 6645
www.faac.de
INDIA
FAAC INDIA PVT. LTD
Noida, Delhi - India
tel. +91 120 3934100/4199
www.faacindia.com
IRELAND
NATIONAL AUTOMATION LIMITED
Boyle,Co. Roscommon - Ireland
tel. +353 071 9663893
www.faac.ie
MIDDLE EAST
FAAC MIDDLE EAST FZE
Dubai Silicon Oasis free zone
tel. +971 4 372 4187
www.faac.ae
NORDIC REGIONS
FAAC NORDIC AB
Perstorp - Sweden
tel. +46 435 779500
www.faac.se
POLAND
FAAC POLSKA SP.ZO.O
Warszawa - Poland
tel. +48 22 8141422
www.faac.pl
RUSSIA
FAAC RUSSIA LLC
Moscow - Russia
tel. +7 495 646 24 29
www.faac.ru
MILANO
tel +39 02 66011163
PADOVA
tel +39 049 8700541
ROMA
tel +39 06 41206137
TORINO
tel +39 011 6813997
SPAIN
CLEM, S.A.U.
S. S. de los Reyes, Madrid - Spain
tel. +34 091 358 1110
www.faac.
SWITZERLAND
FAAC AG
Altdorf - Switzerland
tel. +41 41 8713440
www.faac.ch
TURKEY
FAAC OTOMATİK GEÇİS SİSTEMLERİ
SAN. VE TİC. LTD. ŞTİ.
Çağlayan, Kağıthane, İstanbul - Turkey
tel.+90 (0)212 – 3431311
www.faac.com.tr
UNITED KINGDOM
FAAC UK LTD.
Basingstoke, Hampshire - UK
tel. +44 1256 318100
www.faac.co.uk
U.S.A.
FAAC INTERNATIONAL INC
Rockledge, Florida - U.S.A.
tel. +1 904 4488952
www.faacusa.com
FAAC INTERNATIONAL INC
Fullerton, California - U.S.A.
tel. +1 714 446 9800
www.faacusa.com
732773- Rev. B
Table of contents
Other FAAC Controllers manuals
Popular Controllers manuals by other brands

ACL
ACL CSC400 Installation and operation manual

Source Audio
Source Audio HOTHAND3 user guide

Edgewater Networks
Edgewater Networks EdgeMarc 4700 Series Hardware installation guide

ModelCraft
ModelCraft ECO-Line 20A operating instructions

Newport
Newport CONEX-PP Series GUI Manual

LenelS2
LenelS2 LNL-X2220 quick reference