GE WIR-10-DR-G-D-W User manual

,
36
20,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
8,
Minor Motion, IR
Major Motion, IR
The WIR-10-DR-G-D Occupancy Sensing Wall Switch is a Passive Infrared (PIR) motion sensing light-
ing control and conventional Wall Switch all-in-one, used for energy savings and convenience.
PIR Technology
The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in
temperature that are created when a person, or part of a person as small as a hand, passes into or
out of a sensor zone.
The WIR-10-DR-G-D allows the control of two separate loads with one occupancy sensor switch.
Energy Saver Mode – Either or both loads may be configured to turn O manually. The default set-
ting for the second load is Manual O . This ensures the Wall Switch only activates one load. If both
loads are on when the sensor times-out, only the primary load will be activated. If the lights were
shut OFF manually, the unit will activate the primary load only.
In Automatic O Mode, the lights turn O automatically when a person enters the room. In Manual
O Mode, the lights are turned O by pressing the pushbutton. In either mode, the lights stay O as
long as the sensor detects motion in the room. When the room is vacated, the lights turn OFF auto-
matically after a preset Time Delay interval.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sen-
sitivity and Time Delay in Real-time. By adjusting sensitivity and Time Delay automatically, the sensor
is maximizing the potential energy savings that are available in the particular application.
The Daylighting feature prevents lights from turning O , when the room is adequately illuminated by
natural light.
Walk-Through feature maximizes energy savings by not leaving the lights O after a momentary oc-
cupancy. The sensor will switch the lights O when it detects a person entering the area. If the sen-
sor does not continue to detect motion 20 seconds following the initial activation, it will
automatically go to a shorter 2 minute Time Delay.
Passive Infrared Dual-Relay Wallbox Occupancy Sensor (Ground Required)
• Read all instructions on both sides of this
sheet first.
• Plan all component locations carefully.
• For use with 120/277 VAC only
• Install in accordance with ALL local codes.
• For indoor use only.
Ge eral I formatio
Technology: Passive Infrared (PIR)
Electrical Ratings(per relay):
120 VAC:
• Incandescent/Tungsten – Max. load: 6.7 amps,
800W, 50/60 Hz
• Fluorescent/Ballast – Max. load: 10 amps, 1200W,
50/60 Hz
Motor Load: ¼ HP @ 125 VAC
277 VAC:
• Fluorescent/Ballast – Max. load: 9.8 amps,
2700W, 50/60 Hz
o minimum load requirements
Time Delays: Self-Adjusting, 15 seconds/test (10 min
Auto), Selectable 5, 15, 30 minutes
Operating Environment:
• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: 20% to 90% non-condensing
• For indoor use only
Coverage: Major Motion - 1000 sq. ft.
Minor Motion - 300 sq. ft.
Light Level Sensing: 0 to 200 foot-candles
Housing:
• Durable, injection-molded housing. Polycarbon-
ate resin complies with UL94V0.
Size:
•Mounting Plate Dimensions:
4.195" H x 1.732" W (106.553 mm x 44 mm)
•Product Housing Dimensions:
2.618" H x 1.752" W x 1.9" D (66.5 mm x 44.5 mm
x 48.26 mm)
LED Indicators: Red indicates PIR detection
Operating Modes:
• Automatic O /Automatic OFF
• Manual O /Automatic OFF
Specificatio s
Descriptio
Coverage
Istallatio
NOTE: Before you begin, read these instructions completely and carefully.
Wiri g
INSTALLATION INSTRUCTIONS
WIR-10-DR-G-D-W
WIR-10-DR-G-D-V
WIR-10-DR-G-D-A
WIR-10-DR-G-D-G
WIR-10-DR-G-D-B
Model #
The WIR-10-DR-G-D is designed for offices up to 300 square feet. Coverage testing has been
performed according to the EMA WD7 Guideline.
The WIR-10-DR-G-D can be installed in
any standard single gang box. It may
be installed in the same manner as an
ordinary Wall Switch.
• Wire the WIR-10-DR-G-D as de-
scribed in the wiring section.
• Mount the WIR-10-DR-G-D in the
junction box.
CA TION: Before installing or performing any service on a GE system, the power M ST be turned
off at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is
used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked
“SWD.” All installations should be in compliance with the National Electric Code and all state
and local codes.
OTE REGARDI G COMPACT FLUORESCE T LAMPS: The life of some compact fluorescent
lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast
manufacturer to determine the effects of cycling.
1. Make sure power is turned off at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements.
3. Mount unit to Wall Box.
4. Turn power back O at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install Wall Switch plate.
LOAD 1
120/277 VAC BLACK BLUE
GROUND
GREEN
RED
LOAD 2
RED
Wiring Diagram 1: 120/277 VAC dual level single circuit wiring diagram
LOAD 1
CIRCUIT 1
120/277 VAC BLACK BLUE
CIRCUIT 1 NEUTRAL
CIRCUIT 1
GROUND
GREEN
RED
LOAD 2
RED
CIRCUIT 2
120/277 VAC
CIRCUIT 2 NEUTRAL
Wiring Diagram 2: 120/277 VAC dual level dual circuit wiring diagram
Locatio
When installing the WIR-10-DR-G-D in a new junction box, choose the switch location
carefully to provide optimum coverage of the occupied area. When replacing an exist-
ing Wall Switch, bear in mind that there must be a clear Line-of-sight between the sen-
sor and the area to be covered. Avoid pointing the WIR-10-DR-G-D directly into the
hallway where it may detect passers-by.

Adjustments should be made with the HVAC system on so that the installer will be able to de-
tect the effect of airflow on the operation of the WIR-10-DR-G-D. Use only insulated tools to
make adjustments. Immediately after applying power to the lighting circuit, wait approxi-
mately two minutes for the switch to power up
and stabilize.
Self-Adjust
The sensor is shipped in self-adjust mode. This
applies to Time Delay and PIR sensitivity. In
preparation for the Installer Test, the Time
Delay is set to 15 seconds, after the sensor is
installed, powered on and has stabilized, the
unit will Time-out 15 seconds after the last mo-
tion detected. Coverage and sensitivity can be
confirmed by watching the Red (PIR) indicator
LED on the front of the sensor, while moving
around the room.
1. Walk around the room and monitor LEDs.
2. Stand in different parts of the room and
wave your hands. LED should only turn on
for one second with each motion. (If LED
does not turn on, go to Installer Adjustments – Sensitivity Adjustment Section)
3. Stand still three to four feet away from sensor for five seconds. LED should not turn on.
(If LED turns on, go to Installer Adjustments – Sensitivity Adjustments section)
4. Walk outside the room and wait 15 seconds for the lights to turn off. (If lights do not turn
off go to Installer Adjustments Section)
5. Re-enter the room to activate sensor. (If lights do not turn on go to Troubleshooting Sec-
tion)
6. At this point you can exit the room and let the sensor Time-out. When the sensor times-
out and is off for five minutes, the unit will go to a 10 minute Time Delay user mode set-
ting.
ote: To place i nto Test Mode, toggle DIP Switch 8 out of its current position, wait 3 seconds,
and then back into its original position.
Checkout a d Adjustme t
I staller Adjustme ts
Manufactured for GE Lighting
General Electric Company
Nela Park Cleveland, OH 44112
1-877-584-2685
www.gelightingcontrols.com
© 2011 GE
PIR Sensitivity
1. Stand in different areas of the room and wave your
hands.
2. If the Red LED does not turn on, check for any obstruc-
tions.
3. Stand still three to four feet away from sensor for five
seconds. LED should not turn on.
4. If Red LED turns on without motion or is constantly on
adjust PIR sensitivity to 50 % by moving DIP Switch 5
up.
O /OFF Disabled Feature
1. O /OFF Button Disable Option – When selected this
option disables the O /OFF button and sensor be-
comes automatic only control regardless of the setting
for automatic or manual activation. This feature will
not allow someone to turn light(s) OFF via the Pushbutton while people are in common
areas such as restroom, break room, and copy room areas.
Field-of-view outside the space
1. Adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
2. Use non-reflective tape strips to cover the portions of the sensor lens that view outside
the space.
Daylight Adjustments
The daylighting feature prevents the lights from turning O when the room is adequately illu-
minated by natural light. If there is enough light in the room regardless of occupancy, the sen-
sor will hold the lights OFF. If there is not enough light in the room, the sensor will allow the
lights to turn O when occupied. The sensor will not allow the daylighting feature to turn the
load OFF until the space is vacant or the light level rises above the setpoint and the Time Delay
expires. While in Manual Activation Mode, if someone attempts to turn the load O and there
is sufficient daylight available the Daylighting feature will hold the lights OFF.
Set the light level when the ambient light is at the level where no artificial light is needed. If
this feature is not needed, leave the light level at maximum (fully CW).
1. With the load(s) O , put the sensor into Test
Mode. To place into Test Mode, toggle DIP
Switch 8 out of its current position, wait 3 sec-
onds and then back in to its original position.
2. Set the Light level to minimum (fully CCW).
3. Let the sensor Time-out so lights are OFF. Enter
the space and lights should remain OFF.
4. Make sure not to block the sensor from the day-
light source and adjust the light level poten-
tiometer CW in small increments. (Pause 5
seconds between each adjustment)
5 Once the lights are O , the load connected to the sensor will not turn O if light levels are
above the current illumination.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer Time Delay than the
default setting of 10 minutes. As long as the self-adjusting feature is enabled, the switch will
respond to each pair of False-offs with no normal OFF in between, by alternately making slight
adjustments to either Time Delay (by 2 minute increments) or sensitivity, so there should be no
need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in
DIP Switch legend.
Reset sensor Time Delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP
Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position, wait 3 sec-
onds, and then back to its original position)
Override
The override setting allows the sensor to operate as a service switch in the unlikely event of
failure.
1. Move DIP Switch 8 up.
2. The Pushbutton can be used to manually turn lights O or OFF.
Limited Warra ty
This product is warranted to be free from defects in material and workmanship and shall conform to and
perform in accordance with Seller’s written specifications for a period of five (5) years from date of shipment
for all occupancy sensors. We guarantee the performance of our product to specifications or your money
back. This warranty will be limited to the repair or replacement, at Seller’s discretion, of any such goods
found to be defective, upon their authorized return to Seller. This limited warranty does not apply if the
goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage during
shipment or by improper service. There are no warranties, which extend beyond the hereinabove-limited
warranty, I CLUDI G, BUT OT LIMITED TO, THE IMPLIED WARRA TY OF MERCHA TABILITY A D THE IM-
PLIED WARRA TY OF FIT ESS. o employee, agent, dealer, or other person is authorized to give any war-
ranties on behalf of the Seller or to assume for the Seller any other liability in connection with any of its
goods except in writing and signed by the Seller. The Seller makes no representation that the goods comply
with any present or future federal, state or local regulation or ordinance. Compliance is the Buyer’s respon-
sibility. The use of the Seller’s goods should be in accordance with the provision of the ational Electrical
Code, UL and/or other industry or military standards that are pertinent to the particular end use. Installation
or use not in accordance with these codes and standards could be hazardous.
Res. #9582190
Printed in USA
DIP Switch Setti gs
LOAD 1
BLACK
NEUTRAL
THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTEDMOTION LAST TIMES-OUT.
GROUND
GREEN
120/277 VAC
BLACK
BLUE
GROUND
GREEN
TRAVELER
WIRES
LOAD 2
RED RED RED RED
BLUE
Wiring Diagram 3: 120/277 VAC dual level single circuit three-way wiring diagram
123456 78
DIP Switches 910 11 12
ON/OFF Buttons
1& 2
PIR Lens
DIP Switches
Daylight Sensor
Level Adjust-
ment
Red (PIR)
Detection LEDs
Troubleshooti g
Issue Possible Causes Suggestions
Lights
Will ot
Turn O
automatically
Sensor is in Manual O mode Press Pushbutton. If Auto Mode
is desired change Activation Mode to Auto.
Sensor was turned OFF manually. If the Sen-
sor was turned OFF manually before the Time
Delay expired, lights will remain OFF for the re-
mainder of the Time Delay.
Press the Pushbutton to turn the lights back O .
Daylight Feature Enabled If all lights are required to turn O
adjust daylight potentiometer.
Power interruption Check incoming voltage and/or wiring.
Lights
Will ot
Turn O
manually
Daylight Feature Enabled If all lights are required to turn O
adjust daylight potentiometer.
Power interruption Check incoming voltage and/or wiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-877-584-2685
Lights
Will ot
Turn OFF
automatically
Override Make sure sensor is not in Override Mode
(DIP Switch 8 up).
Self-Adjust
If sensor is in Self-Adjust Mode, it may be possible for
the unit to have increased the Time Delay to a 30 minute
delay. If the lights do not turn OFF after 30 minutes fol-
low next step.
30 Minute Delay
Maximum Time Delay is 30 Minutes. Check DIP Switches
to verify DIP Switch settings. If lights do not turn OFF at
the set Time Delay, check next step.
PIR activated by heat source other than
occupant Move DIP Switch 5 up.
Lights
Will ot
Turn OFF
manually
Call Technical Services
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-877-584-2685
5 Minutes
Auto*
*Self-Adjusts to
10 min. user
mode
Time Delay
DIP Switch
Activation PIR Sensitivity Not Used Not Used Not Used Daylighting
Relay 1 Relay 2Relay 1 Relay 2
OverrideWalk-Through Mode
Default =
30 Minutes
15 Minutes
12
DIP Switch Legend
12
q
p
Disable
Enable
11
q
p
Disable
Enable
9
6
q
p
Disable
Enable
4
q
p
Auto
Manual
3
q
q
q
q
qp
p
pp
p
Auto
Manual
5
q
p
Full
50%
8
q
p
Disable
Enable
710
12345678910 11 12
This manual suits for next models
4
Other GE Accessories manuals

GE
GE Learn Mode Shock Sensor User manual

GE
GE Giraffe User manual

GE
GE Monogram ZBD7005GII User manual

GE
GE Telaire Ventostat 8001 User manual

GE
GE WR72X10313 Configuration guide

GE
GE DDI602 Assembly instructions

GE
GE PowerBank M540 User manual

GE
GE 32563 User manual

GE
GE 319.5 User manual

GE
GE ve735am User manual