GE 10900 Series User manual

GE Oil & Gas
10900 Series
Masoneilan* Spring Diaphragm and
Differential Pressure Actuators for use
with 500 Series Regulators
Instruction Manual
GE Data Classification : Public

2 | GE Oil & Gas © 2015 General Electric Company. All rights reserved.
THESE INSTRUCTIONS PROVIDE THE CUSTOMER/OPERATOR WITH IMPORTANT PROJECT-
SPECIFIC REFERENCE INFORMATION IN ADDITION TO THE CUSTOMER/OPERATOR’S NORMAL
OPERATION AND MAINTENANCE PROCEDURES. SINCE OPERATION AND MAINTENANCE
PHILOSOPHIES VARY, GE (GENERAL ELECTRIC COMPANY AND ITS SUBSIDIARIES AND AFFILIATES)
DOES NOT ATTEMPT TO DICTATE SPECIFIC PROCEDURES, BUT TO PROVIDE BASIC LIMITATIONS
AND REQUIREMENTS CREATED BY THE TYPE OF EQUIPMENT PROVIDED.
THESE INSTRUCTIONS ASSUME THAT OPERATORS ALREADY HAVE A GENERAL UNDERSTANDING
OF THE REQUIREMENTS FOR SAFE OPERATION OF MECHANICAL AND ELECTRICAL EQUIPMENT
IN POTENTIALLY HAZARDOUS ENVIRONMENTS. THEREFORE, THESE INSTRUCTIONS SHOULD BE
INTERPRETED AND APPLIED IN CONJUNCTION WITH THE SAFETY RULES AND REGULATIONS
APPLICABLE AT THE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER
EQUIPMENT AT THE SITE.
THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT
NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH
INSTALLATION, OPERATION OR MAINTENANCE. SHOULD FURTHER INFORMATION BE DESIRED
OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE
CUSTOMER/OPERATOR'S PURPOSES THE MATTER SHOULD BE REFERRED TO GE.
THE RIGHTS, OBLIGATIONS AND LIABILITIES OF GE AND THE CUSTOMER/OPERATOR ARE
STRICTLY LIMITED TO THOSE EXPRESSLY PROVIDED IN THE CONTRACT RELATING TO THE SUPPLY
OF THE EQUIPMENT. NO ADDITIONAL REPRESENTATIONS OR WARRANTIES BY GE REGARDING
THE EQUIPMENT OR ITS USE ARE GIVEN OR IMPLIED BY THE ISSUE OF THESE INSTRUCTIONS.
THESE INSTRUCTIONS ARE FURNISHED TO THE CUSTOMER/OPERATOR SOLELY TO ASSIST
IN THE INSTALLATION, TESTING, OPERATION, AND/OR MAINTENANCE OF THE EQUIPMENT
DESCRIBED. THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART TO ANY
THIRD PARTY WITHOUT THE WRITTEN APPROVAL OF GE.

Masoneilan 10900 Series Actuator Instruction Manual | 3© 2015 General Electric Company. All rights reserved.
Important - Please Read Before
Installation
Masoneilan 10900 Series actuator instructions contain
DANGER, WARNING, and CAUTION labels, where necessary,
to alert you to safety related or other important information.
Read the instructions carefully before installing and
maintaining your control valve. DANGER and WARNING
hazards are related to personal injury. CAUTION hazards
involve equipment or property damage. Operation of
damaged equipment can, under certain operational
conditions, result in degraded process system performance
that can lead to injury or death. Total compliance with all
DANGER, WARNING, and CAUTION notices is required for
safe operation.
This is the safety alert symbol. It alerts you to potential
personal injury hazards. Obey all safety messages that
follow this symbol to avoid possible injury or death.
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in serious injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in minor or moderate injury.
When used without the safety alert symbol indicates a
potentially hazardous situation which, if not avoided, could
result in property damage.
Note: Indicates important facts and conditions.
About this Manual
• The information in this manual is subject to change
without prior notice.
• The information contained in this manual, in whole or
part, shall not be transcribed or copied without GE’s
written permission.
• Please report any errors or questions about the
information in this manual to your local supplier.
• These instructions are written specifically for the
Masoneilan 10900 Series actuators, and do not apply to
other equipment outside of this product line.
Life Period
The current estimated useful life period for the Masoneilan
10900 Series Actuators is 25+ years. To maximize the
useful life of the product it is essential to conduct annual
inspections, routine maintenance and ensure proper
installation to avoid any unintended stresses on the
product. The specific operating conditions will also
impact the useful life of the product. Consult the factory
for guidance on specific applications if required prior to
installation.
Warranty
Items sold by General Electric are warranted to be free
from defects in materials and workmanship for a period of
one year from the date of shipment provided said items are
used according to GE recommended usages. GE reserves
the right to discontinue manufacture of any product or
change product materials, design or specifications without
notice.
This instruction manual applies to the Masoneilan 10900
Series actuators.
Note:
• The actuator MUST BE installed, put into
service and maintained by qualified and
competent professionals who have undergone
suitable training.
• Under certain operating conditions, the use of
damaged equipment could cause a degradation of the
performance of the system which may lead to personal
injury or death.
• Changes to specifications, structure, and components
used may not lead to the revision of this manual unless
such changes affect the function and performance of
the product.
• All surrounding pipe lines must be thoroughly flushed to
ensure all entrained debris has been removed from the
system.
Safety Information

4 | GE Oil & Gas © 2015 General Electric Company. All rights reserved.
Range
(psi)
Actuator
Type
1.5 - 3
0.5 - 2
Max. Static
Pressure
(psi)
Case
Size
2 - 10
6 - 20
15 - 40
30 - 75
60 - 125
80 - 250
150 - 750
3 - 12
10 - 35
30 - 75
60 - 125
3 - 15
30 - 85
5 - 30
10 - 60
75 - 185
Low Pressure Case
Spring
Diaphragm
Differential
High Pressure Case
100 - 330
250
600
1000
1500
5
4
5
4
3 1/2
5
9
11
4
3 1/2
Special
60
250
750
The following instructions should be thoroughly reviewed
and understood prior to installing operating or performing
maintenance on this equipment. Only qualified personnel to
service this equipment.
Non-compliance with safety rules and caution notes of this
instruction may bring about malfunction of the device or
damage it seriously. In addition, such negligence might expose
personnel present in the field to grave hazards.
General
These adjustment and maintenance instructions apply to the
10900 Series Actuators used with the Masoneilan 500 Series
Pressure Regulators. They include a parts reference list including
recommended spare parts.
For installation, operation, adjustment and maintenance of the
500 Series Regulators body S/A refer to instructions numbers
indicated by the following table.
Spare parts
When performing maintenance always use GE
replacement parts. Masoneilan Parts are obtainable through your
local GE Representative or Masoneilan Spare Parts Department.
When ordering parts, always include Masoneilan Model and
Serial Numbers shown on serial plate.
After sales Department
GE has a highly skilled After Sales Department available
for start-up, maintenance and repair of our regulators and
components parts. Contact the nearest GE Sales Office or
Representative.
Training
GE Masoneilan regularly holds training seminars for technicians.
In order to participate in one of these training seminars you
should contact our local GE Masoneilan Representative or our
Training Department.
Description-Operation
The 10900 Actuator is a simple powerful mechanical device. It
is Air-to-Extend Stem type. The nominal range of an actuator is
the pressure range in pounds per square inch (psi) in which the
pressure setting can be obtained by adjustment.
Conformation of the diaphragm (11) to the diaphram plate
(10) serves as a flexible upper guide for the actuator stem (6).
Nylon reinforced neoprene diaphragms permit smooth, sensitive
operation. The lower guide is an oil impregnated bronze bushing
(3) located in the spring adjuster (2).
Note: On request, for special services, the nylon reinforced
neoprene diaphragm may be provided with a PTFE coating. Other
materials are optional and available to suit the fluids involved.
The 10900 Series Actuators are designed for use with the 500
Series Regulators for reducing, back pressure and differential
pressure applications.
The opposite chart indicates the combinations available to
provide the desired function. The 10900 Series Actuators are
designated by the nominal range (psi). See the following chart.
In Spring Diaphragm Actuators, three actuator cases are
available: a case rated for 60 psi static pressure, a case rated
for 250 psi static pressure and a case rated for 750 psi static
pressure.
In Differential Pressure Actuators, two actuator cases are
available: a low-pressure case rated for 250 psi static pressure,
and a high-pressure case rated at 600, 1000 and 1500 psi static
pressure.
Regulator
Model No
525; 525-50
526; 526-50
Body S/A
Instruction No
535H; 535H-50
536H; 536H-50
535V; 535V-50
GEA30557A
GEA31597
176419
E
Regulator
Model No
REDUCING
Function
Spring Diaphragm
Actuator Type
525
535H
535V
BACK
PRESSURE
DIFFERENTIAL
REDUCING
525-50
535H-50
535V-50
526
536H
Differential
526-50
536H-50
DIFFERENTIAL
BACK PRESSURE

Masoneilan 10900 Series Actuator Instruction Manual | 5© 2015 General Electric Company. All rights reserved.
Design for the 30-75, 60-125
and 80-250 psi ranges
Design for the 0.5-2 ; 1.5-3 ; 2-10 ; 6-20
and 15-40 psi ranges
Figure 1 — Spring-Diaphragm Actuators for 500,
500H and 500V Model Regulators Design for the 150-750 psi range
8
7
5
1
4
2
13
16
6
15
11 28 14 10
23
22
3
27
Serial
Plate
Regulator
Plug
Stem
Plug Stem
Nuts
8
5
1
13
16
6
17
9
11 10
2
4
3
Serial
Plate
Regulator
Plug
Stem
Plug Stem
Nuts
PARTS REFERENCE
1 Yoke
2 Spring Adjuster
3 Bushing (Incl. Ref. 2)
4 Lower Spring Seat
5 Actuator Spring
6 Actuator Stem
7 Cap Screw (L. case to yoke)
8 Diaphragm Case (Lower)
9(2) Diaphragm Chamber
10 Diaphragm Plate
11 Diaphragm •
13 Diaphragm Case (Upper)
14(1) Diaphragm Washer
15 Cap Screw (Diaph.case)
16 Nut (Diaph.case)
17(2) Stud (Diaph. case)
18 Stop Cup
21(4) Reducing Ring
22(5) Stop Screw
23(5) Stop Spacer
27(1) Upper Spring Washer
28(1) Locknut (Actuator stem)
30 Spacer Ring (size 3.5 only)
• Recommended spare parts
(1) Only on 0.5-2 ; 1.5-3 ; 2-10 ; 6-20 and 15-40 psi ranges
(2) Only on 150-750 psi range
(4) Only on 60-125 and 80-250 psi ranges
(5) Only on 0.5-2 ; 1.5-3 ; 2-10 ; 6-20 and 15-40 psi ranges actuators mounted on types 526 and 536H
regulators
Ref. Part Name Ref. Part Name Ref. Part Name

6 | GE Oil & Gas © 2015 General Electric Company. All rights reserved.
8
5
1
6
2
4
3
16
7
17
9
10
11 13
16
25
24
26
27
Regulator
Plug
Stem
Serial
Plate
Plug Stem
Nuts
3
2
4
1
5
7
8
6
16
27
9
10
11
15
12 13 14 28
26
25
24
29
25
Regulator
Plug
Stem
Serial
Plate
Plug Stem
Nuts
Figure 2 — Differential Pressure Actuators for 500-50, 500H-50 and 500V-50 Models Regulators
PARTS REFERENCE
High Pressure Case Design
1 Yoke
2 Spring Adjuster
3 Bushing (Incl. Ref. 2)
4 Lower Spring Seat
5 Actuator Spring
6 Actuator Stem
7 Cap Screw (L. case to yoke)
8 Diaphragm Case (Lower)
9 Diaphragm Chamber
10 Diaphragm Plate (Incl. w. Ref. 24)
11 Diaphragm •
12(1) Upper Diaphragm Plate
13 Diaphragm Case (Upper)
14(1) Diaphragm Washer
15(1) Cap Screw (Diaph.case)
16 Nut (Diaph.case)
17(2) Stud (Diaph. case)
24 Plunger Sub-assembly
25(3) O-Ring •
26 O-Ring Retainer
27 Upper Spring Seat (Incl. w. Ref. 6)
28(1) Locknut
29(1) Connection Adapter
Ref. Part Name Ref. Part Name Ref. Part Name
•Recommended spare parts
(1) Only on Low Pressure Case Design
(2) Only on High Pressure Case Design
(3)
Qty: 2 on Low Pressure Case Design
Qty: 1 on High Pressure Case Design
Installation
On steam service, the regulator should be installed with the
actuator down so that the diaphragm will be protected by a
condensate barrier. If installed otherwise, an adequate
condensate barrier must be incorporated.
In the Spring Diaphragm Actuators, the 1/2” NPT pressure
connection is located on the upper diaphragm case (13).
In the Differential Pressure Actuators, the 1/2” NPT high pressure
connection is located on the upper diaphragm case (13) and the
1/2” NPT low pressure connection is located on the diaphragm
chamber (9) or on the connection adapter (29).
Refer to Regulators Body S/A Instructions for installation
according to the regulator function.
Low Pressure Case Design

Masoneilan 10900 Series Actuator Instruction Manual | 7© 2015 General Electric Company. All rights reserved.
Adjustment
When pressure setting has been specified in order, the regulator
is set accordingly at the factory for test. Then, the spring
compression is fully removed to avoid unnecessary stress to
parts (diaphragm, spring) during the stocking.
The regulator pressure range is engraved on the serial plate.
Proceed as follows :
• Open stop valve on the outlet side of the regulator and partially
open stop valve on the inlet side, allowing pressure in the
system to build up slowly.
• Open controlled pressure line valve(s) and check setting by
means of the gauge(s). Set by means of the spring adjuster (2)
of the actuator.
(To increase pressure setting (or pressure differential), turn
adjusting screw clockwise to compress the spring. To decrease
the setting, turn adjusting screw counterclockwise to relieve
spring compression).
• Fully open stop valve on the inlet side of the regulator.
Maintenance
Replacing diaphragm
On Spring Diaphragm Actuators
(500 Series Regulators - Figure 1)
• Remove the controlled pressure line from the diaphragm case
(13) and relieve all spring compression by unscrewing spring
adjuster (2).
• Remove upper diaphragm case (13), [nuts (16) and screws (15)],
[not screws (15) on 150-750 psi range].
a) On 0.5-2 / 1.5-3 / 2-10 / 6-20 / 15-40 / 30-75 / 60-125 and
80-250 psi ranges:
Remove locknut (28), diaphragm washer (14) and diaphragm (11).
b) On 150-750 psi range:
Remove diaphragm (11).
Note: By means of a wrench applied on the plug stem nuts, hold
the actuator stem during this operation.
• Install new diaphragm and reassemble by reversing of the
above description order.
• Readjust the spring compression (see above).
On Differential Actuators
(500-50 Series Regulators - Figure 2)
a. On low pressure case design:
• Remove the high and low pressure lines from the
diaphragm case (13) and the diaphragm chamber (9).
• Relieve all spring compression by unscrewing spring
adjuster (2).
• Remove nuts (16) and cap screws (15). Remove upper
diaphragm case (13).
• Remove locknut (28), upper diaphragm plate (12), upper
O-Ring (25), washer (14) and diaphragm (11).
• Install new diaphragm and reassemble by reversing of
the above description order. Replace upper O-Ring (25) if
necessary.
• Readjust the spring compression (see above).
b. On high pressure case design:
• Remove the high and low pressure lines from the
diaphragm case (13) and the diaphragm chamber (9).
• Relieve all spring compression by uncrewing spring
adjuster (2).
• Remove nuts (16), upper diaphragm case (13) and
diaphragm (11).
• Install new diaphragm and reassemble by reversing of the
above description order.
• Readjust the spring compression (see above).
Replacing O-ring(s) (25)
(low and high pressure case)
On differential actuators, (Figure 2)
• Disassemble the actuator head as described on the
paragraph : “Replacing diaphragm”.
• Remove diaphragm chamber (9) with plunger S/A (24).
• With a wrench applied over O-Ring retainer (26), unscrew it
out of diaphragm chamber (9).
• Remove O-Ring (25), being careful not to damage plunger.
Install new O-Ring, replace and tighten O-Ring retainer (26).
• Reassemble and readjust spring compression.
Uniformly tighten all diaphragm case nuts (16) when
reassembling.
Regulator must be isolated and pressure vented before
disassembly.
It is necessary to proceed with adjustment before servicing.

DISTRIBUTOR
* Trademark of the General Electric Company.
Other company names and product names used in this document are
the registered trademarks or trademarks of their respective owners.
© 2014 General Electric Company. All rights reserved.
Visit our web-site:
www.fr-eps.com
E.P. & S. - FRANCE
24 bis rue de Picpus
75012 PARIS
Tel: +33 (0) 762 682 291
Tel: +33 (0) 650 590 965
ventes@fr-eps.com
E.P. & S. - CAMEROON
Immeuble Carré d’Or
Rue Soppo Priso Côté Chococho, Bonapriso
DOUALA
Tel: +237 6 52 12 70 95
Tel: +33 (0) 782 006 276
ventes@fr-eps.com
Table of contents
Other GE Controllers manuals

GE
GE SVI II AP User manual

GE
GE VAT2000 Series User manual

GE
GE DTR GEK-106305A User manual

GE
GE AF-650 GP Series User manual

GE
GE ZW4002 User manual

GE
GE GuardSwitch 300 Series User manual

GE
GE T60 User manual

GE
GE VersaMax IC200PWR001 User manual

GE
GE Multilin F650 User manual

GE
GE PACSystems* RX3i User guide