GE ACT17CWA User manual

Table of Contents
Parts and Functions
Interface Display ....................................1
Icons .............................................2
Dip Switch .........................................4
Operation
Mode Key .........................................6
Fan Key ...............................................6
Temperature Adjustment Keys .........................7
Special Function
Special Function Selection ............................8
Installer Settings
Adjust ECO Parameters .............................10
Child Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Lock Settings......................................11
Fahrenheit / Celsius ................................11
Temperature Compensation ..........................12
Forced Defrost/Cooling/Heating .......................12
Error Checks ......................................13
Mode Restriction ..................................14
Mode Combination Settings ..........................15
Wiring Instruction...................................15
Wired Controller
Installation and Operation Manual
ACT17CWA
• Please read this manual before use
• Please keep this manual for future reference. 49-5000395 Rev. 7
GEA 01-22

SUB
MAIN
Full Display
1
Parts and Functions
Interface Display

/
2
Room temperature display
(dip switch SW1-2 on).
Set temperature display
Filter
HRV (Heat Reclaim Ventilation), if HRV
function is set, it will display this icon
Error icon displays detected fault
ECO mode on
Central/lock when connected to a central
controller
UP/DOWN louver swing
LEFT/RIGHT louver swing
Child lock on
Parts and Functions
Icons

MAIN / SUB Main / Subordinate wired
controller
Quiet Fan Speed
(some models)
Low Fan Speed
Medium Fan Speed
High Fan Speed
Turbo Fan Speed
(some models)
Auto Fan speed is indicated by the display automatically
stepping from low to high repeatedly.
Auto Mode
Cooling Mode
Heating Mode
Fan Mode
3
Parts And Functions

4
Dip switch denition
Dip Switch SW1
Dip Switch
SW1 ON OFF Default
Sw1-1 Subordinate wired
controller
Main wired controller OFF
Sw1-2 Room temperature
display on
Room temperature
display o OFF
Sw1-3
Room temperature
collected from indoor unit
Room temperature
collected from controller OFF
Sw1-4 System remains o after
power loss
Auto restart after power
loss OFF
Sw1-5 Old protocol (models
developed before Aug.
2013)
New protocol OFF
Sw1-6 Backlight always on
Backlight 15 second auto
time out
OFF
Sw1-7 Reserved Reserved OFF
Sw1-8 Reserved Reserved OFF

5
Dip Switch SW2
Initialization
When the mini-split system is powered on 88.8 will ash be-
tween the Room Temperature display and the Set Temperature
display until communication is established with the indoor unit.
Press to power ON or power OFF the control. A tone
will be heard with every button press or when a command is
received by a remote control. If a conicting command is re-
ceived, then the tone will sound 3 times.
Audible Alert
Dip Switch
SW2 ON OFF Default
Sw2-1 Mode Lock Normal OFF
Sw2-2
No button conrmation tone. (Tone will
still sound when command is sent by
wireless remote.
Tone on OFF
Sw2-3 Reserved Reserved OFF
Sw2-4 Reserved Reserved OFF

Quiet Fan Speed
(some models)
Low Fan Speed
Medium Fan Speed
High Fan Speed
Turbo Fan Speed
(some models)
6
Mode key:
•
Each press of the MODE button will change the operating mode from
Auto – Cool – Heat – Fan – Dry (Dehumidication) – Auto …
• Each mode has its initial default fan speed.
Mode Key / Fan Key
Mode Fan speed Temperature
Auto Auto 76°F
Cool High 76°F
Heat Auto 76°F
Fan Low No temperature display
Dry (Dehumidication) Auto 76°F
Initial
State
Fan Key:
Each press of the FAN button will change the fan speed from
Auto – Quiet (some models) – Low – Medium – High – Turbo
(some models) – Auto …

7
Temperature Adjustment Keys: /
• Press the TEMP+ or TEMP- keys to change the temperature
by 1°F increments.
• The temperature set point range for Auto, Cooling, Heating
and Dry (Dehumidication) is 60°F~86°F (If ECO is on,
then temperature range will change per the ECO setting
parameters).
• The temperature is set independently under Auto, Cooling,
Heating and Dehumidify modes. Once the temperature is set
in each mode the setting will be saved for that mode.
• In fan mode, Temp +/- keys do not work.
Temperature

8
Special Function Selection:
With the control powered on, press and hold the TEMP+ for
5 seconds to enter the special function menu. All the special
function icons will display. Use the TEMP+ and TEMP- buttons
to move between icons. Use FAN button to select function.
Function Selection
Full display

9
Function Selection
50

10
Adjust ECO Parameters:
• Cooling: Power on the unit. Adjust set temperature to
86°F. Press and hold FAN and TEMP+ for 5 seconds. The
minimum allowable set temperature will be displayed in the
top right corner. Use TEMP+/- to change the parameter,
then press FAN save. The default minimum temperature is
73°F.
• Heating: Power on the unit. Adjust set temperature 60°F.
Press and hold FAN and TEMP- for 5 seconds. The
maximum allowable set temperature will be displayed in the
top right corner. Press TEMP+/- to change the parameter,
then press FAN to save. The default maximum temperature
is 79°F.
• Dry (Dehumidication) ECO parameters are the same as
Cooling.
Child Lock:
• Press and hold TEMP+ and TEMP- for 5 seconds to
activate/deactivate the Child Lock function. When the Child
Lock function is active, will appear.
Installer Settings

11
Central/Lock Function: /
Function is active only when system has a central control, such
as the YCZ-A004. This setting is activated only by the central
Control.
Fahrenheit Setting and Display:
• Fahrenheit to Celsius: Adjust set temperature to lowest
setting; 60°F when ECO is o. Press and hold TEMP- for
15 seconds. During the 15 second count the display will
beep once at 5 seconds and display error codes. Then after
another 5 seconds, the display will beep once again and
display 00, after 5 more seconds the display will change to
Celsius.
• Celsius to Fahrenheit: Adjust set temperature to highest
setting; 30°C when Eco is o. Press and hold TEMP+ for 15
seconds. During the 15 second count, the display will beep
once at 5 seconds and enter Special Functions menu. Then
after another 5 seconds, the display will show 00, after 5
more seconds the display will change to Fahrenheit.
Central Control On/O function only available.
Central Lock No functions available.
Lock Settings / Fahrenheit Setting

12
Set Temperature Compensation:
• With the display o, press and hold the FAN button for 5 seconds.
The display will then show 0 (default) or current compensation set-
ting. Use TEMP+/- buttons to adjust the compensation. Compensa-
tion can be set in 1° increments
+/- 8°F (0.5°C increments up to +/-4°C).
• Temperature compensation changes the ambient temperature
reading. If the system is sensing the ambient temperature at 72°F
and the compensation is set to -2° then the system will use 70°F in
its operation to heat or cool.
Forced Defrost:
• Set to Heating mode, high fan, and 86°F (30°C), or highest
temperature if ECO is on. Press TEMP+ 6 times within 5 seconds.
Three tones will conrm that the unit is in forced defrost mode.
Forced Cooling:
• Set mode to Cool. Tap ON/OFF. Tap any button, except ON/OFF,
to light the display. Press and hold ON/OFF for 5 seconds. LL will
display and the control will beep twice. To exit, turn o control and
turn it on again.
Forced Heating:
• Set mode to Heat. Tap ON/OFF. Tap any button, except ON/OFF,
to light the display. Press and hold ON/OFF for 5 seconds. HH will
display and the control will beep twice. To exit, turn o control and
turn it on again.
Temperature Compensation

13
How to check error:
• If there is an error, will display.
• Check error: Press and hold TEMP- button for 5 seconds.
The error history will appear in the top right corner. The
current error will appear in the middle of the screen. If there
is no error, “--” will display.
Error Checks

14
Mode Restriction Function:
• When SW2-1 is on, the system mode lock is on. This will
lock the mode to Heat, Cool, Dry or Fan. No button press
can change mode. All other control functions are available
such as fan speed, set temperature, and on/o.
• Mode can still be changed with a wireless control, another
wired control, or a central control.
• When setting mode lock, have control set to desired mode.
Set dipswitch SW2-1 to ON. Disconnect and reconnect
system power.
Checking Parameters (only applies to some models):
• Press and hold TEMP+ for 10 seconds to check the
parameters. The parameters will appear in the middle of the
screen to show indoor address (00-15), Letters will appear
after decimal display (AbCdEF). The detailed parameters will
show on the top right corner. See table for denitions.
• If the control is connected to multiple indoor units, each
indoor unit can be viewed by pressing the FAN button. Then
use TEMP+/- to switch between connected indoor units.
Mode Restriction

A BC
A BC
15
• With the control o,
press and hold the MODE
button for 10 seconds.
Use the FAN button to
change available modes of
operation. 4 is default.
Mode Combination Setting
A: One control on one indoor
Indoor 1
Wired controller
Polar wire
Wired controller
Wired Controller Wiring Instruction
Wiring Connections
1. Cassette (AB…AL…MVAB…MVAL…)
Ducted (AD…AM…MVAD…MVAH…)
MRV Wall Mount (MVAW…)
2 Non-MRV Wall mount (AW...)
Indoor PCB board
Wired controller
LED3/R
SW1
CN4
CN3
CN5 CN1
A BC AB C
CN2
1 2 3 4
LED1/R
LED2/G
WK-B
LED4/G
A B C
Display Description Value
A Indoor sensor - Ambient (Tai) Temperature °F (°C)
b Indoor sensor - Vapor (Tc1) Temperature °F (°C)
C Indoor sensor - Liquid (Tc2 Temperature °F (°C)
d Indoor EEV position Half of actual position
E Indoor unit address Shown in hexadecimal
F Indoor unit central address Shown in hexadecimal
Parameter Inquiry:
Mode Combination Setting:

16
A BC
Indoor 2
Wired controller
A BC A B C
A BC
Indoor 1
Wired controller
A BC A B C
Indoor N
Wired controller
Indoor 15
Wired controller
Indoor 16
(main unit)
Wired controller
Control wiring of wired
controller, polar.
Wired controller
B: One Controller for up to 16 indoor
1. Cassette (AB…AL…MVAB…MVAL…)
Ducted (AD…AM24…MVAD…MVAH…)
MRV Wall Mount (MVAW…)
A BC
Indoor 2
Wired controller
A BC A B C
A BC
Indoor 1
Wired controller
A BC A B C
Indoor N
Wired controller
Indoor 15
Wired controller
Indoor 16
(main unit)
Wired controller
Control wiring of wired
controller, polar.
Wired controller
2. Ducted (AM36...AM48…)
• Addressing Indoor Units
• Each indoor unit must hvae a unique
address.
• Compact Cassette (AB…) use SW02_1-4
• Large Cassette (AL…) use SW3_5-8
• Slim Duct (AD…) use SW03_1-4
• High Static Duct (AM24…) use SW03_5-8
• High Static Duct (AM36…AM48…) use
SW02_1-4
• All MRV indoor (MV…) use SW01_1-4
Dipswitch position Dipswitch position
Unit # 1 2 3 4 Unit # 1 2 3 4
5 6 7 8 5 6 7 8
0* o o o o 8on o o o
1o o o on 9on o o on
2o o on o 10 on o on o
3o o on on 11 on o on on
4o on o o 12 on on o o
5o on o on 13 on on o on
6o on on o 14 on on on o
7o on on on 15 on on on on
* Unit 0 is connected directly to the control and is main

17
3. Non-MRV Wall Mount (AW...)
Wiring Connections
SW1
Wired controller
Unit 0 ... ...
(main unit)
Unit 1 Unit 15
A B C A B BB
CCC
AAA B C
A B C
SW1 SW1
High Wall
WK-B
(1) The rst high wall indoor unit to
connect with WK-B is considered as
main unit 0.
(2) Remove the jumpers on CN3 and
CN4.
(3) The wired control must connect to CN1
of the WK-B main unit (unit 0).
(4) Connect the CN2 on the main unit
(unit 0) to the next WK-B subordinate
unit (unit 1) CN1 or CN2. Only the
main unit (unit 0) must use CN1 for
the control. All others may use CN1 or
CN2. See Picture 2.2.
(5) Set the dipswitch address of the WK-B
adapter. The adapters ship with all
switches o (main).
C:
Two controllers on one indoor
Notice: For wired controller connection and warranty details, please
follow the corresponding indoor unit installation instructions.
LED3/R LED4/G
ABCABC
Wired controller Wired controller
Polar wire
SW1
CN4
CN3
CN5 CN1
A BC A BC
CN2
1 2 3 4
LED1/R
LED2/G
WK-B
Indoor PCB board
2. Non-MRV Wall Mount (AW…)1. Cassette ( AB…AL…MVAB…MVAL…)
Ducted (AD…AM…MVAD…MVAH…)
MRV Wall Mount (MVAW…)
A BC
A BC
A BC
Indoor 1
Wired controller
Polar wire
Wired controller
Polar wire
Wired controller
Dipswitch position Dipswitch position
Unit # 1 2 3 4 Unit # 1 2 3 4
0* o o o o 8on o o o
1o o o on 9on o o on
2o o on o 10 on o on o
3o o on on 11 on o on on
4o on o o 12 on on o o
5o on o on 13 on on o on
6o on on o 14 on on on o
7o on on on 15 on on on on
* Unit 0 is connected directly to the control and is main

18
C
B
A
red
yellow
white
Wired Controller Wiring Instruction
Communication Wiring
*Ground only one end of the shielded cable
Wiring Diagrams
Communication wiring length (m/ft) Wire Size
< 100m/328ft 0.3mm2x3-core shielded wire
(22AWG,3wire)
≥100m/328ft and <200m/656ft 0.5mm2x3-core shielded wire
(20AWG,3wire)
≥200m/656ft and <300m/984ft 0.75mm2x3-core shielded
wire (18AWG,3wire)
≥300m/984ft and <400m/1312ft 1.25mm2x3-core shielded wire
(16AWG,3wire)
≥400m/1312ft and <500m/1640ft 2mm2x3-core shielded wire
(14AWG,3wire)

19
2. Secure the back panel to the
wall using screws.
3. Connect the control
wires.
4. Attach the control to the
back panel by aligning the
bottom tabs and then press-
ing the top edge.
Wired Controller Wiring Instruction
Installation Diagrams
1. To take the front panel and back
panel apart, slide the front panel
up and press down on the back
panel.
Other manuals for ACT17CWA
1
Table of contents
Languages:
Other GE Controllers manuals
Popular Controllers manuals by other brands

Omron
Omron NJ-series Network Connection Guide

Infineon
Infineon XDPP1100 user manual

Lumen
Lumen WF-C user manual

Johnson Controls
Johnson Controls CVM03050 installation guide

J&E Hall
J&E Hall Fridgewatch 4000 Installation, operating and maintenance manual

BIFFI
BIFFI ALGA - EAC Installation, operation and maintenance manual

FW Murphy
FW Murphy Centurion C5 M-VIEW Touch Series Operation manual

Moore Industries
Moore Industries 532 user manual

Arcadia
Arcadia REPTILE CONTROLLER RACRE Installation and maintenance instructions

Centurion
Centurion D3 quick guide

Leviosa
Leviosa Zone user manual

Walchem
Walchem WCU Series instruction manual