
Item Description
1. Damper frame
2. Duct outlet
3. Fan (not limited to centrifugal)
4. 3/8 in. (10mm) minimum diameter bolts
5. Actuator
The actuators are to be installed to function per system 
requirements and to be controlled by smoke detection 
devices. 
FAN ISOLATION APPLICATION
 For air handling equipment isolation, leakage rated 
dampers are designed to operate with blades running 
horizontally. Dampers can be installed in a vertical 
or horizontal position. Sealants and damper seal 
materials meet the requirements of NFPA90A for smoke 
developed rating (<50) and flame spread index (<25) as 
tested per UL723/ASTME84-91A/NFPA 255. Dampers 
can be attached to the fan system discharge or inlet 
without being 24 in. (610mm) of a smoke barrier when 
used as an air handling equipment isolation damper.
4
1
2
3
Size Limitations
* All multiple section assemblies are factory assembled.
5
in inches 
(mm)
Maximum single 
section size
Maximum single 
section size when 
multi-section 
assembly
Maximum overall 
multi-section size*
HSD-401 60 x 60
(1524 x 1524)
48 x 60
(1219 x 1524)
120 x 60
(3048 x 1524) or
48 x 120
(1219 x 3048)
1. SMOKE DAMPER REQUIREMENTS AND 
APPLICATION
 Smoke dampers are required to close and prevent the 
passage of air and smoke through ducts or ventilation 
openings in smoke barriers. Smoke dampers are also 
applied in engineered smoke control systems to establish 
air pressure differentials and thereby prevent the spread 
of smoke. HSD-401 damper is designed to operate with 
blades running horizontally. Dampers can be vertically or 
horizontally installed at, in accordance with NFPA-90A, 
or adjacent to the point where the duct passes thru the 
smoke barrier. 
2. LOCATION OF DAMPER IN DUCTWORK
 Place the damper assembly in its proper position relative 
to the barrier. The plane of the closed damper blades 
must be within 24 in. (610mm) of the rated smoke barrier 
and before any duct inlets or outlets.
3. ATTACHING DAMPER TO THE DUCT
 HSD-401 damper is a flange mounted to the duct, sleeve, 
or wall opening with 3/8 in. (10mm) minimum diameter 
bolts and spaced a maximum of 6 in. (152mm) apart, on 
center. Dampers can be attached directly to the fan, if 
required.
4. SEALING THE INSTALLATION
 After installing the damper in the ductwork, seal the 
joint between the damper frame and the duct using Dow 
Corning RTV 732 Sealant. Make sure to press the sealant 
into the joint to guarantee a proper seal. Use the minimum 
amount of material required to completely seal the joint.
5. ACTUATOR CONNECTIONS
 Electrical and/or pneumatic connections to damper 
actuators should be made in accordance with wiring and 
piping diagrams developed in compliance with applicable 
codes, ordinances and regulations.