02/19 Models 3600/3601/3602/3603/3610/3611/3612/3620/3621/3630/3601FR/ Page 2 of 10
3602FR/3603FR/3610FR/3611FR/3612FR/3620FR/3621FR/3630FR
RECOMMENDED TOOLS: Hack saw, PVC solvent weld glue, screwdriver, level, 12"
adjustable wrench, 10" pipe wrench, 1/8” or 5/32” tamper-resistant hex key wrench (supplied),
9/16”, 1/2", 7/16” socket wrench or open- end wrench.
LOCATION OF UNIT: The Model 36XX/36XXFR Modular Fountain System can be assembled
to be wheelchair accessible. When the pedestal arm is installed in the high orientation, the
height dimensions shown on the model specification sheet meet current ADA requirements.
When installing this unit, local, state or federal codes should be adhered to. If height other
than shown is required, then dimensions must be adjusted accordingly.
SUPPLY LINE: The minimum recommended line size is 1/2“IPS with 30-90 psi (2-6 ATM)
flowing pressure. Where sediment or mineral content is a problem, an inlet filter is
recommended.
PLUMBING CONNECTIONS: Inlet is 3/8“O.D. quick-connect fitting. Waste outlet is female 1-
1/2” PVC pipe. Plumbing connections vary depending on how the unit is configured during
assembly. The pedestal (3674/3675) is supplied with various fittings and PVC pipe for a top
waste connection. The arm (3671/3673) is supplied with various fittings, waste tee, and elbow
for a side arm waste connection. If two arms are attached to the pedestal at the same height,
a 1-1/2” PVC cross is required (not supplied) for connecting the waste lines.
MAINTENANCE:
For 36XX models- Periodically clean the pushbutton strainer. Refer to 5874 Series Valve
Operation and Maintenance Sheet for more information.
For 36XXFR models- Refer to 6518 Operation and Maintenance Sheet for more information.
INSTALLATION PROCEDURE
The 36XX Modular Outdoor Drinking Fountain is a system in interchangeable components that
can be installed in the configuration best suited to the installation site. The fountain can re-
configured after installation as desired. Follow the installation procedures outlined in the
installation diagram. 36XXFR versions must be connected to 6518 series freeze resistant bury
valve. See 6518 installation manual for instructions.
GENERAL NOTES:
1. For all plastic push-in type fitting connections, only connect NSF-61 copper or
plastic tubing. Stainless steel or glass tubing is not recommended. The
following assembly instructions must be followed to ensure a watertight
connection:
a. Cut tubing square and clean.
b. Mark from end of tube the length of insertion (See table below).
c. Push tube into the fitting until it bottoms out.
d. To remove, depress collet and pull tubing out.
Tube Sizes
Tolerance Insertion Depth