2
Doc. D004970, issue 6,
2016-01-18
Helvar 311 Ceiling PIR Detector: Datasheet
Technical Data
Connections
External power / DALI: Removable connector block;
Wire size: 0.5mm² –1.5mm²
solid or stranded
Cable rating: All cables must be mains rated.
Max. length: 300 m @ 1.5mm²
Power
DALI supply input: 13 V to 22.5 V
DALI consumption: 15 mA
Sensors
Presence detector: PIR: Passive infrared presence
detector
Infrared receiver: For remote control commands.
Note: Adjust sensitivity using
Designer or Toolbox (not by
remote control unit).
Mechanical data
Mounting hole diameter: 68 mm
Bezel diameter: 76 mm
Material (casing): Flame-retardant ABS
Finish / Colour: Matt / White RAL 9003
Weight: 58 g
IP code: 311: IP40
311P*: IP55
311M*: IP55
* Only when the supplied
gasket is used and the unit is
mounted onto Helvar’s SBB-P
back box or flush in a ceiling.
Operating conditions
Ambient temperature: 311 & 311P: 0 °C to +35 °C
311M: –30 °C to +35 °C
Note: The temperature difference
between the detection target and
the background must be at least
4°C.
Relative humidity: Max. 90 %, noncondensing
Storage temperature: 311 & 311P: –10 °C to +70 °C
311M: –30 °C to +70 °C
Conformity and standards
EMC emission: EN 61000–6–1
EMC immunity: EN 61000–6–3
Safety: EN 60730–1
Environment: Complies with WEEE and RoHS
directives.
Version information
Software version: 6.08
Hardware version: Rev. 2
Dimensions (mm)
Connections
DALI+
DALI–
Ø 76 61
68
58