Copyright HK Instruments 2018 www.hkinstruments. Installaon version 6.0 2018
INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-MOD Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
ThankyouforchoosinganHKInstrumentsDPT-MODseriesdier-
enalpressuretransmier.TheDPT-MODseriesisintendedforuse
incommercialenvironments.DPT-MODisamulfunconaltrans-
mierformeasuringvolumeow,velocity,andstacanddieren-
alpressure.Themeasurementscanbereadandtheconguraon
done via Modbus communicaon. DPT-MOD requires less wiring
than the tradional 3-wire transmiers because mulple devices
can be connected on serial line. DPT-MOD can alsobe used with
several dierent measurement probes such as FloXact™ or pitot
tube,andairdampers.
The DPT-MOD series is comprised of DPT-MOD-2500 and DPT-
MOD-7000 with measurement ranges of -250...2500 Pa and
-250...7000Parespecvely.Allmodels come withdisplayandop-
onalautozerocalibraon.
DPT-MODseriesdevicesarecommonlyusedinHVAC/Rsystemsfor:
•fan,blowerandltermonitoring
•pressureandowmonitoring
•valveanddampercontrol
•pressuremonitoringincleanrooms
•airowmonitoringacrosscentrifugalfansandblowers
•in-ductairoworpressuremonitoring
•measuringairoworpressureinVAVapplicaons
SPECIFICATIONS
Performance
Accuracy (at applied pressure):
Model2500:
Pressure<125Pa=1%+±2Pa
Pressure>125Pa=1%+±1Pa
Model7000:
Pressure<125Pa=1.5%+±2Pa
Pressure>125Pa=1.5%+±1Pa
(Accuracyspecicaonsinclude:generalaccuracy,
linearity,hysteresis,longterm
stability,andrepeonerror)
Thermal eects:
Temperaturecompensated0...50°C
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zero point calibraon:
Automacautozero,manualpushbuonorviaModbus
register
Response me:
1.0−20s,selectableviamenuorviaModbusregister
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat(11bits)inRTUmode:
 CodingSystem:8-bitbinary
 BitsperByte:
1 start bit
  8databits,leastsignicantbitsent
  rst
  1bitforparity
  1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1−247addressesselectablein
conguraonmenu
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Pressure units (select via menu):
Pa,kPa,mbar,inWC,mmWC
Flow units (select via menu):
Volume:m3/s,m3/hr,cfm,l/s
Velocity:m/s,/min
Measuring element:
MEMS,noow-through
Environment:
Operangtemperature:-20...50°C,
withautozero(-AZ)calibraon-5...50°C
Storagetemperature:-40...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:90.0x95.0x36.0mm
Weight:
150g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case:ABS
Lid:PC
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Display
2-linedisplay(12characters/line)
 Line1:Volumeorvelocitymeasurement
 Line2:Pressuremeasurement
Size:46.0x14.5mm
Electrical connecons:
4-screwterminalblock
Wire:0.2–1.5mm2(12–24AWG)
Cable entry:
Strainrelief:M16
Knockout:16mm
Pressure ngs
Maleø5.0mmand6.3mm
Electrical
Supply voltage:
24VACorVDC±10%
Power consumpon:
<1.3W
Output signal:
viaModbus
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU
APPLICATIONS
INTRODUCTION WARNING
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU
Copyright HK Instruments 2018 www.hkinstruments. Installaon version 6.0 2018
SCHEMATICS
DIMENSIONAL DRAWINGS
Figure 1a - Surface mounng
MOUNTING THE DEVICE CONTINUED
Figure 1b - Mounng orientaon
Figure 1c - Applicaon connecons
Connecon for display
Terminal block
Pressure
sensor
Menu buons
LED
SELECT
UP
DOWN
ZERO
B
A
24 V
GND
90.0
77.0
71.5
53.0
4.2
95.0
36.0
DPT
Thepressuretubesareconnectedtoaowmeasurementprobe(i.e.FloXact),ortothe
measurementportsspeciedbythefanmanufacturer.PleaseseetheFloXactinstallaon
guideorthefanmanufacturer’stechnicalspecicaonsformoreinformaon.
YES NO NO
INSTALLATION
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecablethroughthestrainreliefand
connectthewirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
STEP 2: WIRING DIAGRAMS
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable.
2)Connectthewiresasshowningure2.
3)Tightenthestrainrelief.
Figure 2 - Wiring diagram
B
A
24 V
GND
+ Power supply
24 VDC / 24 VAC
Modbus
STEP 1: MOUNTING THE DEVICE
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Pressure
Flow
Static pressure Filter/Damper
monitoring
Fan/Blower
monitoring
Not
connected
Copyright HK Instruments 2018 www.hkinstruments. Installaon version 6.0 2018
CONFIGURATION CONTINUED
NOTE:Theowunit
none
isselectedbydefaultandthedisplay
showsonlythepressurereading.
1)Selectthefunconingmodeoftheowmeter:
-Select
Manufacturer
whenconnecngDPT-MODtoafanwith
pressuremeasurementpoints
-Select
Commonprobe
whenusingDPT-MODwithacommon
measurmentprobethatfollowstheformula:
 q=k∙√∆P
(i.e.FloXact)
STEP 3: CONFIGURATION
2)If
Commonprobe
selected:selectmeasurementunitsusedinthe
formula(akaFormulaunit)(i.e.l/s)
MANUFACTURER
Common probe
SELECT
UP
DOWN
Common probe Flakt Woods
SELECT
UP
DOWN
FORMULA UNIT
l/s
SELECT
UP
DOWN
3)SelectK-value
a.Ifmanufacturerselectedinstep1:
EachfanhasaspecicK-value.SelecttheK-valuefromfanmanufac-
turer’sspecicaons.
Manufacturer: K-value:
Fläktwoods k=0,3...99
Rosenberg k=37...800
Nicotra  k=10...1500
Comefri  k=10...2000
Ziehl  k=10...1500
Ebm-papst k=10...1500
Gebhardt k=50...4700
6)Responseme:Selectresponsemebetween1.0–20s.
RESPONSE TIME
20 s
SELECT
UP
DOWN
10)Pushselectbuontosavechangesandtoexitmenu.
SELECT
EXIT MENU
SELECT
b. If
Commonprobe
selectedinstep1:
Each common probe has a specic K-value. Select the K-value from
commonprobemanufacturer’sspecicaons.
AvailableK-valuerange:0.001...9999.000.
K-VALUE
9000.000
SELECT
UP
DOWN
7)SelecttheaddressforModbus:1...247.
8)Selectthebaudrate:9600/19200/38400.
ADDRESS
99
SELECT
UP
DOWN
BAUD RATE
9600
SELECT
UP
DOWN
9)Selecttheparitybit:None/Even/Odd.
PARITY BIT
NONE
SELECT
UP
DOWN
STEP 4: ZEROING THE DEVICE
NOTE! Always zero the device before use.
Tozerothedevicethreeoponsareavailable:
1)ManualPushbuonzeropointcalibraon
2)Autozerocalibraon
3)ViaModbusregister
Doesmytransmierhaveanautozerocalibraon?Seetheproductla-
bel.Ifitshows-AZinthemodelnumber,thenyouhavetheautozero
calibraon.
1)ManualPushbuonzeropointcalibraon
NOTE: Supply voltage must be connected at least one hour prior to
zeropointadjustment.
a)Disconnectbothpressuretubesfromthepressureportslabeled+
and–.
b)PushdownthezerobuonunltheLEDlight(red)turnsonandthe
displayreads“zeroing”(displayopononly).(seegure3)
c)Thezeroingofthedevicewillproceedautomacally.Zeroingis
completewhentheLEDturnso,andthedisplayreads0(display
opononly).
d)ReinstallthepressuretubesensuringthattheHighpressuretube
isconnectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
5)Selectowunitfordisplay:
Flowvolume:m3/s,m3/h,cfm,l/s,none(default)
Velocity:m/s,f/min,none
4)Selectpressureunitfordisplay:Pa,kPa,mbar,inWC,mmWCor
none.
PRESS.UNIT
Pa
SELECT
UP
DOWN
FLOW UNIT
m3/s
SELECT
UP
DOWN
Copyright HK Instruments 2018 www.hkinstruments. Installaon version 6.0 2018
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsidered tostart on thedelivery dateof theproduct.If adefect
in raw materials or a producon awis found, theseller is obligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
byrepairingthedefecveproductorbydeliveringfreeofchargetothe
buyeranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, ood or other natural phenomenon, normal wear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warranty requires that the buyer hascorrectly fullled his/herdues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anew warrantyforgoods thathavebeenreplacedorrepairedwithin
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device, or if needed, a new part or device, but not installaon or ex-
change costs. Under no circumstance is the seller liable for damages
compensaonforindirectdamage.
2)Autozerocalibraon
If the device includes the oponal autozero circuit, no acon is re-
quired.
Autozero calibraon (-AZ) is an autozero funcon in the form ofan
automaczeroingcircuitbuiltintothePCBboard.Theautozerocali-
braon electronically adjusts the transmier zero at predetermined
me intervals(every10minutes).Thefuncon eliminates all output
signaldriduetothermal,electronicormechanicaleects,aswellas
theneedfortechnicianstoremovehighandlowpressuretubeswhen
performing inial or periodic transmier zero point calibraon. The
autozeroadjustmenttakes4secondsaerwhichthedevicereturnsto
itsnormalmeasuringmode.Duringthe4secondadjustmentperiod,
theoutputanddisplayvalueswillfreezetothelatestmeasuredvalue.
Transmiers equipped with the autozero calibraon are virtually
maintenancefree.
3)ViaModbusregister
Makesurethereisnopressureintheductwhenthezeroingisdone
viaModbusregister.
a) Disconnect both pressure tubes from the pressure ports labeled +
and –.
b) Push down the zero buon (joysck) unl the LED light (red)
turns on and the display reads “zeroing” (display opon only). (see
Figure 6)
c) The zeroing of the device will proceed automacally. Zeroing is
complete when the LED turns off, and the display reads 0 (display
opon only).
d) Reinstall the pressure tubes, ensuring the High pressure tube is
connected to the port labeled +, and the Low pressure tube is
connected to the port labeled −.
Press down buon
LED turns ON
Display reads “Zeroing”
LED
Figure 3
ZEROING THE DEVICE CONTINUED
STEP 5: MODBUS REGISTERS
Register Parameter descripon Data Type Value Range
3x0001 Programversion 16bit 0...9900 0,00...99,00
3x0002 Pressurereading 16bit -250...2500/7000 -250...2500/7000Pa
3x0003 Flowm3/s 16bit 0...10000 0...100m3/s
3x0004 Flowm3/h 16bit 0...30000 0...30000m3/h
3x0005 Flowcfm 16bit 0...30000 0...30000cfm
3x0006 Flowl/s 16bit 0...3000 0...3000l/s
3x0007 Velocitym/s 16bit 0...1000 0...100m/s
3x0008 Velocityf/min 16bit 0...5000 0...5000f/min
Funconcode04-Readinputregister
MODBUS REGISTERS CONTINUED
Funconcode06-Writesingleregister
Register Parameter descripon Data Type Value Range
4x0001 Manufacturer 16bit 0...7 0...7
4x0002 Formulaunit(Manufacturer=7) 16bit 0...5
0:m3/s,1:m3/h,2:cfm,3:l/s,
4:m/s,5:f/min
4x0003 K-factorinteger 16bit 0...9999 0...9999
4x0004 K-factordecimal 16bit 0...999 0...999
4x0005 Responseme 16bit 1...20 1...20s
Funconcode16-Writemulpleregisters
Register Parameter descripon Data Type Value Range
4x0001 Manufacturer 16bit 0...7 0...7
4x0002 Formulaunit(Manufacturer=7) 16bit 0...5
0:m3/s,1:m3/h,2:cfm,3:l/s,
4:m/s,5:f/min
4x0003 K-factorinteger 16bit 0...9999 0...9999
4x0004 K-factordecimal 16bit 0...999 0...999
4x0005 Responseme 16bit 1...20 1...20s
Funconcode05-Writesinglecoil
Register Parameter descripon Data Type Value Range
0x0001 Zeropointcalibraon Bit0 0...1 On-O
WARRANTY POLICY
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
Funconcode03-Readinputholdingregister
Register Parameter descripon Data Type Value Range
4x0001 Manufacturer 16bit 0...7 0...7
4x0002 Formulaunit(Manufacturer=7) 16bit 0...5
0:m3/s,1:m3/h,2:cfm,3:l/s,
4:m/s,5:f/min
4x0003 K-factorinteger 16bit 0...9999 0...9999
4x0004 K-factordecimal 16bit 0...999 0...999
4x0005 Responseme 16bit 1...20 1...20s

This manual suits for next models

2

Other HK Instruments Transmitter manuals

HK Instruments DPT2500-R8 Series Instruction manual

HK Instruments

HK Instruments DPT2500-R8 Series Instruction manual

HK Instruments KLU 100 User manual

HK Instruments

HK Instruments KLU 100 User manual

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments DPT-Priima Series User manual

HK Instruments

HK Instruments DPT-Priima Series User manual

HK Instruments RHT-MOD Duct Series User manual

HK Instruments

HK Instruments RHT-MOD Duct Series User manual

HK Instruments CDT-MOD-2000 Duct Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Duct Series User manual

HK Instruments DPT-IO-MOD Series User manual

HK Instruments

HK Instruments DPT-IO-MOD Series User manual

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments CDT2000 Series User manual

HK Instruments

HK Instruments CDT2000 Series User manual

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments DPT-CR-MOD Series User manual

HK Instruments

HK Instruments DPT-CR-MOD Series User manual

HK Instruments DPT-Flow-1000 Quick start guide

HK Instruments

HK Instruments DPT-Flow-1000 Quick start guide

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments DPT-R8 Series User manual

HK Instruments

HK Instruments DPT-R8 Series User manual

HK Instruments CMT Series User manual

HK Instruments

HK Instruments CMT Series User manual

HK Instruments RHT DUCT Series User manual

HK Instruments

HK Instruments RHT DUCT Series User manual

HK Instruments DPT Series User manual

HK Instruments

HK Instruments DPT Series User manual

HK Instruments DPT-Flow Series User manual

HK Instruments

HK Instruments DPT-Flow Series User manual

HK Instruments DPT-Priima Series User manual

HK Instruments

HK Instruments DPT-Priima Series User manual

HK Instruments SIRO Series User manual

HK Instruments

HK Instruments SIRO Series User manual

HK Instruments DPT-Priima Series User manual

HK Instruments

HK Instruments DPT-Priima Series User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

Popular Transmitter manuals by other brands

DGFLOW TEEVALVE 10 1 1/2 Operator and  maintenance manual

DGFLOW

DGFLOW TEEVALVE 10 1 1/2 Operator and maintenance manual

Entrematic BIXLR12 Installation and use manual

Entrematic

Entrematic BIXLR12 Installation and use manual

Metrix ST5491E installation manual

Metrix

Metrix ST5491E installation manual

Blu Stream Multicast IP250UHD-TX user manual

Blu Stream

Blu Stream Multicast IP250UHD-TX user manual

Tecnocontrol TS220EC-S user manual

Tecnocontrol

Tecnocontrol TS220EC-S user manual

Watchguard CMR24WAT user guide

Watchguard

Watchguard CMR24WAT user guide

IMG STAGE LINE TXS-606HSE/2 instruction manual

IMG STAGE LINE

IMG STAGE LINE TXS-606HSE/2 instruction manual

J-TECH MultiCast Quick setup guide

J-TECH

J-TECH MultiCast Quick setup guide

Veris Industries G Series installation guide

Veris Industries

Veris Industries G Series installation guide

Status Pro T250 instruction manual

Status Pro

Status Pro T250 instruction manual

Linear MULTI-CODE 1051 manual

Linear

Linear MULTI-CODE 1051 manual

MTS Sensors Level Plus Interface manual

MTS Sensors

MTS Sensors Level Plus Interface manual

Emcee TTU500FA user manual

Emcee

Emcee TTU500FA user manual

Vaisala HUMICAP HMT330 SERIES user guide

Vaisala

Vaisala HUMICAP HMT330 SERIES user guide

Kramer VP-300THD user manual

Kramer

Kramer VP-300THD user manual

ADEMCO 5817CB quick start guide

ADEMCO

ADEMCO 5817CB quick start guide

Simu 5C instructions

Simu

Simu 5C instructions

PST PST-UM-2010-EN-02 user manual

PST

PST PST-UM-2010-EN-02 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.