Novus TxIsoRail-HRT User manual

NOVUS AUTOMATION 1/4
TxIsoRail
-HRT
TEMPERATURE TRANSMIT
TER - OPERATING MANUAL – V1.0x D
INTRODUCTION
The TxIsoRail-HRT is a configurable DIN rail mount temperature
transmitter widely required in various industrial processes. Its
universal input can be configured to read RTDs, thermocouples and
mV signals.
It converts the input signal into a 4-20 mA linear output proportional
to the configured range. The TxIsoRail-HRT uses the HART®
communication protocol over the 4-20 mA output current loop.
The input and output are electrically isolated, enhancing their
performance and user and system safety.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in
Table 1, along with their minimum and maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E and B according to
IEC 60584 (ITS-90).
Impedance >> 1 MΩ
Pt100: Excitation 0.15 mA, α= 0.00385, according IEC 60751
(ITS-90).
Pt1000: Excitation 0.20 mA, α= 0.00385, according IEC 60751
(ITS-90).
NTC R25: 10 kΩ±1 %, β25/85 = 3435
Voltage: 0 to 50 mVdc. Impedance >> 1 MΩ
Sensor Type
Maximum Measurement
Range
Minimum Measurement
Range
Thermocouple K
-150 to 1370 °C
(-238 to 2498 °F)
50 °C
(122 °F)
Thermocouple J
-100 to 760 °C
(-148 to 1400 °F)
50 °C
(122 °F)
Thermocouple R
-50 to 1760 °C
(-58 to 3200 °F)
200 °C
(392 °F)
Thermocouple S
-50 to 1760 °C
(-58 to 3200 °F)
200 °C
(392 °F)
Thermocouple T
-160 to 400 °C
(-256 to 752 °F)
50 °C
(122 °F)
Thermocouple N
-270 to 1300 °C
(-454 to 2372 °F)
50 °C
(122 °F)
Thermocouple E
-90 to 720 °C
(-130 to 1328 °F)
50 °C
(122 °F)
Thermocouple B
500 to 1820 °C
(932 to 3308 °F)
200 °C
(392 °F)
Pt100
-200 to 650 °C
(-328 to 1202 °F)
30 °C
(86 °F)
Pt1000
-200 to 650 °C
(-328 to 1202 °F)
30 °C
(86 °F)
NTC
-30 to 120 °C
(-22 to 248 °F)
10 °C
(50 °F)
Voltage 0 to 50 mV 3 mV
Table 1 – Sensors accepted by the transmitter
Switch-on delay: < 10 s with factory damping filter configured. The
accuracy is only guaranteed after 15 min.
Terms of reference: Ambient: 25 ° C (77 °F); voltage: 24 Vdc, load:
250 Ω. 10 minutes required for stabilization time after configuration.
Temperature Effect: < 0.05 % / 25 °C (77 °F)
Response time: Typical 6 s using factory damping filter.This is the
maximum time between a temperature step being applied in the input
and the output reaching 90 % of the corresponding value.
HART Protocol Version: 7
RTD cable resistance effect: 0.005 °C / Ω
Maximum allowable cable resistance for RTD: 25 Ω
Accuracy: Calibration error in relation to sensor measuring range.
Sensor Type
CURRENT LOOP
HART
Typical
Error
Maximum
Error
Typical
Error
Maximum
Error
Pt100
(-200 to 650 °C)
0.08 % 0.15 % 0.05 % 0.15 %
Pt1000
(-200 to 650 °C)
0.07 % 0.15 % 0.04 % 0.15 %
K, J, R, S, T, N,
E, B 0.07 % (*) 0.15 % (*) 0.04 % (*) 0.15 % (*)
mV
0.07 %
0.15 %
0.04 %
0.15 %
NTC
0.20 °C
(0.36 °F)
0.45 °C
(0.81 °F)
0.15 °C
(0.27 °F)
0.45 °C
(0.81 °F)
Table 2 – Input accuracy
(*) Add cold junction compensation: < ± 1 °C (1.8 °F).
Power supply influence: < 0.005 % / V typical (percentage of the
full measure range).
Output (4-20 mA):4-20 mA current, 2-wires; and proportional to the
configured range.
Output Resolution (4-20 mA): 0.25 µA
Power supply: 8.5 to 36 Vdc (output 4-20 mA)
Maximum load (RL): RL (max.) = (Vdc – 8.5) / 0.0215 [Ω]
Where: Vdc = Power supply voltage (8.5 to
36 Vdc)
Operating Temperature: -40 to 85 °C (-40 to 185 °F)
Humidity: 0 to 90 % RH
It features electrical isolation between input and output: 1.5 kVrms
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Connection Wire Cross Section: 0.14 to 1.5 mm²
Screw Tightening: 0.8 Nm.
Housing: ABS UL94-HB.
Certifications: CE and HART®.

TxIsoRail-HRT
NOVUS AUTOMATION 2/4
CONFIGURATION
When the transmitter is used with the factory setting, no further
action is required and the transmitter is ready to be installed.
Changes to the configuration are possible through the TxConfig II
software, provided free of charge.
The TxConfig II configuration software allows the device configuration.
A TxConfig-HRT interface is required to allow the communication
between a computer and the device. The Txconfig II configuration
software is continuously updated and new versions can be downloaded
at no charge from the manufacturer’s website. To install, execute the
TxConfigIISetup.exe file and follow the instructions.
The interface connects the transmitter to the computer, as shown in
Fig. 1:
Fig. 1 – TxConfig-HRT interface connection to the TxIsoRail-HRT
SOFTWARE CONFIGURATION:
Fig. 2– TxConfig II software main screen
The fields in the screen mean:
1. General Information: This field shows information that identifies
the transmitter. This information should be sent to the
manufacturer in an eventual request for technical assistance.
2. Sensor: Select the type of sensor to be used. See Table 1.
3. Unit: Select the temperature unit to °C (Celsius) or °F
(Fahrenheit).
4. Range: Sets de measurement range of the transmitter.
Lowest Limit: Equivalent temperature for a current of 4 mA.
Highest Limit: Equivalent temperature for a current of 20 mA.
Sensor Range
The values chosen cannot exceed the Range of Sensor shown
in this field. See Table 1 of this manual.
Minimum Range
Do not set a lower band (span) that the Minimum Range
indicated below in this same field. See Table 1 of this manual.
5. HART Information:
Tag: Field with a brief identification of the equipment (up to 8
characters);
Descriptor: Descriptor used by the master to register the data
(up to 16 characters);
Message: Message used by the master for registering (up to 32
characters);
6. Sensor Failure: It establishes the output behavior, when the
transmitter indicates a failure:
Minimum: Output current goes to < 3.6 mA (down-scale),
typically used for refrigeration.
Maximum: Output current goes to > 21.5 mA (up-scale), typically
used for heating.
7. Zero Offset: It corrects small deviations presented in the
transmitter output, for example, when the sensor is replaced.
8. Filter: Damping filter.
The damping filter changes the response time of the transmitter in
order to smooth the variations in the output. The value set in the
filter indicates the time interval at which the PV will reach 63 % of
its final value.
The factory setting is 1.0 s, and can be changed from 0 s to 32 s.
For example, in the case where the temperature should range
from 0 ° C to 100 ° C, if you considering the factory settings, after
1.0 s the temperature value shall be equal to 63 °C. A zero value
disables this function.
9. Enable Write protection: When activated, configuration is not
allowed.
10. Send Configuration: It applies the new setup. Once sent, the
setup will be immediately applied on the transmitter.
11. Read Configuration: Reads the current configuration in the
transmitter connected. The screen now presents the current setup
that may be changed by the user.
FACTORY SETTINGS:
•Sensor: Pt100 3-wire, range 0 to 100 °C;
•Sensor failure: Upscale (maximum);
•0 °C zero correction;
•Unit: °C;
•Filter: 1.0 s.
It is possible to configure the device through a third party
software and with the help of an FSK modem to perform
HART® communication.
An EDD (Electronic Device Descriptor) file is available,
which can be used with compatible systems and allows
access to the settings and supervise the transmitter.
Fig. 3– Handheld terminal connection

TxIsoRail-HRT
NOVUS AUTOMATION 3/4
MECHANICAL INSTALLATION
The TxIsoRail-HRT transmitter is suitable to be installed in 35 mm
DIN rail. Vibrations, moisture and extreme temperatures, electro-
magnetic interference, high voltage and other interferences can
permanently damage the unit, and could cause error in the measured
value.
DIMENSIONS:
Fig. 4– Transmitter dimensions
ELECTRICAL INSTALLATION
The Fig. 5shows the electrical connections required. The
TxIsoRail-HRT wiring for thermocouple, RTD, resistance and
voltage are done according to the Fig. 4.
Fig. 5 – TxIsoRail-HRT transmitter electrical connections
LOAD represents the 4-20 mA current measuring device (indicator,
controller, register, etc.).
•Polyamide enclosure.
•Section of the cable used: 0.14 to 1.5 mm ².
•Recommended torque in the terminal: 0.8 Nm.
RECOMMENDATIONS FOR INSTALLATION
•Conductors of small electrical signals must be distant from
activation or high-tension/current conductors, preferably passing
through grounded conduits.
•A specific electrical power supply network should be provided for
instruments use only.
•In controlling and monitoring applications, possible consequences
of any system failure must be considered in advance.
•RC filters (47 Ωand 100 nF) in inductor charges (contactors,
solenoids, etc.) are recommended.
ELECTRICAL CONNECTIONS
The figures below show the electrical connections required. The
terminals 1, 2, 3 and 4 are dedicated to the sensor connection.
LOAD represents the 4-20 mA current measuring device (indicator,
controller, recorder, etc.).
PT100 2-WIRE
Note: When the Pt100 2-wire the terminals 1 and 3 must be
interconnected, according to the figure below.
To use the Pt100 2-wire, you must configure the Pt100 3-wire option
in TxConfig II.
The Pt100 wire length should be less than 30 cm to maintain the
measurement error within specifications (electrical resistance).
Fig. 6– Transmitter electrical connections (Pt100 2-wire)
PT100 3-WIRE
Fig. 7– Transmitter electrical connections (Pt100 3-wire)
PT100 4-WIRE
Fig. 8– Transmitter electrical connections (Pt100 4-wire)
Pt100 3 and 4-wire / Pt1000 3 and 4-wire: The use of wires with same
length and gauge is recommended for a better resistance
compensation. The transmitter compensates up to 25 ohm per wire.
THERMOCOUPLES
Fig. 9– Transmitter electrical connections (Thermocouple)

TxIsoRail-HRT
NOVUS AUTOMATION 4/4
VOLTAGE (0-50 mV)
Fig. 10 – Transmitter electrical connections (0-50 mV)
NTC
Fig. 11 – Transmitter electrical connections (NTC)
OUTPUT (4-20 mA)
Fig. 12 – Transmitter electrical connections (4-20 mA)
OPERATION
The transmitter is factory calibrated with standardized sensors, not
requiring any adjustment by the user.
Fine corrections can be accomplished through the TxConfig II
software (in units of temperature).
The user may choose the sensor and the span that best fits its
application. The sensor span must lie within the range specified for
the selected sensor.
It is important to note that the accuracy of the transmitter refers to the
maximum range of the sensor used, regardless of the actual span.
Example:
•The sensor Pt100 has a maximum range of -200 to 650 °C and
typical accuracy 0.08 %.
•Thus, we can have a typical error up to 0.68 °C (0.08 % of 850 °C).
•This error is the same, no matter if total span is used (-200 to 650
°C) or a narrower user-defined span is used, like 0 to 100 °C.
SAFETY INFORMATION
Any control system design should take into account that any part of
the system has the potential to fail. This product is not a protection or
safety device and its alarms are not intended to protect against
product failures. Independent safety devices should be always
provided if personnel or property are at risk.
Product performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure
proper grounding, shielding, cable routing and electrical noise
filtering, in accordance with local regulations, EMC standards and
good installation practices.
SUPPORT AND MAINTENANCE
This product contains no serviceable parts inside. Contact our local
distributor in case you need authorized service.
LIMITED WARRANTY AND LIMITATION OF LIABILITY
NOVUS warrants to the original purchaser that this product is free
from defects in material and workmanship under normal use and
service within one (1) year from the date of shipment from factory or
from its official sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the
cost of correcting defects in the product or of supplying replacement
product as herein provided and upon the expiration of the warranty
period all such liability shall terminate.
For complete information on warranty and liability limitations, check
appropriate section in our website:
www.novusautomation.com/warranty.
Table of contents
Other Novus Transmitter manuals

Novus
Novus TxIsoRail 0-10 Vdc User manual

Novus
Novus TxRail User manual

Novus
Novus TXMINI-DIN43650 User manual

Novus
Novus TxIsoRail-HRT User manual

Novus
Novus RHT-WM User manual

Novus
Novus TXRAIL Series User manual

Novus
Novus TxIsoBlock-HRT User manual

Novus
Novus RHT-WM User manual

Novus
Novus TxIsoRail User manual

Novus
Novus TXMINI-M12-485 User manual

Novus
Novus TXMINI-M12 User manual

Novus
Novus NP785 User manual

Novus
Novus NP785-50 User manual

Novus
Novus TxRail-USB User manual

Novus
Novus TL400-V User manual

Novus
Novus RHT-WM-485-LCD User manual

Novus
Novus TxIsoPack User manual

Novus
Novus RHT Climate-WM Series User manual

Novus
Novus TxIsoBlock-HRT User manual

Novus
Novus NP785 User manual