manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. HK Instruments
  6. •
  7. Transmitter
  8. •
  9. HK Instruments DPT-Ctrl-MOD Series User manual

HK Instruments DPT-Ctrl-MOD Series User manual

Copyright HK Instruments 2018 www.hkinstruments. Installaon version 5.0 2018
INSTALLATION
INSTRUCTIONS
Pressure and flow controllers
DPT-Ctrl-MOD Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failuretoobservesafetyinformaonandcomplywithinstruconscan
result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnectpower
beforeinstallingorservicinganduseonlywiringwithinsulaonratedfor
fulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineeredsystemwhose
specicaonsandperformancecharacteriscsarenotdesignedor
controlledbyHKInstruments.Reviewapplicaonsandnaonalandlocal
codestoassurethattheinstallaonwillbefunconalandsafe.Useonly
experiencedandknowledgeabletechnicianstoinstallthisdevice.
Thankyoufor choosing an HK InstrumentsDPT-Ctrl-MOD series air han-
dling controller with dierenal pressure or airow transmier. The DPT-
Ctrl-MODseriesPIDcontrollersareengineeredforbuildingautomaonin
theHVAC/Rindustry.Withthe built-incontroller oftheDPT-Ctrl-MOD it
ispossibletocontroltheconstantpressureorowoffans,VAVsystemsor
dampers.Whencontrollingairow,itispossibletoselectafanmanufacturer
oracommonmeasuringprobethathasaK-value.
TheDPT-Ctrl-MODincludes anInputterminalthat enables the reading of
mulple signals such as temperature or control relays over Modbus. The
Input terminal has one input channel designed to accept 0−10 V, ntc10k,
Pt1000,Ni1000/(-LG),andBININ(potenalfreecontact)signals.
DPT-Ctrl-MODseriesdevicesarecommonlyusedinHVAC/R
systems for:
•Controllingdierenalpressureorairowinairhandlingsystems
•VAVapplicaons
•Controllingparkinggarageexhaustfans
SPECIFICATIONS
Performance
Accuracy (from applied pressure):
Pressure<125Pa=1%+±2Pa
Pressure>125Pa=1%+±1Pa
(Accuracyspecicaonsinclude:generalaccuracy,
linearity,hysteresis,longterm
stability,andrepeonerror)
Thermal eects:
Temperaturecompensated0...50°C
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zero point calibraon:
ManualpushbuonorModbus
Response me:
1.0−20s,selectableviamenuorModbus
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat(11bits)inRTUmode:
 Codingsystem:8-bitbinary
 Bitsperbyte:
  1startbit
  8databits,leastsignicantbitsent
  rst
  1bitforparity
  1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1–247addressesselectablein
conguraonmenu
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Controller parameter (selectable via menu and
Modbus):
Setpoint0...2500
P-band0...10000
I-me0...1000
D-factor0...1000
Pressure units (selectable via menu):
Pa,kPa,mbar,inWC,mmWC,psi
Flow units (selectable via menu):
Volume: m3/s, m3/hr,cfm,l/s
Velocity:m/s,/min
Measuring element:
MEMS,noow-through
Environment:
Operangtemperature:-20...50°C
Storagetemperature:-40...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:102.0x71.5x36.0mm
Weight:
150g,withaccessories290g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case: ABS
Lid:PC
Pressure inlets: Brass
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Display
2-linedisplay(12characters/line)
 Line1:Direconofcontroloutput
 Line2:Pressureorairowmeasurement, 
 selectableviamenu
  Ifinputisselected,line2showsalso
  inputinformaon(forexample 
 temperature)
Size:46.0x14.5mm
Electrical connecons:
4+4posionspring-loadedterminals
Wire:0.2–1.5mm2(12–24AWG)
Cable entry:
Strainrelief:M16
Knockout:16mm
Pressure ngs
5.2mmbarbedbrass
+Highpressure
−Lowpressure
Electrical
Voltage:
Circuit:3-wire(VOut,24V,GND)
Input:24VACorVDC,±10%
Output:0–10V
Powerconsumpon:<1.0W
Resistanceminimum:1kΩ
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU
INTRODUCTION WARNING
APPLICATIONS
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU
Copyright HK Instruments 2018 www.hkinstruments. Installaon version 5.0 2018
SCHEMATICS
INSTALLATION
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecablethroughthestrainreliefandconnectthe
wirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Display connecon
A
B
24 V
GND
LEDs
Joysck 1
Joysck 2
Joysck 3
Select
Up
Down
Menu buons
Terminal
blocks
Pressure
sensor
Input terminal
configuraon
jumpers
Control out
Input
GND
GND
Figure 1a - Mounng orientaon
YES NO NO
STEP 3: CONFIGURATION
1)Zeropointadjustment.Formoreinformaon,seeStep4.
PRESS. UNIT
Pa
SELECT
UP
DOWN
When control unit FLOW is selected.
2.2.0)Selectthefunconingmodeofthecontroller
-SelectManufacturerwhenconnecngDPT-Ctrl-MODtoafanwithpressure
measurementtaps
-SelectCommon probewhenusingDPT-Ctrl-MODwithacommon
measurementprobethatfollowstheformula:
 q=k∙√∆P(i.e.FloXact)
SELECT
ZERO SENSOR
SELECT
UP
DOWN
2)Selectthefunconingmodeofthecontroller:PRESSUREorFLOW.
-SelectPRESSUREwhencontrollingdierenalpressure.
Gotopoint2.1.
-SelectFLOWwhencontrollingairow.
Gotopoint2.2.0.
CONTROL UNIT
PRESSURE
SELECT
UP
DOWN
When control unit PRESSURE is selected.
2.1)Selectpressureunitfordisplayandoutput:Pa,kPa,mbar,inWCor
mmWC.Thengotopoint3.
MANUFACTURER
Common probe
SELECT
UP
DOWN
Common probe Flakt Woods
SELECT
UP
DOWN
STEP 2: WIRING DIAGRAMS
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable(s).
2)Connectthewiresasshowningure2aand2b.
3)Tightenthestrainrelief.
Figure 2a - Wiring diagram
A
B
24 V
GND
+Power Supply
24VDC / 24VAC
Control out
Input
GND
GND
Modbus
Figure 2b - Wiring diagram example for input signals
Input
GND
ntc10k J1
J2
J3
IN
Input ntc10k temperature:
Funcon 04 - Read input register 3x0007
2.2.1)If
Commonprobe
selected:selectmeasurementunitsusedinthe
formula(akaFormulaunit)(i.e.l/s)
b. If
Commonprobe
selectedinstep1:
Each common probe hasa specicK-value. Selectthe K-valuefromcommon
probemanufacturer’sspecicaons.
AvailableK-valuerange:0.001...9999.000
FORMULA UNIT
l/s
SELECT
UP
DOWN
2.2.2)SelectK-value
a.Ifmanufacturerselectedinstep1:
Each fan has aspecic K-value.Select the K-value from fanmanufacturer’s
specicaons.
K-VALUE
9000.000
SELECT
UP
DOWN
2.2.3)Selectowunitfordisplayandoutput:
Flowvolume:m3/s, m3/h,cfm,l/s
Velocity:m/s,f/min
FLOW UNIT
m3/s
SELECT
UP
DOWN
Copyright HK Instruments 2018 www.hkinstruments. Installaon version 5.0 2018
6)Selecttheresponseme:1...20s.
RESPONSETIME
20 s
SELECT
UP
DOWN
3)SelecttheaddressforModbus:1...247
BAUD RATE
9600
SELECT
UP
DOWN
ADDRESS
99
SELECT
UP
DOWN
PARITY BIT
NONE
SELECT
UP
DOWN
4)Selectthebaudrate:9600/19200/38400.
5)Selecttheparitybit:None/Even/Odd
7)Selecttheinputtype.
Passivetemperaturesensors:PT1000,NTC10k,Ni1000LG,Ni1000
Voltageinput0–10V:Vinput
Noinput:None
INPUT
PT1000
SELECT
UP
DOWN
8)Selectthesetpointofthecontroller.
REF FLOW
0.025 m3/s
SELECT
UP
DOWN
REF PRESSURE
100 Pa
CONFIGURATION CONTINUED
NOTE! Always zero the device before use.
Supplyvoltagemustbeconnectedonehourbeforethezeropointadjust-
mentiscarriedout.AccessviaModbusorbypushbuon.
1)Loosebothtubesfromthepressureinlets+and-.
2)Acvatethedevicemenubypushingthetheselectbuonfor2
seconds.
3)SelectZero sensorbypressingtheselectbuon.
4)WaitunltheLEDturnsoandtheninstalltubesagainforthe
pressureinlets.
STEP 4: ZERO POINT ADJUSTMENT
SELECT
STEP 5: INPUT SIGNAL CONFIGURATION
InputsignalscanbereadoverModbusviaDPT-MODRS485interface.
Signals Accuracy for measurement Resoluon
0...10V <0,5% 0,1%
NTC10k <0,5% 0,1%
Pt1000 <0,5% 0,1%
Ni1000/(-LG) <0,5% 0,1%
BININ(potenalfreecontact)
Thejumpersshouldbe set accordingtothe instruconsbelowandthe value
shouldbereadfromtherightregister.
Figure 3 - Input signal conguraon
J1
J2
J3
IN
J1
J1
J1
J2
J2
J2
J3
J3
J3
NTC10k / BIN IN
Pt1000 / Ni10007(-LG)
0...10 V
D-VALUE
1.00
SELECT
UP
DOWN
12)Pushtheselectbuontoexitmenu.
SELECT
EXIT MENU SELECT
9)Selectproporonalbandaccordingtoyourapplicaon
specicaons.
P-VALUE
206
SELECT
UP
DOWN
10)Selectintegraonmeaccordingtoyourapplicaon
specicaons.
I-VALUE
4.00
SELECT
UP
DOWN
11)Selectderivaonmeaccordingtoyourapplicaon
specicaons.
STEP 6: TEMPERATURE COMPENSATION
Thedeviceincludesanoutdoortemperaturecompensaonfunconthatcan
beenabledfromthemenu.Whenacvatedandanoutdoortemperaturesensor
isaached,theeecvesetpointofthedevicewillbemodiedtocompensate
forthecoldoutdoorair.Thismayresultinenergysavings.
If temperaturecompensaonis enabled, thedevicewill linearly decrease the
user’s setpoint (REF FLOW/REF PRESSURE) by 0 % to TC DROP % from TC
START TE to TC STOP TE.
Thedeviceenforcesa+5 °Cdierence betweenthe startand stoptempera-
tures.Thestarttemperaturemustbehigherthanthestoptemperature.
1)Connectandcongureanoutdoorairtemperaturesensor.Seestep5.
2)Enabletemperaturecompensaon.
4)Setthestoppingtemperatureforcompensaon.
TC STOP TE
-15 °C
SELECT
UP
DOWN
TEMP COMP
ON
SELECT
UP
DOWN
TC START TE
5 °C
SELECT
UP
DOWN
3)Setthestarngtemperatureforcompensaon.
5)Setthemaximumdroppercentageforcompensaon.
TC DROP %
25.0
SELECT
UP
DOWN
Copyright HK Instruments 2018 www.hkinstruments. Installaon version 5.0 2018
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliveredgoods
regarding material and manufacturing. The warranty period is considered to
startonthedeliverydateoftheproduct.Ifadefectinrawmaterialsorapro-
ducon aw isfound, theseller isobligated,when theproduct issent tothe
sellerwithoutdelayorbeforeexpiraonofthewarranty,toamendthemistake
athis/herdiscreoneitherbyrepairingthedefecveproductorbydelivering
freeofchargetothebuyeranewawlessproductandsendingittothebuyer.
Deliverycostsfortherepairunderwarrantywillbepaidbythebuyerandthe
returncostsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident,lightning,oodorothernaturalphenomenon,normalwearandtear,
improperorcarelesshandling,abnormaluse,overloading,improperstorage,in-
correctcareorreconstrucon,orchangesandinstallaonworknotdonebythe
seller.Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldthemanufacturer
alterthestructureofthedevice,thesellerisnotobligatedtomakecomparable
changestodevicesalreadypurchased.Appealingforwarrantyrequiresthatthe
buyerhascorrectlyfullledhis/herduesarisenfromthedeliveryandstated
inthe contract.Thesellerwillgivea new warranty for goodsthat havebeen
replacedorrepairedwithinthewarranty,howeveronlytotheexpiraonofthe
originalproduct’swarrantyme.Thewarrantyincludestherepairofadefec-
ve partordevice, orifneeded, anew partordevice, but not installaon or
exchangecosts.Undernocircumstanceisthesellerliablefordamagescompen-
saonforindirectdamage.
Register Parameter descripon Data Type Value Range
4x0001 Manufacturer 16bit 0...7 0...7
4x0002 Formulaunit(Manufacturer=7) 16bit 0...5 0=m3/s,1=m3/h,2=cfm,
3=l/s,4=m/s,5=f/min
4x0003 K-factorintegral 16bit 0...9999 0...9999
4x0004 K-factordecimal 16bit 0...999 0...999
4x0005 Responseme 16bit 0...20 0...20s
4x0006 PIDcontrolunit 16bit 0...1 0...1
4x0007 PIDpressureref 16bit 0...2500 0...2500
4x0008 PIDowrefinteger 16bit 0...30000 0...30000
4x0009 PIDowrefdecimal 16bit 0...999 0...999
4x0010 PIDpvalue 16bit 0...10000 0...10000
4x0011 PIDiinteger 16bit 0...1000 0...1000
4x0012 PIDidecimal 16bit 0...99 0...99
4x0013 PIDdinteger 16bit 0...1000 0...1000
4x0014 PIDddecimal 16bit 0...99 0...99
4x0015 Overdrivevalue 16bit 0...100 0...100%
4x0016 Overdriveacve 16bit 0...1 0...1
4x0017 Temperaturecompensaon 16bit 0…1 0=o,1=on
4x0018 Temp.comp.startTE 16bit -45…50 -45…50°C
4x0019 Temp.comp.stopTE 16bit -50…45 -50…45°C
4x0020 Temp.comp.dropintegerpart 16bit 0…99 0…99%
4x0021 Temp.comp.dropdecimalpart 16bit 0…999 0.0…0.999%
Funconcode03-Readinputholdingregister
Funconcode05-Writesinglecoil
Register Parameter descripon Data Type Value Range
0x0001 Zeroingfuncon Bit0 0...1 On-O
Thepartsleoverfrominstallaonshouldberecycled
accordingtoyourlocalinstrucons.Decommissioned
devicesshouldbetakentoarecyclingsitethatspecial-
izesinelectronicwaste.
STEP 8: MODBUS REGISTERS
RECYCLING/DISPOSAL
WARRANTY POLICY
Funconcode02-Readinputstatus
Register Parameter descripon Data Type Value Range
1x0001 Input:BININ Bit0 0...1 On-O
MODBUS REGISTERS CONTINUED
STEP 7: Fixed output
Fixedoutputsengscanbeenabledtosetthecontroloutputtoapresetvalue.
Primarypurposeofthisfunconalityistoenabletheadjustmentofairvalves
andterminalswithouttheDPT-Ctrlaecngtheductpressureorairow.Itcan
alsoaidintroubleshoongtheinstallaon.
1)Toenablethexedoutput,scrolltoitsposioninthemenu.
2)Presstheselectbuonandselectthedesiredxedoutputvalue.The
outputwillnowstayatthisvalueindenitely.Innormaloperaonmode
(shownbelow),theupperrowofthedisplaywillshowFIXEDxx%to
indicatetheoutputisxed.
FIXED OUTPUT
OFF
SELECT
UP
DOWN
FIXED 50 %
184 Pa
3)Toenablethenormalcontroloutputanddisablethexedoutput,scrollto
itsposion,selectitandsetvaluetoOFF.
FixedoutputfunconisalsoavailableviaModbus.(4x0016:Overdriveacve,
4x0015:Overdrivevalue)
Funconcode04-Readinputregister
Register Parameter descripon Data Type Value Range
3x0001 Programversion 16bit 0...1000 100...9900
3x0002 PressurereadingA 16bit -250...2500 -250...2500Pa
3x0003 Input0...10V 16bit 0...100 0...100%
3x0004 InputPT1000 16bit -500...500 -50...+50°C
3x0005 InputNi1000 16bit -500...500 -50...+50°C
3x0006 InputNi1000-LG 16bit -500...500 -50...+50°C
3x0007 InputNTC10k 16bit -500...500 -50...+50°C
3x0008 Flowm3/s 16bit 0...10000 0...100m3/s
3x0009 Flowm3/h 16bit 0...30000 0...30000m3/h
3x0010 Flowcfm 16bit 0...30000 0...30000cfm
3x0011 Flowl/s 16bit 0...3000 0...3000l/s
3x0012 Velocitym/s 16bit 0...1000 0...100m/s
3x0013 Velocityf/min 16bit 0...5000 0...5000f/min

Other HK Instruments Transmitter manuals

HK Instruments RHT-MOD Duct Series User manual

HK Instruments

HK Instruments RHT-MOD Duct Series User manual

HK Instruments DPT-Priima Series User manual

HK Instruments

HK Instruments DPT-Priima Series User manual

HK Instruments DPT-IO-MOD Series User manual

HK Instruments

HK Instruments DPT-IO-MOD Series User manual

HK Instruments DPT-MOD Series User manual

HK Instruments

HK Instruments DPT-MOD Series User manual

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments DPT-Flow-1000 Quick start guide

HK Instruments

HK Instruments DPT-Flow-1000 Quick start guide

HK Instruments RHT-MOD Duct Series User manual

HK Instruments

HK Instruments RHT-MOD Duct Series User manual

HK Instruments CDT-MOD-2000 Duct Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Duct Series User manual

HK Instruments AVT Series User manual

HK Instruments

HK Instruments AVT Series User manual

HK Instruments CDT2000 Series User manual

HK Instruments

HK Instruments CDT2000 Series User manual

HK Instruments DPT-Dual-MOD Series User manual

HK Instruments

HK Instruments DPT-Dual-MOD Series User manual

HK Instruments RHT DUCT Series User manual

HK Instruments

HK Instruments RHT DUCT Series User manual

HK Instruments SIRO Series User manual

HK Instruments

HK Instruments SIRO Series User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments DPT Series User manual

HK Instruments

HK Instruments DPT Series User manual

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments KLU 100 User manual

HK Instruments

HK Instruments KLU 100 User manual

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments DPT-MOD Series User manual

HK Instruments

HK Instruments DPT-MOD Series User manual

HK Instruments CMT Series User manual

HK Instruments

HK Instruments CMT Series User manual

HK Instruments AVT Series User manual

HK Instruments

HK Instruments AVT Series User manual

HK Instruments DPT-Flow Series User manual

HK Instruments

HK Instruments DPT-Flow Series User manual

HK Instruments AVT Series User manual

HK Instruments

HK Instruments AVT Series User manual

Popular Transmitter manuals by other brands

CYP CH-1103TX Operation manual

CYP

CYP CH-1103TX Operation manual

DogWatch IB-200 operating instructions

DogWatch

DogWatch IB-200 operating instructions

ABB 2600T Series operating instructions

ABB

ABB 2600T Series operating instructions

SKF CMSS500 Series user manual

SKF

SKF CMSS500 Series user manual

Endress+Hauser Liquisys M CLM223F operating instructions

Endress+Hauser

Endress+Hauser Liquisys M CLM223F operating instructions

Extron electronics TP T 15HD AV user manual

Extron electronics

Extron electronics TP T 15HD AV user manual

INOR IPAQ-L User instructions

INOR

INOR IPAQ-L User instructions

Dejero LIVE+ EnGo user guide

Dejero

Dejero LIVE+ EnGo user guide

FISCHER DE45 series instruction manual

FISCHER

FISCHER DE45 series instruction manual

Kyosho PERFEX EX-5UR instruction manual

Kyosho

Kyosho PERFEX EX-5UR instruction manual

CYP EL-2600V user guide

CYP

CYP EL-2600V user guide

SABINE SW70-T BELTPACK TRANSMITTER Quick setup guide

SABINE

SABINE SW70-T BELTPACK TRANSMITTER Quick setup guide

Signet 8450-1 manual

Signet

Signet 8450-1 manual

Emerson Rosemount 248 quick start guide

Emerson

Emerson Rosemount 248 quick start guide

Absolute Process Instruments APD 4300 manual

Absolute Process Instruments

Absolute Process Instruments APD 4300 manual

Audiovox Prestige 07S1BP Programming guide

Audiovox

Audiovox Prestige 07S1BP Programming guide

Marmitek MicroModule AWM2 user manual

Marmitek

Marmitek MicroModule AWM2 user manual

Vaisala DRYCAP DMT143 user guide

Vaisala

Vaisala DRYCAP DMT143 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.