HK Instruments CDT2000 Series User manual

Copyright HK Instruments 2017 www.hkinstruments. Installaon version 5.0 2017
INSTALLATION
INSTRUCTIONS
CARBON DIOXIDE TRANSMITTERS
CDT2000 Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsCDT2000seriescarbon
dioxidetransmier.TheCDT2000seriesisintendedforuseincom-
mercialenvironmentsinHVAC/Rapplicaons.
TheCDT2000seriesmeasurescarbondioxide(CO2),ulizingthein-
dustrystandardNDIRmeasurementprinciple,andtemperature(T).
Oponalrelavehumidity(rH)measurementisalsoavailableinthe
samedevice.Eachmeasurementparameter(CO2,rH,T)hasasepa-
rateeldcongurableoutput.
TheCDT2000seriescarbondioxidetransmiersareavailablewith
Modbusconguraon,relayandtouchscreendisplay.
The CDT2000 series transmiers calibrate themselves automa-
callyusingABCTMlogic.TheABCTMlogicrequiresthatthespacein
which the transmier is used needs to to be unoccupied for four
hoursperdaysothattheindoorCO2concentraondropstotheout-
sidelevel.CDT2000-DCisadualchannelmodelwithameasuring
channelandareferencechannelthatmakesaconnuouscompari-
sonandthenecessaryadjustmentaccordingly.CDT2000-DCisalso
suitableforbuildingsthatareconnuouslyoccupied.
•humidityinvariousindustrialapplicaons
•temperaturesinHVAC/Renvironment
•CDT2000-DCseriesdevicescanalsobeusedinapplicaonswhere
thereisaconstantsourceofcarbondioxidepresent(forexample
hospitalsandgreenhouses)
SPECIFICATIONS
Performance
Measurement ranges :
CO :400–2000ppm
Temperature:0...50° °F 32...122 /C
Relavehumidity:0–100%
Accuracy:
CO2:±40ppm+2%ofreading,DCmodel:75ppmor
10%ofreading(whicheverisgreater)
Temperature:<0.5º °F <0.9 /C
Relavehumidity:±2...3%at0...50°Cand10–90%rH
Totalerrorbandincludesaccuracy,hysteresisand
temperatureeectover5...50°Cand10–90%rH.
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
ppm,°Cand%rH
Measuring element:
CO2:Non-dispersiveinfrared(NDIR)
Temperature:Pt1000
Relavehumidity:Thermosetpolymercapacive
sensingelement
Calibraon:
Automacself-calibraonABCLogicTMorconnuous
comparison(DC)
Environment:
Operangtemperature:0...50° °F 32...122 /C
Storagetemperature:-20...70° °F -4...158 /C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:99x90x32m 1.26" x 3.54 x 3.90 /m
Weight:
150 oz 5.30 /g
Mounng:
3screwholessloed,3.8mm
Materials:
Case: ABS
Protecon standard:
IP20
Display (Oponal)
Touchscreen
Size:77.4x52.4mm
Electrical connecons:
Powersupply:
 5-screwterminalblock
 (24V,GND,CO2, rH, T)
 0.2–1.5mm2(12–24AWG)
Relay out:
 3-screwterminalblock
 (NC,COM,NO)
 0.2–1.5mm2(12–24AWG)
Electrical
Input: 24VACorVDC,±10%
 Currentconsumpon:max90mA(at24V)+
 10mAforeachvoltageoutputor20mAfor
 eachcurrentoutput
CO2outputsignal:
 0–10V,R>1kΩ
 2–10V,R>1kΩ
 4–20mA,R<500 Ω
Temperatureoutputsignal:
 0–10V,R>1kΩ
 2–10V,R>1kΩ
 4–20mA,R<500Ω
Relavehumidityoutputsignal:
 0–10V,R>1kΩ
 2–10V,R>1kΩ
 4–20mA,R<500Ω
Relay out:
 SPDTRelay,250VAC/30VDC/6A
 Adjustableswitchingpointandhysteresis
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
LVDDirecve2014/35/EU
WEEEDirecve2012/19/EU
INTRODUCTION
APPLICATIONS
WARNING
CDTseriesdevicesarecommonlyusedtomonitor:
• CO2andhumiditylevelsinoces,publicspaces,meengrooms
andclassrooms
• CO2levelsofreturnairinvenlaonsystems
•incomingairandreturnairhumiditylevelsinvenlaonsystem
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 5.0 2017
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Routethecablesandconnectthewires(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
Figure 1 - Surface mounng
1)Selectamounnglocaononthewallat1.2–1.8m(4–6)
abovetheoorandatleast50cm(20in)fromtheadjacentwall.
Locatetheunitinanareawithgoodvenlaonandanaverage
temperature,whereitwillberesponsivetochangestotheroom
condions.TheCDTmaybemountedonaatsurface.
DonotlocatetheCDTwhereitcanbeaectedby:
•Directsunlight
•Drasordeadareasbehinddoors
•Radiantheatfromappliances
•Concealedpipesorchimneys
•Outsidewallsorunheated/uncooledareas
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountthewallplatewithscrews.
•Incorrectinstallaonmaycauseashiintemperatureoutput
Display locking
jumper
Output mode
selecon
jumpers
Contact pins for
relay terminal
Contact pins for
terminal block
Terminal block
Terminal block for relay
99.0
90.0
83.0
49.5
14.0
45.0
18.0
Ø 4.0
32.0
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 5.0 2017
CAUTION!
•ForCEcompliance,aproperlygroundedshieldingcableis
required.
•Usecopperwireonly.Insulateorwirenutallunusedleads.
•Supplyaseparatecableforrelayandsignaloutwhenusingline
voltagetopowertherelay.
•Anywiringmaycarrythefulloperanglinevoltagecurrentbased
oneldinstallaon.Thecoverlockingscrewmustbeinstalledif
thelinevoltageissuppliedtotherelay.
•Careshouldbeusedtoavoidelectrostacdischargetothedevice.
•Thisunithasconguraonjumpers.Youmayneedtorecongure
thisdeviceforyourapplicaon.
1)Routethecablesthroughthesquareopeninginthebackplateor
forsurfacewiringselectaknockoutonthetoporboomofthe
wallplate,asshowninFigure2a.
2)ConnectthewiresasshowninFigure2band2c.
WIRING DIAGRAMS CONTINUED
Figure 2a - Roung the cables
24 V
GND
CO2
rH
Temp
+
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Output 0/2–10 V / 4–20 mA
Figure 2b - Wiring diagram: Power input & signal output
Wires can be routed through the square opening in the back plate
Wires can be routed through the top knockouts
Wires can be routed through the boom knockouts
Figure 2d - Wiring diagram: Relay
NC
COM
NO
STEP 2: WIRING DIAGRAMS
NOTE!Whenusinglongconneconwiresitmaybenecessarytousea
separateGNDwireforvoltageoutputcurrenttopreventmeasurement
distoron.TheneedforanextraGNDwiredependsonthecrosssec-
onandlengthoftheusedconneconwires.Iflongand/orsmallcross
seconwiresareused,supplycurrentandwireresistancemaygener-
ate avoltage drop in the common GNDwire resulng in adistorted
outputmeasurement.
CO2
T
24 V
GND
+Power Supply
24VDC / 24VAC
Output 0/2...5/10 V
Output 0/2...5/10 V
V
V
Figure 2c - Wiring diagram: Extra GND wire
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 5.0 2017
1)Conguraonoftheoutputmodesof:
•Carbondioxide(CO2)
•Relavehumidity(rH)
•Temperature(Temp)
Selecttheoutputmode,current(4–20mA)orvoltage(0–10V),
byinstallingjumpersasshowninFigure4.Eachoutput,CO2,
relavehumidity,andtemperatureareconguredseparately.
Toselect2–10Voutputmodeonadisplayversionofthedevice:
First,select0–10Voutputbyjumper(s),thenchangethevoltage(V)
outputfrom0–10Vto2–10Vviatheconguraonmenu.Please
seetheusermanualformoredetails.
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefectin
rawmaterialsoraproduconawisfound,thesellerisobligated,when
theproductissenttothesellerwithoutdelayorbeforeexpiraonof
thewarranty,toamendthemistakeathis/herdiscreoneitherbyre-
pairingthedefecveproductorbydeliveringfreeofchargetothebuy-
eranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, ood or other natural phenomenon, normal wear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warrantyrequiresthatthebuyerhascorrectlyfullledhis/herdues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anewwarrantyforgoodsthathavebeenreplacedorrepairedwithin
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device, orif needed, anew part ordevice,butnotinstallaonorex-
change costs. Under no circumstance is theseller liable for damages
compensaonforindirectdamage.
Jumper installed to the le side pins:
0–10 V output selected
CO2
rH
Temp
0–10 V 4–20 mA
Jumper installed to the right side pins:
4–20 mA output selected
CO2
rH
Temp
0–10 V 4–20 mA
First jumper installed to the right side pins:
4–20 mA output selected for CO2
Second and third jumper installed to the le side pins
0–10 V outputs selected for relave humidity & temperature
CO2
rH
Temp
0–10 V 4–20 mA
Figure 4
STEP 4: SELECTING THE OUTPUT MODE
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
WARRANTY POLICY
SELECTING THE OUTPUT MODE CONTINUED
2)Lockingthedisplay:
Installthejumpertolockthedisplaytopreventaccesstothecongu-
raonmenuaerinstallaoniscompleted(seetheschemacsforthe
locaonofthepins).
STEP 3: CONFIGURATION
ConguraonoftheCDTseriesdeviceconsistsof:
1)Conguringthejumpers(seestep4).
2)Conguraonmenuopons.
(Displayversionsonly.Seetheusermanualforfurtherdetails.)
(Grey colour indicates that a jumper is installed)
No jumper
Circuit open
Jumper installed
Circuit closed
Jumper stored
Figure 3 - Jumper installaon
SELCOUSA.com

Other HK Instruments Transmitter manuals

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments

HK Instruments DPT-2W- 100-R2 User manual

HK Instruments KLU 100 User manual

HK Instruments

HK Instruments KLU 100 User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments DPT-MOD Series User manual

HK Instruments

HK Instruments DPT-MOD Series User manual

HK Instruments DPT-Flow Series User manual

HK Instruments

HK Instruments DPT-Flow Series User manual

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments CDT2000 Series User manual

HK Instruments

HK Instruments CDT2000 Series User manual

HK Instruments DPT-Flow Series User manual

HK Instruments

HK Instruments DPT-Flow Series User manual

HK Instruments DPT-MOD Series User manual

HK Instruments

HK Instruments DPT-MOD Series User manual

HK Instruments DPT-IO-MOD Series User manual

HK Instruments

HK Instruments DPT-IO-MOD Series User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments DPT-Dual-MOD Series User manual

HK Instruments

HK Instruments DPT-Dual-MOD Series User manual

HK Instruments DPT-MOD Series User manual

HK Instruments

HK Instruments DPT-MOD Series User manual

HK Instruments AVT Series User manual

HK Instruments

HK Instruments AVT Series User manual

HK Instruments DPT-CR-MOD Series User manual

HK Instruments

HK Instruments DPT-CR-MOD Series User manual

HK Instruments RHT DUCT Series User manual

HK Instruments

HK Instruments RHT DUCT Series User manual

HK Instruments DPT-Ctrl-MOD Series User manual

HK Instruments

HK Instruments DPT-Ctrl-MOD Series User manual

HK Instruments SIRO Series User manual

HK Instruments

HK Instruments SIRO Series User manual

HK Instruments RHT-MOD Series User manual

HK Instruments

HK Instruments RHT-MOD Series User manual

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments DPT Series User manual

HK Instruments

HK Instruments DPT Series User manual

HK Instruments CDT Series User manual

HK Instruments

HK Instruments CDT Series User manual

HK Instruments RHT-MOD Duct Series User manual

HK Instruments

HK Instruments RHT-MOD Duct Series User manual

Popular Transmitter manuals by other brands

Beyerdynamic S 900 operating instructions

Beyerdynamic

Beyerdynamic S 900 operating instructions

Onix AT-03FM instruction manual

Onix

Onix AT-03FM instruction manual

Erone SATL2641E15 Use manual

Erone

Erone SATL2641E15 Use manual

Regin HTRT10A-420 instructions

Regin

Regin HTRT10A-420 instructions

LITEWAY VT-4005 operating instructions

LITEWAY

LITEWAY VT-4005 operating instructions

Genie Intellicode instructions

Genie

Genie Intellicode instructions

Siro SI1605 manual

Siro

Siro SI1605 manual

Rotronic HygroFlex TF5 user guide

Rotronic

Rotronic HygroFlex TF5 user guide

Emerson Rosemount 3408 quick start guide

Emerson

Emerson Rosemount 3408 quick start guide

Akai FMT-26BT user manual

Akai

Akai FMT-26BT user manual

Rice Lake SCT-4X-AN quick start guide

Rice Lake

Rice Lake SCT-4X-AN quick start guide

Godox WH-M1 instruction manual

Godox

Godox WH-M1 instruction manual

Baxall ZTX3 Installation and operating instructions

Baxall

Baxall ZTX3 Installation and operating instructions

RIB NOVA Wi-Fi manual

RIB

RIB NOVA Wi-Fi manual

Nice SELD instruction manual

Nice

Nice SELD instruction manual

MSA Ultima OPIR-5 quick start guide

MSA

MSA Ultima OPIR-5 quick start guide

FMUser FU-300W user manual

FMUser

FMUser FU-300W user manual

Jonsa DF/TXDG12 instruction manual

Jonsa

Jonsa DF/TXDG12 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.