Honeywell Home DB7110U User manual

INSTALLATION INSTRUCTIONS
34-00032EF-01
DB7110U Universal Heat Pump
Defrost Controller
APPLICATION
The DB7110U Universal Heat Pump Defrost
Controller is a heat pump defrost control used in
single stage heat pump appliances. This product
replaces over 260 OEM and competitive controls and
can be easily programmed to meet the requirements
of virtually any single stage heat pump. See Table 2,
“Compatibility Chart.,” on page 5.
FEATURES
The DB7110U provides:
• Universal defrost control for single stage heat
pumps
• LED display for easy setup and configuration
• Small, square footprint for easier installation
• Demand and timed defrost modes
• System status and fault indication
• Selectable reversing delay to limit noise when
going in and out of a defrost cycle
• Fault history for easy troubleshooting
Fig. 1. DB7110U1000.
SPECIFICATIONS
Electrical Ratings
Input Voltage: 24VAC, 60Hz
Max. Input Current: 200mA
Compressor Contactor: 1A @ 24VAC
Outdoor Fan:
1/2HP motor
5A full load, 30A locked rotor, 240VAC.
Aux Heat: 1A @ 24VAC
Reversing Valve: 1A @ 24VAC
All outputs rated for 100,000 operations.
All terminals except FAN-IN and FAN-OUT are NEC
Class 2 low voltage.
Environmental Ratings
Operating Temperature Range: -40F to 150F
Humidity Limits: less than 95% (non-condensing)
INSTALLATION AND
CONFIGURATION
Overview
When Installing This Product…
1. Read these instructions carefully. Failure to fol-
low instructions can damage the product or
cause a hazardous condition.
2. Check ratings given in these instructions and
on the product to make sure the product is suit-
able for your application.
3. Installer must be a trained, experienced service
technician.
4. Use these instructions to check out the product
operation after installation.
MENU SETTING
SYSTEM FAULT
M37637
DB7110U-DEFROST CONTROL

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
34-00032EF—01 2
WARNING
Electrical Shock Hazard. Can cause severe
injury, death or property damage.
Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage. More than one disconnect
may be involved.
Control Location
1. Before removing the old control, make note of
the wire connections to ensure the wires will be
connected to the correct terminals of the
DB7110U.
2. Mount DB7110U inside the junction box on the
outdoor unit using the two included self-drilling
sheet metal screws.
3. Use the control as a template to drill new mount-
ing holes if necessary.
4. If the mounting tabs interfere with other compo-
nents in the junction box, break/cut off the
unused mounting tabs prior to tightening the
mounting screws.
Coil Sensor Location
Fig. 2. Coil Sensor.
1. The outdoor coil sensor must be used. Without
the coil sensor, the DB7110U cannot determine
when to defrost. The coil sensor included with
the DB7110U replaces the existing defrost ther-
mostat or coil sensor installed on the unit.
2. Place the sensor on the coil where the OEM sen-
sor/thermostat was located. If replacing a
defrost thermostat, note the original settings for
proper adjustment of the termination and
enable temperatures on the DB7110U. They are
often marked with their open and close points. A
thermostat marked L60-25F for example would
correspond to a Termination Temperature of
60degF and an Enable Temperature of 35degF
(60deg-25deg).
3. If the location of the OEM sensor/thermostat is
inaccessible or difficult to access, place the new
coil sensor on the coil loop nearest the expan-
sion valve where refrigerant is entering the coil
during the heating mode. This location gives the
largest temperature difference between the air.
4. Ensure the coil sensor is clamped tightly to the
coil. It may be desirable to add insulation to the
sensor to yield more accurate readings,
although this is generally not needed.
Fig. 3. Coil Sensor Mounting.
OUTDOOR AIR SENSOR
LOCATION (DEMAND
DEFROST ONLY)
Fig. 4. Air Sensor.
1. The outdoor air sensor is for demand defrost
systems only. Using the outdoor air sensor will
enable the DB7110U to implement a more
advanced defrost algorithm that determines to
defrost based on the relationship between coil
and air temperatures. Without the air sensor, the
DB7110U defrosts when the coil temperature is
below the Enable Temperature for the Defrost
Cycle Time. It is advisable to use the air sensor if
possible as it may reduce the number of unnec-
essary defrosts that are common among defrost
timers.
2. Mount the air sensor such that the capsule is
hanging in air near the outdoor coil.
3. Do not locate the air sensor too close to the coil
that sensor readings are influenced by it.
4. Do not mount the air sensor in direct sunlight.
5. The air sensor capsule should not be in contact
with metal or some other material that may
change its readings.
M37663
M37638
SENSOR
M37664

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
3 34-00032EF—01
Wiring
WARNING
Electrical Shock Hazard. Can cause severe
injury, death, or property damage.
Disconnect power supply before beginning
wiring to prevent electrical shock or equipment
damage. More than one disconnect may be
involved.
1. Make sure the wiring complies with all local
codes and ordinances.
2. If the low voltage wiring is bare wire with no ter-
minals, wire nut them to the included wiring pig-
tails. Do not crimp terminals to solid wire.
3. Check the line voltage connections on the fan
relay to ensure they are tight, in good connec-
tion, and more than 1/4" away from any part of
the appliance enclosure.
4. Plug in the outdoor sensor (if used) and the coil
sensor.
5. Reference the wiring diagrams in Figs. 5 to 8 to
aide in proper appliance wiring.
Table 1. Class 2 Low Voltage Terminations,
24V 60Hz.
Fig. 5. Wiring diagram with pressure switches
connected to defrost control.
Fig. 6. Wiring diagram for systems with no low
pressure switch.
Name Function
R (24V) 24V Hot
C (COM) 24V Common
W Aux/emergency heat request from
thermostat – W requests will cause
the AUX output to be energized.
Y Compressor request from
thermostat – Y requests will cause
the COMPR and FAN terminals to be
energized.
O Reversing valve request from
thermostat – controls the status of
the RV output.
HPC
(2 Terminals)
High pressure cutout/switch – these
terminals must be shorted for
compressor operation. Never
bypass protective pressure
switches.
LPC
(2 Terminals)
Low pressure cutout/switch – these
terminals must be shorted for
compressor operation. Never
bypass protective pressure
switches.
AUX Output to auxiliary/emergency heat
– energized during a defrost cycle or
when requested by W input.
COMPR
(2 Terminals)
Output to compressor contactor –
energized by Y request.
RV
(2 Terminals)
Output to reversing valve –
energized by O input and as
required by a defrost cycle.
LPC
HPC
CONTACTOR
AUX
REVERSING
VALVE
FAN-IN
FAN-OUT
R
C
O/B
W
Y
AIR
SENSOR
(OPTIONAL)
COIL
SENSOR
INDOOR
EQUIPMENT
OUTDOOR
EQUIPMENT
FAN
DB7110U
L1
L2
COMPR
RV
HIGH
PRESSURE
SWITCH
LOW
PRESSURE
SWITCH
AIR
COIL
M37756
LPC
HPC
CONTACTOR
A
UX
REVERSING
VALVE
FAN-IN
FAN-OUT
R
C
O/B
W
Y
AIR
SENSOR
(OPTIONAL)
COIL
SENSOR
INDOOR
EQUIPMENT
OUTDOOR
EQUIPMENT
FAN
DB7110U
L1
L2
COMPR
RV
HIGH
PRESSURE
SWITCH
AIRCOIL
M37757

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
34-00032EF—01 4
Fig. 7. Wiring diagram for systems with pressure
switches in series with the contactor and no
connection to the defrost control.
Fig. 8. Wiring diagram for simple timer applications.
CONFIGURATION
1. Connect power.
2. On power up the display will briefly flash the
software version of the DB7110U and then begin
cycling between the normal operating screens
showing the current mode and the values of the
two temperature sensors. Note that there is brief
startup delay following power up where com-
pressor operation is prohibited.
Fig. 9.
The displayed coil and air temperature readings
can be very useful for optimizing and trouble-
shooting defrost performance.
3. There are several configurable options to opti-
mize defrost performance. See “User Interface”
on page 7 for a detailed description of each
parameter/screen. Press the select (o) button
advance through the various screens and and
buttons to adjust the various parameters.
Table 4 below describes each parameter.
CHECKOUT
1. After the startup delay has expired, generate a
request for heat by shorting R to Y (and R to O if
configured as a “B” system, reversing valve ener-
gized in heating mode).
2. Verify the compressor, fan, and reversing valve (if
applicable) are energized.
3. Press and hold the button until “tESt” appears
on the display as shown below.
Fig. 10.
4. Verify the unit enters defrost mode
Fig. 11.
The reversing valve will change states and the
aux heat will be energized. A few moments later
the fan will be turned off. If Reversing Delay is
enabled, the compressor will be turned off for
the selected time, and then turn back on to
reduce noise.
The DB7110U will remain in defrost for at least
one minute. After one minute has elapsed, the
DB7110U will exit defrost after the coil tempera-
ture has risen above the termination
temperature or after the selected defrost time,
whichever comes first.
Test mode can be terminated at any time by
pressing and holding the button again.
LPC
HPC
CONTACTOR
AUX
REVERSING
VALVE
FAN-IN
FAN-OUT
R
C
O/B
W
Y
AIR
SENSOR
(OPTIONAL)
COIL
SENSOR
INDOOR
EQUIPMENT
OUTDOOR
EQUIPMENT
FAN
DB7110U
L1
L2
COMPR
RV
HIGH
PRESSURE
SWITCH
LOW
PRESSURE
SWITCH
AIRCOIL
IF THE PRESSURE SWITCH(ES) ARE IN SERIES
WITH THE CONTACTOR, JUMPER THE
ONBOARD CONNECTIONS. DO NOT BYPASS
ANY PROTECTIVE PRESSURE SWITCHES.
M37758
LPC
HPC
CONTACTOR
AUX
REVERSING
VALVE
FAN-IN
FAN-OUT
R
C
O/B
W
Y
COIL
SENSOR
INDOOR
EQUIPMENT
OUTDOOR
EQUIPMENT
DB7110U
L1
L2
COMPR
RV
FAN
IF THE PRESSURE
SWITCH(ES) ARE IN SERIES
WITH THE CONTACTOR,
JUMPER THE ONBOARD
CONNECTIONS.
DO NOT BYPASS ANY
PROTECTIVE PRESSURE
SWITCHES.
AIRCOIL
HIGH
PRESSURE
SWITCH
LOW
PRESSURE
SWITCH
WHEN THE COMPRESSOR CONTACTOR IS POWERED DIRECTLY
FROM THE Y TERMINAL, SET THE REVERSING DELAY AND SHORT
CYCLE DELAY TO 0.
M37759
M37640
CURRENT MODE OF OPERATION
OFF, HEAT, COOL, DELAY, ETC.
OUTDOOR COIL TEMPERATURE
DEGREES FAHRENHEIT
OUTDOOR AIR TEMPERATURE
DEGREES FAHRENHEIT
M37641
M37642
de Fr

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
5 34-00032EF—01
COMPATIBILITY CHART
Table 2. Compatibility Chart.
Amana C64301-1 C6431001
Arcoaire 32312-00 3232140
Armstrong 39840B001 44614-0001
44614-002 46257-001
47181-001 R46257-001
R46614-002 R47181-001
39840B002 37967B001
37967B002 R46K6701
R44614-001 R44614-002
Artesian 10321-00
Carrier 150-83-6A 621-xxxx
CES0110063-00 CES0110063-01
CES0110063-02A CES0130024-00
CES0130024-01 CES0130076
HK25SZ359A HK32EA001
HK32EA003 HK32EA007
HK32EA008 HK32FA003
HK32FA006
Coleman 3030A374 3030A364
3C30A374
Comfortmaker 1029-2 34332100
34332101
Evcon 9218-374
Fast 1093410
Goettl 305007
Goodman 1084-03-2022 1084-200D
20293901 B1226006
B1226008 LR40061
PCBDM101 PCBDM130
PCBDM133 PCBDM160
PCBDM101S PCBDM130S
Heil Quaker HQ1052727
Heil/Tempstar 1087952 1087953
1173636 CEPL130524-01
Honeywell ST74A1004 ST74A1020
ST74A1038 ST74A1053
ST74C1002
ICM DFORB24A21300 ICM300C
DFORB-AB1004 DFORF
DFOSP24A2 ICM301C
ICM302C ICM303C
ICM304 ICM307
ICM316 ICM317
ICM318 ICM319
ICM320 ICM321
ICM322 ICM323
W1001-4
ICP 1052757 1069364
Interthem 6208800
Lennox 100269-01 100269-02
100269-04 100269-05
11K7101 1507N170027
29M0101 29M0201
30W87 33G9501
34M6301 46K67
56M3701 68I2901
68J8401 78H6801
84W8801 86G1601
97M81 LB-101263A
LB-101263B 11K71
97M8101 30W8701
34M63 29M01
56M37 HPXB15
68I84 68I29
78H68
Nordyne 620880 621301A
621579B 621579C
624519A 624608
624626 624633
624644 624656
624700 917012
917178 917178A
920338 624644R
6246440 624633R
6246330
Ranco DT2
Rheem 47-102684-01 47-102684-02
47-102684-03 47-102684-04
47-102684-07 47-102684-08
47-102684-83 47-102685-01
47-102685-02 47-102685-03
47-102685-04 47-102685-05
47-102685-06 47-102685-84
47-21517-11 47-21517-13
47-21517-14 47-21517-16
47-21517-17 47-21517-18
47-21517-22 47-21517-23
47-21517-24 47-21517-82
47-21517-88 47-21517-92
47-21776-01 47-21776-06
47-21776-86 DDL-013002-0RH
DLL-013002-1RH DDL-0131020-1RH
DDL-017002-2RH DDL-017102-1RH
DDL-017702-1RH DDL-117702-3RH
DDL-122131-2RH 47-21517-12
47-21517-85 47-102685-87
47-102684-09 47-102685-07
47-21517-20
Robertshaw DT2-1000 TD-10
SnyderGeneral 1395-329 CEBD430524-04B
Table 2. Compatibility Chart. (Continued)

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
34-00032EF—01 6
Tempstar/ICP 1084-100 1084-83-1008
1087562
Therm-O Disc 26E-10
Trane 21C14501G18 21C1450127
21C1450136 21C1450137
21C1450138 21C1450142
21C1450144 21C1450145
21C1450153 21C1450154
21C1450155 21C1450160
21C14282G01 CNT01106
CNT01108 CNT01129
CNT01152 CNT01431
CNT01510 CNT01642
CNT01923 CNT01924
CNT01926 CNT02514
CNT02515 CNT02516
CNT02920 CNT02935
CNT03715 CNT03716
CNT04362 CNT04363
CNT04364 CNT04366
CNT04368 CNT04695
CNT05001 CNT05008
CNT05009 CNT05010
CNT05482 CNT05875
CNT1108 CNT01693
Weatherking 840-4-5548
White-Rodgers 840-4-5548 47D40-801
47D43-101 47D43-111
47D43-11102 47D43-811
90-621 47D01U-843
York 031-00872-001 031-00872-002
031-00872-002 031-00872-701
031-00872-702 031-00872-703
031-01222-000 031-01251-000
031-01268-000 031-01954-000
031-01975-000 031-09104-000
031-09170-000 331-01975-001
331-01975-102 331-09139-000
9218-3741 S1-03100872701
S1-03109170000 S1-33101954000
S1-33101975102
Table 2. Compatibility Chart. (Continued)

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
7 34-00032EF—01
USER INTERFACE
The user interface consists of three buttons, two LED’s, and 4 7-segment digits. The two left digits generally
represent the category of what is being displayed while the two right digits represent the value or setting of the
category. The exception is in the event a value requires 3 digits such as a temperature higher than 99F as shown
below with two “termination temperature” values of 90F and 100F.
Fig. 12. Two example values of configuration option 2 (Termination Temperature).
The “o” button advances to the next screen while the and buttons are used to adjust the value of each
parameter.
Note that after one hour without a button press, the 7-segment display will turn off to save power. A button must
be pressed to turn the display on again.
Table 3. Status Screens.
The configuration screens are numbered parameters where numbered parameter has a selectable value
according to the table below.
For example, would represent Parameter 1 (Defrost Enable Temperature) set to 35 (degF).
Display Description
Current Fault(s) Present.
Right digits blank if there is no fault.
and to scroll through active faults.
Fault History
and to scroll through history.
Press and hold for more than two seconds to clear all inactive faults.
Table 4. Configuration Screens.
Display Description Range Default
1 Defrost Enable Temperature
Coil temperature where defrost functionality is active.
30degF-36degF 35degF
2 Termination Temperature.
Coil temperature where defrost is terminated.
50degF-100degF 70degF
3 Defrost Cycle Time
Time the coil temperature is below the Defrost Enable
Temperature before a defrost is triggered if in timed mode
(no outdoor air sensor present).
30-120 minutes 30 minutes
4ShortCycleDelayTime
Minimum off time between compressor cycles.
0-5 minutes 3 minutes
5 Reversing Valve System Type
O = reversing valve energized in cool.
B = reversing valve energized in heat.
O or B O
90 1
00
M37659
22
4
F
M37660
H 11
F
M37661
135
M37662

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
34-00032EF—01 8
Green LED: Indicates system power and operation.
Red LED: Indicates a fault is currently present and the user should inquire with the 7-segment display for more
information.
6 Reverse Delay
Compressor off time when switching between heating and defrost
modes. Setting this to 0 will shorten the overall defrost time, but
may result in objectionably loud noises when entering/exiting
defrost (depending on compressor type).
0-30 seconds 30 seconds
7 Maximum Defrost Time
The maximum amount of time a defrost cycle can last. A defrost
cycle may be terminated earlier if the coil reaches the Termination
Temperature, but a defrost cycle should never last longer than this
time.
8-14 minutes 14 minutes
8 Aux Heat Lockout Temperature
W requests will be ignored if the outdoor temperature is higher
than this temperature. The Aux heat output will still function
normally during a defrost cycle regardless of this setting.
Do not set this temperature below the Compressor Lockout
Temperature or there will be a range of temperatures with no
heating operation.
0degF-40degF No Lockout
(OF)
9 Compressor Lockout Temperature
Y requests will be ignored if the outdoor temperature is lower than
this temperature.
Do not set this temperature above the Aux Heat Lockout
Temperature or there will be a range of temperatures with no
heating operation.
-10degF-40degF No Lockout
(OF)
Table 4. Configuration Screens. (Continued)
Display Description Range Default

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
9 34-00032EF—01
TROUBLESHOOTING AND MAINTENANCE
IMPORTANT
Due to the potential hazard of line voltage, only a trained experienced service technician should perform
the troubleshooting procedures.
This control contains no field-serviceable parts. Do not attempt to take it apart. Replace the entire control
if operation is not as described.
Table 5. Troubleshooting.
Condition Procedure Control Status Corrective Action
System does not
start with a call
for heat or cool
Observe display for
current operational
mode.
Display shows OFF • Verify call for heat or cool is present.
• Check the wiring from thermostat and
indoor equipment
• Measure input terminals (W, Y, O) for
proper voltage.
• Verify cold weather compressor
lockout isn’t active. Adjust
“Compressor Lockout Temperature” if
necessary.
Control displays HEAT or
COOL but the system is
not operating.
• Check wiring to outdoor equipment.
• Check contactor
• Measure output terminals for proper
voltage. WARNING: fan terminals are
line voltage.
• Verify system pressure switches. The
onboard HPC and LPC terminals
must be shorted to run. Never bypass
protective pressure switches.
• Check coil sensor, the system will not
run without a coil sensor.
Control displays DLY • The system is in a startup delay due
to short cycle protection, powerup, or
low voltage. Wait for the delay to
expire.
Compressor does
not stop when
the call for heat
or cool ends
Observe display for
current operational
mode.
Control displays current
mode; OFF, HEAT, or
COOL.
• If HEAT or COOL is shown after the
call ended, investigate thermostat
wiring.
Unplug Y wire from
control
Display shows OFF,
compressor turns OFF
• Investigate thermostat wiring to
ensure all wires are on the proper
terminals.
Display shows OFF but
compressor remains ON
• Check the wiring between the control
and contactor.
• Check for a failed/stuck contactor.
•UnplugtheCOMPRwiresand
measure voltage across the two
COMPR terminals. If they measure
24V while the display says OFF,
replace control.
Display continues to show
shows HEAT or COOL
• Replace the control.
System operates
in wrong mode,
heating when
cooling is
requested or vice
versa
Check O/B setup Control displays current
configuration:
• O means the control will be in
COOLING mode when there’s 24V on
the O terminal.
• B means the control will be in
HEATING mode when there’s 24V on
the O terminal. In most cases this will
only apply to Rheem units.

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
34-00032EF—01 10
System does not
defrost at all Observe operational
mode while heating.
Display shows COOL • O/b configured incorrectly. Verify
proper setting of O/b input for
reversing valve control. The control
won’t defrost if it “thinks” it’s in
cooling mode.
Display shows HEAT, but
no defrost is triggered.
• Verify sensor placement and readings
are correct.
• Increase the “Enable Temperature” to
trigger defrost sooner. Defrost will
never be triggered if the coil
temperature does not fall below the
Enable Temperature. If the Enable
Temperature is too high, the system
may defrost when it’s not necessary.
System does not
defrost
completely
Observe defrost cycle Defrost starts too late. Too
much ice is built up before
starting a defrost cycle.
• Verify sensor placement and readings
are correct.
• Increase the “Enable Temperature” to
trigger a defrost sooner.
• Lower the “Defrost Cycle Time” to
trigger a defrost sooner. Note this
parameter has no effect if an outdoor
air sensor is installed as the decision
would be made based on the
temperature difference between coil
and air.
Defrost cycle ends too
soon. Not all the ice is
removed.
• Verify sensor placement and readings
are correct.
• Increase the “Termination
Temperature” to allow the coil to get
hotter before a defrost cycle is
terminated.
• Increase the “Maximum Defrost
Time” to allow a defrost cycle to run
longer.
System defrosts
too much Observe defrost cycle Defrost triggers too
frequently, even with little
or no ice buildup.
• Verify sensor placement and readings
are correct.
• Decrease the “Enable Temperature”
to force the coil to get colder before a
defrost is triggered. Increasing this
parameter too much can result in not
triggering a defrost at all. Verify coil
readings with respect to this
parameter.
• Increase the “Defrost Cycle Time” to
delay triggering a defrost. Note this
parameter has no effect if an outdoor
air sensor is installed.
Defrost cycle lasts too
long. Ice is melted long
before the cycle ends.
• Verify sensor placement and readings
are correct.
• Decrease the “Termination
Temperature” to allow the defrost
cycle to end with a cooler coil
temperature.
• Decrease the “Maximum Defrost
Time” to force the defrost cycle to end
sooner.
No
Auxiliary/Emerg
ency Heat
Check configuration
parameters
Active W request with no
Aux heat output
• Verify warm weather aux heat lockout
isn’t active. Adjust “Aux Heat Lockout
Temperature” if necessary.
•Checkwiring
•Replacecontrol
No Aux heat output during
defrost cycle
•Checkwiring
•Replacecontrol
Table 5. Troubleshooting. (Continued)
Condition Procedure Control Status Corrective Action

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
11 34-00032EF—01
Table 7. Sensor Diagnostics.
The product should not be disposed of with other household waste. Check for the nearest authorized collection
centers or authorized recyclers. The correct disposal of end-of-life equipment will help prevent potential
negative consequences for the environment and human health.
Table 6. Fault Code Information.
Fault No. Description Corrective Action
1 Internal Communication Fault • Replace control
2 Internal Fault • Replace control
3 Low 24V • Measure 24V (R & C). There may be something in the
system loading the 24V transformer excessively. If voltage
is normal while the fault is currently active, replace the
control.
4 Corrupt Memory • Reset configuration options. Replace the control if the fault
persists.
5HighPressureLockout–HPC
opened 3 times on a single
request.
• Investigate refrigerant charge
• Check indoor coil for blockage
• Check outdoor coil for blockage
6 Low Pressure Lockout – LPC
opened 3 times on a single
request.
• Investigate refrigerant charge
7 High Pressure Cutout is currently
open
• Investigate refrigerant charge
• Check indoor coil for blockage
• Check outdoor coil for blockage
8 Low Pressure Cutout is currently
open
• Investigate refrigerant charge
9 Coil Sensor Open Circuited • Check the sensor hasn’t become unplugged.
• Check sensor wiring
•Replacesensor
10 Coil Sensor Shorted • Check for pinched wires
•Replacesensor
11 Air Sensor Open Circuited • Check the sensor hasn’t become unplugged.
• Check sensor wiring
•Replacesensor
Note that this fault will only present itself if the sensor opens
after it has been detected. It will be cleared on a reset or power
cycle. Running without an air sensor causes the control to
operate in a timed defrost mode, which may be desired
operation.
12 Air Sensor Shorted • Check for pinched wires
•Replacesensor
Display Description
Air sensor open circuit or unplugged
Air sensor shorted
Coil sensor open circuit or unplugged
Coil sensor shorted
A−−
M37655
A
__
M37656
−−
C
M37657
C
M37658
__

DB7110U UNIVERSAL HEAT PUMP DEFROST CONTROLLER
This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-633-3991
©2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved.
www.resideo.com
Resideo Inc., 1985 Douglas Drive North,
Golden Valley, MN 55422
34-00032EF—01 M.S. 03-19 | Printed in United States

INSTRUCTIONS D’INSTALLATION
Régulateur de dégivrage
universel pour thermopompe
DB7110U
APPLICATION
Le régulateur de dégivrage universel pour
thermopompe DB7110U est utilisé avec les
thermopompes à un étage. Ce produit remplace plus
de 260 régulateurs de fabricants d’origine et
peut-être facilement programmé pour répondre aux
exigences de pratiquement toutes les thermopompes
à un étage. Voir la Tableau 2, « Tableau de
compatibilité. » à la page 5.
CARACTÉRISTIQUES
Le régulateur DB7110U offre :
• Régulateur de dégivrage universel pour
thermopompes à un étage
• Affichage à DEL pour une configuration et une
installation faciles
• Petit encombrement pour une installation plus
facile
• Modes de dégivrages programmés et sur demande
• Indicateurs d’état et d’anomalie
• Retard d’inversion sélectionnable pour limiter le
bruit lors de l’activation et la désactivation d’un
cycle de dégivrage
• Historique des pannes facilitant le dépannage
Fig. 1. DB7110U1000.
SPÉCIFICATIONS
Spécifications électriques
Tension d’entrée : 24 V c.a., 60 Hz
Intensité d’entrée maximale : 200mA
Contacteur du compresseur : 1 A à 24 V c.a.
Ventilateur extérieur :
moteur ½ HP, 5A à pleine charge, 30 A avec rotor
bloqué, 240 V c.a.
Chauffage auxiliaire : 1 A à 24 V c.a.
Robinet inverseur : 1 A à 24 V c.a.
Toutes les sorties ont une capacité nominale de
100 000 opérations.
Toutes les bornes sauf FAN-IN et FAN-OUT sont
type basse tension NEC classe 2.
Spécifications
environnementales
Plage de températures de fonctionnement :
40°C à 66°C (-40°F à 150°F)
Limites d’humidité :
moins de 95 % (sans condensation)
INSTALLATION ET
CONFIGURATION
Présentation
Lorsque vous installez ce produit…
1. Lisez ces instructions attentivement. L’omission
de suivre les instructions peut endommager le
produit ou causer une condition dangereuse.
2. Vérifiez les caractéristiques nominales
indiquées dans ces instructions et sur le produit
pour vous assurer qu’il convient à l’utilisation
prévue.
3. L’installateur doit être un technicien en
entretien formé et expérimenté.
MENU SETTING
SYSTEM FAULT
M37637
DB7110U-DEFROST CONTROL

RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U
34-00032EF—01 2
4. Une fois l’installation terminée, utilisez ces
instructions pour vérifier le fonctionnement du
produit.
AVERTISSEMENT
Danger d’électrocution. Peut causer des
blessures graves, le décès ou des dommages
matériels.
Débranchez l’alimentation électrique avant de
commencer l’installation afin de prévenir les
décharges électriques ou les dommages
matériels. Plus d’un débranchement peut être
nécessaire.
Emplacement du régulateur
1. Avant de retirer le régulateur existant, prenez
note des raccordements de fils pour assurer leur
branchement correct aux bornes du régulateur
DB7110U.
2. Montez le DB7110U dans la boîte de jonction
sur l’unité extérieure à l’aide des deux vis
autotaraudeuses incluses.
3. Au besoin, utilisez le régulateur comme modèle
pour percer de nouveaux trous de montage.
4. Si les pattes de montage interfèrent avec les
autres composants de la boîte de jonction,
coupez celles qui ne sont pas utilisées avant de
serrer les vis de montages.
Emplacement du capteur du
serpentin
Fig. 2. Capteur de serpentin.
1. Le capteur de serpentin extérieur doit être
utilisé. Sans ce capteur de serpentin, le
DB7110U ne peut pas déterminer si un
dégivrage est nécessaire. Le capteur de
serpentin fourni avec le DB7110U remplace le
thermostat de dégivrage ou le capteur de
serpentin existant installé sur l’appareil.
2. Placez le capteur sur le serpentin, à l’endroit où
se trouvait le capteur/thermostat d’origine. Si
vous remplacez un thermostat de dégivrage,
prenez note des réglages d’origine pour un
réglage correct des températures d'activation et
de fin de cycle sur le DB7110U. Ils sont souvent
marqués par leurs points d’ouverture et de
fermeture. Par exemple, un thermostat marqué
L60-25F correspondrait à une température de
fin de cycle de 15°C (60°F) et une température
d’activation de 1,6°C (15,6°C - 14°C) (60°F
[60°F -25°F]).
3. Si l’emplacement du capteur/thermostat
d’origine est inaccessible ou difficile d’accès,
placez le nouveau capteur de serpentin sur la
boucle de serpentin la plus proche du détendeur,
où le réfrigérant pénètre dans le serpentin
durant le mode de chauffage. Cet emplacement
procure la plus grande différence de
températures de l’air.
4. Assurez-vous que le capteur de serpentin est
bien serré sur le serpentin. Il peut être
souhaitable d’ajouter de l’isolant au capteur
pour obtenir des lectures plus précises, bien que
cela ne soit généralement pas nécessaire.
Fig. 3. Montage du capteur de serpentin.
CAPTEUR DE
TEMPÉRATURE D’AIR
EXTÉRIEUR (DÉGIVRAGE
SUR DEMANDE
SEULEMENT)
Fig. 4. Capteur d’air.
1. Le capteur de température extérieure est conçu
uniquement pour les systèmes de dégivrage sur
demande. L’utilisation de ce capteur permet au
régulateur DB7110U d’utiliser un algorithme de
dégivrage plus avancé qui détermine le
dégivrage en fonction de la relation entre la
température du serpentin et celle de l’air. Sans
capteur de température d’air, le DB7110U
()dégivrera lorsque la température du serpentin
est inférieure à la température d’activation du
cycle de dégivrage. Il est conseillé d’utiliser le
capteur de température d’air s’il est possible de
le faire afin de réduire le nombre de dégivrages
inutiles qui sont fréquents avec les minuteries
de dégivrage.
2. Montez le capteur de température d’air de sorte
que la capsule soit suspendue dans l’air près du
serpentin extérieur.
M37663
MF37638
CAPTEUR
M37664

RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U
3 34-00032EF—01
3. Ne placez pas le capteur de température d’air
trop près du serpentin, car cela pourrait avoir
une incidence sur les lectures du capteur.
4. Ne montez pas le capteur de température d’air
directement au soleil.
5. La capsule du capteur de température d’air ne
doit pas être en contact avec du métal ou tout
autre matériau susceptible de modifier ses
lectures.
Câblage
AVERTISSEMENT
Danger d’électrocution. Peut causer des
blessures graves, le décès ou des dommages
matériels.
Débranchez l’alimentation électrique avant de
commencer le câblage afin de prévenir les
décharges électriques ou l’endommagement
de l’équipement. Plus d’un débranchement
peut être nécessaire.
1. Assurez-vous que le câblage est conforme à tous
les codes et ordonnances locaux.
2. Si le câblage bas tension est constitué de fils
dénudés sans bornes, câblez-les aux raccords
flexibles compris. Ne pas sertir les bornes au fil
plein.
3. Vérifiez les raccordements de tension secteur au
relais du ventilateur pour vous assurer qu’ils
sont bien serrés, en bon état et à plus de 6 mm
(¼ po) de toute partie du boîtier de l’appareil.
4. Branchez le capteur extérieur (le cas échéant) et
le capteur de serpentin.
5. Reportez-vous aux schémas de câblage des
figures 5 à 8 pour assurer un câblage correct de
l’appareil.
Tableau 1. Raccordements basse tension de classe
2, 24 V/60 Hz.
Fig. 5. Schéma de câblage avec les pressostats
raccordés à la commande de dégivrage.
Fig. 6. Schéma de câblage pour les systèmes sans
pressostat basse pression.
Nom Function
R (24 V) 24 V chargé
C (neutre) 24 V neutre
W Demande de chaleur
auxiliaire/d’appoint du thermostat –
les demandes W provoquent
l’excitation du circuit de sortie AUX.
Y Demande de compresseur
provenant du thermostat – les
demandes Y entraîneront
l’excitation des bornes COMPR et
FAN.
O Demande de robinet inverseur du
thermostat - contrôle l’état de la
sortie RV.
HPC (2 bornes) Coupe-circuit haut pression – ses
bornes doivent être court-circuitées
pour le fonctionnement du
compresseur. Ne jamais contourner
les pressostats de protection.
LPC (2 bornes) Contacteur de basse pression – ces
bornes doivent être mises en court-
circuit pour utiliser le compresseur.
Ne jamais contourner les
pressostats de protection.
AUX Sortie vers le chauffage
auxiliaire/d’appoint – excité lors
d’un cycle de dégivrage ou à la
demande de l’entrée W.
COMPR
(2 bornes)
Sortie vers le contacteur du
compresseur - activée par une
demande Y.
RV (2 bornes) Sortie vers le robinet inverseur –
excité par l’entrée O et à la demande
d’un cycle de dégivrage.
Nom Function
LPC
HPC
CONTACTEUR
AUX
ROBINET
INVERSEUR
FAN-IN
FAN-OUT
R
C
O/B
W
Y
CAPTEUR DE
TEMPÉRATURE D’AIR
EXTÉRIEUR (FACULTATIF)
CAPTEUR DE
SERPENTIN
É
QUIPEMENT
INTÉRIEUR
É
QUIPEMENT EXT
É
RIEUR
VENTILATEUR
DB7110U
L1
L2
COMPR
RV
CONTACTEUR
HAUTE
PRESSION
CONTACTEUR
BASSE
PRESSION
AIR
COIL
MF37756
LPC
HPC
AUX FAN-IN
FAN-OUT
R
C
O/B
W
Y
DB7110U
L1
L2
COMPR
RV
AIRCOIL
MF37757
CAPTEUR DE
SERPENTIN
ROBINET
INVERSEUR
CONTACTEUR
CONTACTEUR
HAUTE
PRESSION
CAPTEUR DE
TEMPÉRATURE D’AIR
EXTÉRIEUR (FACULTATIF)
ÉQUIPEMENT
INTÉRIEUR
ÉQUIPEMENT EXTÉRIEUR
VENTILATEUR

RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U
34-00032EF—01 4
Fig. 7. Schéma de câblage pour les systèmes avec
pressostats en série avec le contacteur et sans
raccordement à la commande de dégivrage.
Fig. 8. Schéma de câblage pour les installations à
une minuterie.
CONFIGURATION
1. Branchez l’alimentation.
2. Lors de la mise sous tension, la version logicielle
du DB7110U clignote brièvement sur l’écran,
puis les cycles de fonctionnement normaux
commencent à s’afficher, indiquant le mode
actuel et les valeurs des deux capteurs de
température. Notez qu’il existe un bref délai de
démarrage après la mise en marche lorsque le
fonctionnement du compresseur est interdit.
Fig. 9.
Les valeurs de température de serpentin et d’air
affichées peuvent être très utiles pour optimiser
et dépanner les performances de dégivrage.
3. Plusieurs options configurables permettent
d’optimiser les performances de dégivrage. Voir
la section « INTERFACE UTILISATEUR » à la
page 7 pour une description détaillée de chaque
paramètre/écran. Appuyez sur le bouton de
sélection (o) pour parcourir les différents écrans
et les boutons et pour régler les différents
paramètres. La Tableau 4 ci-dessous décrits
chaque paramètre.
VÉRIFICATION
1. Après l’expiration du délai de démarrage,
générez une demande de chauffage au moyen
d’un court-circuit de R sur Y (et R sur O si
configuré en tant que système « B », inversant le
robinet excité en mode de chauffage).
2. Confirmez que le compresseur, le ventilateur et
le robinet inverseur (le cas échéant) sont sous
tension.
3. Maintenez le bouton enfoncé jusqu’à ce que
« test » apparaisse à l’écran, comme indiqué ci-
dessous.
Fig. 10.
4. Confirmez que l’appareil passe en mode
dégivrage
Fig. 11.
Le robinet inverseur changera d’état et le
chauffage auxiliaire sera alimenté. Quelques
instants plus tard, le ventilateur sera éteint. Si le
retard d’inversion est activé, le compresseur se
désactivera pour la durée sélectionnée, puis se
rallumera pour réduire le bruit.
Le DB7110U restera en mode de dégivrage
pendant au moins une minute. Après une
minute, le DB7110U quittera le mode de
dégivrage lorsque la température du serpentin
dépassera la température de fin de cycle ou
après la durée de dégivrage sélectionnée, selon
la première éventualité.
Le mode test peut être arrêté à tout moment en
maintenant de nouveau le bouton enfoncé.
LPC
HPC
AUX FAN-IN
FAN-OUT
R
C
O/B
W
Y
DB7110U
L1
L2
COMPR
RV
AIRCOIL
SI LES PRESSOSTATS SONT RACCORDÉS EN SÉRIE
AVEC LE CONTACTEUR, METTRE DES CAVALIERS
ENTRE LES RACCORDEMENTS EMBARQUÉS. NE
CONTOURNER AUCUN PRESSOSTAT DE PROTECTION.
MF37758
ROBINET
INVERSEUR
CONTACTEUR
CONTACTEUR
HAUTE
PRESSION
CONTACTEUR
BASSE
PRESSION
CAPTEUR DE
TEMPÉRATURE D’AIR
EXTÉRIEUR (FACULTATIF)
CAPTEUR DE
SERPENTIN
ÉQUIPEMENT
INTÉRIEUR
ÉQUIPEMENT EXTÉRIEUR
VENTILATEUR
LPC
HPC
AUX FAN-IN
FAN-OUT
R
C
O/B
W
Y
DB7110U
L1
L2
COMPR
RV
SI LES PRESSOSTATS SONT
RACCORDÉS EN SÉRIE AVEC LE
CONTACTEUR, METTRE DES
CAVALIERS ENTRE LES
RACCORDEMENTS EMBARQUÉS.
NE CONTOURNER AUCUN
PRESSOSTAT DE PROTECTION
AIRCOIL
LORSQUE LE CONTACTEUR DU COMPRESSEUR EST ALIMENTÉ
DIRECTEMENT À PARTIR DE LA BORNE Y, RÉGLER LE RETARD
D’INVERSION ET LE RETARD DU CYCLE COURT SUR 0.
MF37759
ROBINET
INVERSEUR
CONTACTEUR
CONTACTEUR
HAUTE
PRESSION
CONTACTEUR
BASSE
PRESSION
CAPTEUR DE
SERPENTIN
É
QUIPEMENT
INTÉRIEUR
É
QUIPEMENT EXT
É
RIEUR
VENTILATEUR
MF37640
MODE DE FONCTIONNEMENT
ACTUEL ARRÊT, CHAUFFAGE,
CLIMATISATION, RETARD, ETC.
TEMPÉRATURE DU SERPENTIN
EXTÉRIEUR EN DEGRÉS
FAHRENHEIT
TEMPÉRATURE DE L’AIR
EXTÉRIEUR EN DEGRÉS
FAHRENHEIT
M37641
M37642
de Fr

RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U
5 34-00032EF—01
TABLEAU DE
COMPATIBILITÉ
Tableau 2. Tableau de compatibilité.
Amana C64301-1 C6431001
Arcoaire 32312-00 3232140
Armstrong 39840B001 44614-0001
44614-002 46257-001
47181-001 R46257-001
R46614-002 R47181-001
39840B002 37967B001
37967B002 R46K6701
R44614-001 R44614-002
Artesian 10321-00
Carrier 150-83-6A 621-xxxx
CES0110063-00 CES0110063-01
CES0110063-02A CES0130024-00
CES0130024-01 CES0130076
HK25SZ359A HK32EA001
HK32EA003 HK32EA007
HK32EA008 HK32FA003
HK32FA006
Coleman 3030A374 3030A364
3C30A374
Comfortmaker 1029-2 34332100
34332101
Evcon 9218-374
Fast 1093410
Goettl 305007
Goodman 1084-03-2022 1084-200D
20293901 B1226006
B1226008 LR40061
PCBDM101 PCBDM130
PCBDM133 PCBDM160
PCBDM101S PCBDM130S
Heil Quaker HQ1052727
Heil/Tempstar 1087952 1087953
1173636 CEPL130524-01
Honeywell ST74A1004 ST74A1020
ST74A1038 ST74A1053
ST74C1002
ICM DFORB24A21300 ICM300C
DFORB-AB1004 DFORF
DFOSP24A2 ICM301C
ICM302C ICM303C
ICM304 ICM307
ICM316 ICM317
ICM318 ICM319
ICM320 ICM321
ICM322 ICM323
W1001-4
ICP 1052757 1069364
Interthem 6208800
Lennox 100269-01 100269-02
100269-04 100269-05
11K7101 1507N170027
29M0101 29M0201
30W87 33G9501
34M6301 46K67
56M3701 68I2901
68J8401 78H6801
84W8801 86G1601
97M81 LB-101263A
LB-101263B 11K71
97M8101 30W8701
34M63 29M01
56M37 HPXB15
68I84 68I29
78H68
Nordyne 620880 621301A
621579B 621579C
624519A 624608
624626 624633
624644 624656
624700 917012
917178 917178A
920338 624644R
6246440 624633R
6246330
Ranco DT2
Rheem 47-102684-01 47-102684-02
47-102684-03 47-102684-04
47-102684-07 47-102684-08
47-102684-83 47-102685-01
47-102685-02 47-102685-03
47-102685-04 47-102685-05
47-102685-06 47-102685-84
47-21517-11 47-21517-13
47-21517-14 47-21517-16
47-21517-17 47-21517-18
47-21517-22 47-21517-23
47-21517-24 47-21517-82
47-21517-88 47-21517-92
47-21776-01 47-21776-06
47-21776-86 DDL-013002-0RH
DLL-013002-1RH DDL-0131020-1RH
DDL-017002-2RH DDL-017102-1RH
DDL-017702-1RH DDL-117702-3RH
DDL-122131-2RH 47-21517-12
47-21517-85 47-102685-87
47-102684-09 47-102685-07
47-21517-20
Robertshaw DT2-1000 TD-10
Tableau 2. Tableau de compatibilité. (Suite)

RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U
34-00032EF—01 6
SnyderGeneral 1395-329 CEBD430524-04B
Tempstar/ICP 1084-100 1084-83-1008
1087562
Therm-O Disc 26E-10
Trane 21C14501G18 21C1450127
21C1450136 21C1450137
21C1450138 21C1450142
21C1450144 21C1450145
21C1450153 21C1450154
21C1450155 21C1450160
21C14282G01 CNT01106
CNT01108 CNT01129
CNT01152 CNT01431
CNT01510 CNT01642
CNT01923 CNT01924
CNT01926 CNT02514
CNT02515 CNT02516
CNT02920 CNT02935
CNT03715 CNT03716
CNT04362 CNT04363
CNT04364 CNT04366
CNT04368 CNT04695
CNT05001 CNT05008
CNT05009 CNT05010
CNT05482 CNT05875
CNT1108 CNT01693
Weatherking 840-4-5548
White-Rodgers 840-4-5548 47D40-801
47D43-101 47D43-111
47D43-11102 47D43-811
90-621 47D01U-843
York 031-00872-001 031-00872-002
031-00872-002 031-00872-701
031-00872-702 031-00872-703
031-01222-000 031-01251-000
031-01268-000 031-01954-000
031-01975-000 031-09104-000
031-09170-000 331-01975-001
331-01975-102 331-09139-000
9218-3741 S1-03100872701
S1-03109170000 S1-33101954000
S1-33101975102
Tableau 2. Tableau de compatibilité. (Suite)

RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U
7 34-00032EF—01
INTERFACE UTILISATEUR
L’interface utilisateur comprend trois boutons, deux voyants DEL et 4 chiffres à 7 segments. Les deux chiffres
de gauche représentent généralement la catégorie de ce qui est affiché, tandis que les deux chiffres de droite
représentent la valeur ou le réglage de la catégorie. La seule exception est lorsqu’une valeur nécessite 3 chiffres,
comme une température supérieure à 37°C (99°F), comme indiqué ci-dessous, avec deux valeurs de
« température de fin de cycle » de 32°C et 37,7°C (90°F et 100°F).
Fig. 12. Deux exemples de valeurs de l’option de configuration 2 (température de fin de cycle).
Le bouton « o » permet de passer à l’écran suivant, tandis que les boutons et permettent de régler la valeur
de chaque paramètre.
Notez qu’après une heure sans action sur un bouton, l’affichage à 7 segments s’éteint pour économiser de
l’énergie. Vous devez appuyer sur un bouton pour rallumer l’écran.
Tableau 3. Écrans d’état.
Les écrans de configuration sont des paramètres numérotés comprenant une valeur sélectionnable,
conformément au tableau ci-dessous.
Par exemple, cet écran représenterait le paramètre 1 (température d’activation du dégivrage) réglé sur
1,6/35 (°C/°F).
Affichage Description
Anomalies actuellement présentes. Aucun chiffre à droite s’il n’y a aucune anomalie.
Appuyez sur et pour faire défiler les anomalies actives.
Historique des anomalies. Appuyez sur et pour faire défiler l’historique.
Maintenez le bouton enfoncé pendant plus de deux secondes pour supprimer
toutes les anomalies inactives.
90 1
00
M37659
22
4
F
M37660
H 11
F
M37661
135
M37662
Tableau 4. Écrans de configuration.
Affichage Description Plage Par défaut
1 Température d’activation du dégivrage. Température du
serpentin à laquelle la fonction de dégivrage est active.
-1°C à 2°C
(30°F à 36°F)
1,6°C (35°F)
2 Température de fin de cycle. Température du serpentin à
laquelle le dégivrage est terminé.
10°C à 37,7°C
(50°F à 100°F)
21°C (70°F)
3 Durée du cycle de dégivrage. Le temps durant lequel la
température du serpentin est inférieure à la température
d’activation du dégivrage avant qu’un dégivrage ne soit
déclenché si en mode temporisé (aucun capteur de température
d’air extérieur n’est présent).
30 à 120 minutes 30 minutes
4 Temporisation de cycle court. Durée d’arrêt minimale entre les
cycles du compresseur.
0 à 5 minutes 3 minutes
5 Type de robinet inverseur. Type O = le robinet inverseur est excité
en mode de climatisation. B = le robinet inverseur est excité en
mode de chauffage.
O ou B O

RÉGULATEUR DE DÉGIVRAGE UNIVERSEL POUR THERMOPOMPE DB7110U
34-00032EF—01 8
DEL verte : Indique la puissance et le fonctionnement du système.
DEL rouge : Indique qu’une anomalie est actuellement présente et que l’utilisateur doit consulter l’affichage à
7 segments pour en savoir plus.
6 Délai d’inversion. Temps d’arrêt du compresseur lors de la
commutation entre les modes de chauffage et de dégivrage.
Régler cette valeur sur 0 réduira le temps de dégivrage général,
mais peut entraîner des bruits excessivement forts lors de
l’activation et de la désactivation du mode de dégivrage (selon
le type de compresseur).
0 à 30 secondes 30 secondes
7 Durée maximale de dégivrage. Durée maximale d’un cycle de
dégivrage. Un cycle de dégivrage peut être terminé plus tôt si le
serpentin atteint la température de fin de cycle, mais un cycle de
dégivrage ne doit jamais durer plus longtemps que cette valeur.
8 à 14 minutes 14 minutes
8 Température de verrouillage du chauffage auxiliaire. Les
demandes de W seront ignorées si la température extérieure est
supérieure à cette température. La sortie du chauffage
auxiliaire fonctionnera tout de même normalement pendant un
cycle de dégivrage, sans égard à ce réglage. Ne réglez pas cette
température à une température inférieure à celle du verrouillage
du compresseur, sinon il y aura une plage de températures sans
chauffage.
-17,7°C à 4,4°C
(0°F à 40°F)
Aucun
verrouillage
(OF)
9 Température de verrouillage du compresseur. Les demandes de
Y seront ignorées si la température extérieure est inférieure à
cette température. Ne réglez pas cette température à une
température supérieure à celle du verrouillage du chauffage
auxiliaire, sinon il y aura une plage de températures sans
chauffage.
-23,3°C à 4,4°C
(-10°F à 40°F)
Aucun
verrouillage
(OF)
Tableau 4. Écrans de configuration. (Suite)
Affichage Description Plage Par défaut
Table of contents
Languages:
Other Honeywell Home Controllers manuals

Honeywell Home
Honeywell Home TheraPro HR90 User manual

Honeywell Home
Honeywell Home H4600A User manual

Honeywell Home
Honeywell Home HR92UK User manual

Honeywell Home
Honeywell Home HR92 User manual

Honeywell Home
Honeywell Home Lyric LCP500-L Product information sheet

Honeywell Home
Honeywell Home HVC0001 User manual

Honeywell Home
Honeywell Home H46C-F User manual

Honeywell Home
Honeywell Home Evohome User manual

Honeywell Home
Honeywell Home 3000 Series User manual

Honeywell Home
Honeywell Home R8182H User manual