manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell ADEMCO 4204 User manual

Honeywell ADEMCO 4204 User manual

Other Honeywell Control Unit manuals

Honeywell NOTIFIER FCM-1A User manual

Honeywell

Honeywell NOTIFIER FCM-1A User manual

Honeywell AVS User manual

Honeywell

Honeywell AVS User manual

Honeywell NOTIFIER ASY-01-044-NIM User manual

Honeywell

Honeywell NOTIFIER ASY-01-044-NIM User manual

Honeywell VGF21 Operation manual

Honeywell

Honeywell VGF21 Operation manual

Honeywell RA890F Protectorelay Primary Control Installation guide

Honeywell

Honeywell RA890F Protectorelay Primary Control Installation guide

Honeywell WV8840B User manual

Honeywell

Honeywell WV8840B User manual

Honeywell VF5000 Series User manual

Honeywell

Honeywell VF5000 Series User manual

Honeywell Braukmann FD300 User manual

Honeywell

Honeywell Braukmann FD300 User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell RM7800L1087 User manual

Honeywell

Honeywell RM7800L1087 User manual

Honeywell MNG verafix User manual

Honeywell

Honeywell MNG verafix User manual

Honeywell TR70 User manual

Honeywell

Honeywell TR70 User manual

Honeywell RV284 User manual

Honeywell

Honeywell RV284 User manual

Honeywell SM152 AA Series User manual

Honeywell

Honeywell SM152 AA Series User manual

Honeywell GSMVLP5 Assembly instructions

Honeywell

Honeywell GSMVLP5 Assembly instructions

Honeywell W8735ER User manual

Honeywell

Honeywell W8735ER User manual

Honeywell MK VI Manual

Honeywell

Honeywell MK VI Manual

Honeywell S8910U Original instructions

Honeywell

Honeywell S8910U Original instructions

Honeywell Gamewell FCI Velociti Series User manual

Honeywell

Honeywell Gamewell FCI Velociti Series User manual

Honeywell SM152 Series User manual

Honeywell

Honeywell SM152 Series User manual

Honeywell SILENT KNIGHT SK-FML User manual

Honeywell

Honeywell SILENT KNIGHT SK-FML User manual

Honeywell SV2 Series User manual

Honeywell

Honeywell SV2 Series User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell Class 500 User manual

Honeywell

Honeywell Class 500 User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

ADEMCO 4204 Relay Module – Installation Instructions
GENERAL INFORMATION
The ADEMCO 4204 Relay Module provides from one to four
dry, form-C (SPDT) relay outputs to compatible
control/communicators. It connects to the control’s keypad
wiring terminals.
The 4204 can be mounted inside the control’s cabinet or
mounted remotely depending on the application. Refer to the UL
notes below for certain restrictions.
If mounted remotely, the 4204 has a built-in tamper switch that
allows it to detect and report the removal of its cover to the
control. Second, communication to the 4204 is supervised so
that it cannot be disconnected from the keypad wiring without
detection by the control. If the wiring is cut, a tamper or alarm
signal will result, to indicate that this device (and possibly other
devices connected to the keypad wiring) has become
inoperative.
INSTALLATION
For UL Installations:
When used with controls that do not support cover tamper or
supervise communications wiring to the 4204, mount the 4204
inside the control’s cabinet.
When used with controls that support cover tamper and
supervise communications wiring to the 4204, mount the 4204
may either be mounted inside the control’s cabinet or mounted
remotely.
CUL
NOTE: The maintenance instructions shall detail all test
and maintenance instruction codes and software
necessary to provide test and inspection requirements
of CAN/ULC-S536, Standard for the Inspection and
Testing of Fire Alarm Systems
When mounted inside the control’s cabinet, some controls allow
the 4204 to be mounted horizontally as follows: insert the self-
tapping screws (provided) in two adjacent raised tabs on the
back of the cabinet. Leave the heads projecting 1/8”. Hang the
4204 on the screw heads via two of the slotted holes on the
back of its housing. The 4204’s cover need not, in this case, be
tamper-protected. Set DIP switch 1 to “ON” if the cover is not
used (see table). See the control’s instructions for additional
information.
When the 4204 is mounted remotely, it can be mounted
horizontally or vertically and the built-in tamper switch can be
used. Wires can exit from the side or via the breakout on the
back of its housing. The DIP switch must be set with its position
1 “OFF” and when the installation is completed, the unit’s
tamper-protected cover must be replaced.
NOTE: For EN50131-3 compliance a tie-wrap must be secured
around the case of a remotely mounted 4204.
Apply tie-wrap around the case to the right of the large zone
wire opening (4-inch case width). This is in opposition of the
tamper switch and magnet.
NOTE: CE installations require maximum cable length of 30
meters.
Affix the connections label that accompanies the 4204 to the
inside of the 4204’s cover (if the cover is used) or to the inside of
the control’s cover.
CONNECTIONS AND SETTINGS
Select and set an address for the 4204, using its DIP switch as
shown in the DIP switch table. Each 4204 must be assigned a
unique address so the control can identify and communicate
with the 4204. The address to set is determined by the
particular control to be used. See the control’s installation
instructions. As shipped, the DIP switch is set for address “0”.
UL
•
For UL fire installations, no more than
one wire per terminal may be
connected.
•Use only 14-22AWG wire.
NOTE: All power-limited wiring must be separated from non-
power limited wiring by ¼”.
Make connections to the 4204’s four relays via 12-position
terminal block TB2. Refer to the control’s installation
instructions for specific information on how to program the
activation options for the relays.
Make connections to the control’s keypad wiring points via 4-
position terminal block TB1, the 4-pin plug, or both (wire color
connections are the same). See the diagram on the other side
of this page.
SPECIFICATIONS
Physical: 6-7/16” W x 4-1/4” H x 1-1/4” D
(163mm x 108mm x 32mm)
Electrical:
Input Voltage:
12VDC nominal (10
-
14VDC, from
control’s remote keypad connection
points)
Input Current:
15mA standby + 40mA per active relay
Contact Rating:
2A max. at 28VDC/AC (resistive loads)
UL
•
For dry, indoor use only. Do not install in air-
handling spaces.
•For UL Commercial Burglary installations, the
4204 must be tamper protected or mounted in
a tamper-protected cabinet.
•In Commercial Fire applications, the module
cannot be mounted in the control unit’s
cabinet, but must be mounted in an external
UL864-listed cabinet.
N8909V5 1/17 Rev. A
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright

2008 Honeywell International Inc.
www.honeywell.com/security
4204-01-V1
4204 ADDRESS SETTINGS
("—" means "OFF")
DETERMINE 4204'S ADDRESS: CONTROL'S INSTRUCTIONS SPECIFY ADDRESS
TO USE. "0" ADDRESS SETTING SHOWN (AS SHIPPED).
SWITCH
NUMBER
0 1 2
3 4 5 6 78910 11 12 13 14 15
2
ON
—
ON —ON —ON —ON —ON —ON —ON —
3
ON ON
—
—ON ON ——ON ON ——ON ON ——
4
ON ON ON ON ————ON ON ON ON ————
5
ON ON ON ON ON ON ON ON —————— — —
1 2 3 4 5
Þ
DIP SWITCH SETTINGS
OFF ON
DIP SWITCH (WHITE AREAS DENOTE SWITCH HANDLES)
POSITIONS 2-6:
POSITION 1: ENABLES/DISABLES COVER TAMPER. ON = TAMPER DISABLED,
OFF = TAMPER ENABLED. SHOWN DISABLED AS SHIPPED.
6
ON ON ON ON ON ON ON ON
6 7
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
ON —ON —ON —ON —ON —ON —ON —ON —
ON ON ——ON ON
—
—ON ON ——ON ON ——
ON ON ON ON ——
—
—ON ON ON ON ————
ON ON ON ON ON ON ON ON —————— — —
—————— — —
——————
—
—
ON ON ON ON ON ON ON ON
POSITION 7: NO FUNCTION
TB2
121110
9
87654321
(–) GROUND
(+) 12VDC
YEL
BLK
GRN
RED
13 14 15 16
DIP SWITCH
FOR SETTING DEVICE ADDRESS
AND ENABLING/DISABLING TAMPER
COVER TAMPER (REED) SWITCH
TB1
4204
4-PIN TOUCHPAD PLUG
3
2
RELAY
1
4
TYPICAL
(SHOWN "OFF")
C
NC
NO
C
NC
NO
C
4204-02-V2
NC
NO
C
NC
NO
EITHER OR BOTH
CAN BE USED
DATA IN FROM CONTROL
DATA OUT TO CONTROL
RELAY
RELAY
RELAY
4204 CONNECTIONS
1 2 3 4 5 6 7
Must be connected to a
power-limited source.
If switching power
through a relay, the
power must be from a
power-limited source.
Relays are programmable
but outputs are not
supervised.
Supervised
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED FOR DETAILS REGARDING
THE LIMITATIONS OFTHE ENTIRE ALARM SYSTEM.
FEDERAL COMMUNICATIONS COMMISSION STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for
your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the
manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the
limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable
protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA CLASS B STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may
cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC & de RSS 210 des Industries Canada. Son fonctionnement est soumis aux
conditions suivantes: (1) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y
compris les interférences causant une réception indésirable.
SUPPORT & WARRANTY
For the latest documentation and online support information, please go to:
https://mywebtech.honeywell.com/
For the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
For patent information, see www.honeywell.com/patents
MyWebTech
Warranty
Patents