  9. Honeywell S300RPTU User manual

Honeywell S300RPTU User manual

1
Esc
Ok
D300-03-00
8
7
6
5
4
32
Connection
failed
**Retry? **
Deviceis:
conventional
Type--
Class:
------------
Detector
-¯ Sensor
CONTAMINATED
Service
Chamber
FAULTY
ReplaceUnit
Reading
OpticalXX %
ThermalXX %
ACQUIRE1
Detector
Settings
Last 2
Detector
Read
%Dirty
1234567890
OK
OK
OK
Detector Data
Corrupted
Device
Information
Missing
Attempting
Connection
LINK?...>END
Device
Address
XX
EscEsc
Esc
USERSGUIDEFORS300RPTUREMOTEPROGRAMMINGTEST
TOOL AND S300SATSATELLITERELAYDEVICE
INTRODUCTION
TheS300RPTURemoteProgrammingandTestToolisdesignedforcommunication withSystem
Sensor300seriesdetectors,permittingaccesstovariousfunctionsandlogswithinthedetectors.
Communicationisachieved throughthedetector’sindicator LED,andusesone oftwomethods:
1.Viaan LEDandOpto-diodebuilt intotheS300RPTU,forcloserange(approximately30mm)
communication.Thisallowsdirectcommunicationviathedetector LEDindicator.
2.UsingradiocommunicationviaanS300SATwhich canbeclippedto thedetectorusing
proprietaryaccesspoles,allowingarangeupto4.5m.
TheS300RPTUisamenudrivendevice. Withreferencetofigure1,thecontrolsfornavigating
throughthemenusareasfollows:
(1)On/OffSwitch
(2)Up/DownArrows-toscroll throughmenus
(3)OKbutton-Selectrequiredfunction
(4)Esc-Returnstothepreviousmenu
POWERON
Whenthe S300RPTUisturnedon,thescreenshownleft willbe
displayedforapproximately5seconds,and thenwillbe replacedby
thefirstofthemainmenuscreens.
MAINMENU
Thereare sixmainmenuitemsasfollows:
Readsthesettingspreviouslyprogrammedintothedetectorbeing
accessedincludingsensitivity,address,devicetype,LEDoperation
andservice date.Referto section2.
Displaystheinformationacquiredfromthelastdetectorread. Refer
tosection 2.
Programmesnewsettingssuchasaddress,sensitivityandmodeof
LEDoperationinto thedetector.Refertosection3.
Checksthatmaintenancehasbeensatisfactory,andifOK
programmesthe currentdateintothe detectorasthe newservice
date.Refertosection4.
PerformsadetectorAlarmTest.Refertosection5.
Allowsthe usertosetthe S300RPTUtoolto suitrequirements,
includingthe tooloperatinglanguageandcommunicationmethod.
Refertosection1.
Usetheup/downarrowbuttonstoadjust
screenintensitytosuitthenpressOKto
confirmsetting
Usetheup/downarrowbuttonstodisplay
eithercommunicationviathe RPTU LED or
the S300SAT,thenpressOKtoconfirm
setting.
Dateisdisplayedas-
Day/Month/Year
(Basedon GMT)PressOK toconfirm
Usethe up/downarrowsto displaythe
requiredlanguage to beused bythe
S300RPTU,andthenpressOKtoconfirm
setting
TheS300SATcan besettooneof16
addressesto preventcrosstalkif morethan
oneistobeusedon asite.Usetheup/
downarrowstoselecttherelevantaddress
(00-15)thenpressOKto confirmsetting.
Notethatonlyonenewsettingcanbemadeeach timetheRPTUsettingsscreenisaccessed.For
eachnewsetting, theS300RPTUwilldisplaythereadyscreenasfollowsforafew seconds,then
returnto the“RPTU Settings”screen.
Theexceptiontothisisthe S300SATaddressscreen,wheretheRPTU
willbriefly display“Attempting Connection”beforethe readyscreen
appears.
1: S300RPTU AND S300SATSETUP
Priortoanycommunicationswithdetectors,itisnecessarytoconfigure theS300RPTUand
S300SAT.Thisprocedureshouldonlyneed tobecarriedoutonce,thesettingsthen beingretained
untilchangedvia thisscreen.
Duringthe set-upprocedure,ensurethatonlyoneS300RPTUandS300SATpairare switchedon
withina10marea.
SwitchonboththeS300RPTUandS300SAT.Scrolldownthroughthemainmenuscreenstoselect
“RPTUSettings”. Thisgivesaccesstoset-upscreensasfollows:
2: ACQUIREDETECTORSETTINGS AND LASTDETECTORREAD
Exceptwhere indicated,thesameoperatingscreensapplytobothacquisitionofthedetectorsettings
andthedisplayofinformationfromthe lastdetectorread:
DisplaysDetectorTypeCode:
A=ConventionalEN54Standard,
B=ConventionalNF(AFNOR),
C= Special
DisplaysDetectorType:
Thermal, Optical or Opto-Thermal
DisplaysDetector Address
(00to 99) Serviceinformation-This
screenisonlydisplayed
forOpticalandPhoto-
Thermaldetectors.
DisplaysthecurrentChamber/Sensorvalues. Foran optical orthermal
detector,theopticalorthermalsensor readingonlywillbe displayedas
applicable.For photo-thermaldetectorsbothreadingswillbeshown.
Continuedoverleaf
DetectorDataCorrupted,
Returndetectortosupplier
forreprogramming.
TheS300RPTUwillautomaticallydisplaytherelevantscreen.Innormalconditions
withno smokepresent,the“%Dirty screen”willbedisplayed, givinganindicationof
thelevel ofcontaminationinthe detectorchamber.Ifthedetectorhasreached it’sdrift
compensationlimitandneedscleaning the “Sensor Contaminated”screenwillbe
shown,and iffaultythe“ChamberFaulty”screenwillbeshown.
Figure 1: S300RPTU
Figure 2: S300RPTU
Batteries
3x1.5V LR03(AAA)
BatteriesRequired.
RPTU 6
Settings
LCD6.1
Intensity
RPTU 6.2
SetLINK
mode
Read 6.3
Current
Date
Set
LinkVia
S300SAT
Set6.5
S300SAT
Address
Set6.4
RPTU
Language
CurrentDate
dd/mm/yy
SATAddress
setto:
XXOK
Language
setto:
English
*** Ready***
OK
1234567
Detectorincompatible
withS300RPTU.
Note:
1.LastDetectorRead
Detectorinformationisonly
displayedif asuccessful
“AquireDetector Settings”
haspreviouslybeenrun.
2.WhentheS300RPTUis
switchedoff, theLast
DetectorReaddataislost.
Series 300
RPTU - v.1.5
*** READY***
ACQUIRE1
Detector
Settings
Last2
Detector
Read
Write3
Detector
Settings
Write4
NEW
Service Date
Alarm5
Test
Press OKx2
RPTU6
Settings
I56-1720-003EN
D300-03-00
Alarm 5
Test
Press OK x2
Contaminated
Invalid
Attempting
Connection
LINK?...END
Deviceset
to Alarm
Connection
Failed
**Retry **
Chamber
FAULTY
ReplaceUnit
OK
OK OK
Fail
Device3.1
Address
SelectAddr.
andpress OK
01
Alarm3.2
Sensitivity
LED3.3
Operation
Set LED
Operation
-------- OK
Siren 3.4
Operation
SirenSound
set to:
X OK
Start OK
INCREMENTAL
Address Mode
Write3
Detector
Settings
OK
OK
OK
OK
OK
NEWAlarm
Sensitivity
--------OK
OK
OK
OK
OK
OK Attempting
Connection
LINK?...>END
Connection
failed
**Retry? **
OK
Fail
Success
OK
Esc OK
OK Fail
Success
Attempting
Connection
LINK?...>END
Connection
failed
** Retry? **
SelectAddr.
andpressOK
001
Device
Information
Missing
Start OK
toTransmit
NEWSettings
Esc
Detector
Data
Corrupted
Esc
Low Battery
inRPTU
RPTU
Faulty!
Goodbye...
LowBattery
in S300SAT
Will display“Alarm Sensitivity”for photo
and photo-thermalor“Alarm Method”for
thermaldetectors.
Levelwill be “Low”, “Medium” or “High”
Method will be “Fixed Temp”or “Rateof
Rise”
Displaysthedatethedetectorwaslastserviced.
Displayswhether thegreenLEDon thedetectorisset to“Blink”or
“No Blink”innormalconditions.
Displaysthedateofmanufacture
3: WRITEDETECTORSETTINGS
Selectsandwritesnewsettingsto thedetector.
Usearrowstoselecttherequired
address (01 to 99)andpressOKto
confirm.
Note: Only addresses1to 32 are
valid on the S300ZDU.
Usearrowsto selectalarmsensitivity
(LOW / MEDIUM / HIGH)and press
OKtoconfirm.
Note:Detectorsaresuppliedsetto
Mediumsensitivityasdefault.
Usearrowstoselectsiren sound-
from 1upto 6
Note:Thisfunctionisnotyet
available
Usearrowstoselect
No-Blink -LED offonstandby
Blink - GreenLEDBlinkingonstandby
Fromthe “Start to Transmit NEW Settings”Screen, press OKto send new settings
tothe detector. The“Attempting Connection”Screenwillbe displayedforafew
seconds,andabargraphwillbe displayedindicatingprogress.Onsuccessful
completionofprogramming, theRPTUwillreturn tothe “StartTransmission”screen.
Ifthe “ConnectionFailed”screen appears,eithercommunicationshave notbeen
established,or communicationshavebeeninterrupted duringtransmissionofthenew
settings.Connectionshouldbere-attemptedbypressingOK.
Note: It is possible to return to the "Start to Transmit NEW
Settings"Screen directly from the "Connection Failed"screen by
pressingEsc once if communications were not been established,or
twiceif thebargraph is displayedon thescreenbeforecommunica-
tions were lost, and asensitivity changewasrequested.However
extreme caution shouldbe exercised: If communicationswith a detectorhad
started, then using the Esc button to return to the "Start to Transmit NEW
settings"screencan cause thedetector's data to be lost,and the detector will
have to be returned to the supplier for reprogramming.
The “Deviceinformation Missing”screenappearsto indicatethatcommunication
hasbeenattemptedwithanincompatibledetector typeforexampleanECO1000. Press
“Esc”to returnto the “Start to Transmit NEW Settings”Screen.
The “Detector Data Corrupted”screen will appear ifan attempt is made to
reprogrammeadetectorwhichhaspreviouslybeen corrupted.Press“Esc” toreturnto
the “Start to Transmit NEW Settings”Screen.
Immediatelyfollowing completionofthewrite sequence,thenewsettingsshouldbe
verifiedusing“Acquire Detector Settings”, see section 2.
5: ALARM TEST
Thiswill forcethedetectortorunachambertestand,providedthechamberisgood,setthealarm
flagtoputthedetectorintoalarm.Ifthe chamberisfaultyorcontaminatedtherelevantscreen willbe
displayedon theRPTU. Note:Beforerunningthistest,notifythe
properauthoritiesthat thedetectoris
undergoingtest.
Oncethe detectorhasbeensetinto
alarm,communicationswiththe
S300RPTUwill belost,andthedetector
willneedtoberesetfrom thecontrol
panel.
PressOKtoreturntothemainmenu
6: OTHERSCREENS
Otherscreensthatmayappearatanytimeinclude thefollowing:
BatteriesintheS300RPTUneedreplacing.Withreference tothe
diagramonthefrontpage:
Thebatteryisaccessedbyunscrewingthefourscrews(8)and
removingthe rearcover.
Replacementbatteries(7)are3xLR03.AAASize1.5V.Ensurethat
correctpolarityisused.
WARNING: Do not remove the backup button cell (6) at anytime. This will cause RPTU
clock information to be lost, and the unit to stop working. Do not tamper with any part of
thecircuit except the main batteries or permanent damagemaybe caused.
Batteriesin theS300SATSatelliteunitneedreplacing.SeeS300SAT
instructionsbelowfordetails.
Lossof informationonthereal timeclockon theRPTU. This willdisable
anyfurtheroperationexcepttoturnthe unitoff.
Note:Ifthismessageappears,theS300 RPTUmustbereturnedto
SystemSensorforrepairandreprogramming.
DisplayedwhentheS300RPTUisswitchedoff.
4: WRITENEWSERVICEDATE
Ifthedetectorhasbeensatisfactorily
serviced,thisfunctionwillwrite thecurrent
datetothe detectorasit’snewservicedate,
otherwisetheS300RPTUwilldisplaya
warningthat thedetectorisdirtyor
contaminated.Ifthedate hasbeen
correctlyprogrammed,the currentdatewill
bedisplayedontheS300 RPTUscreen.
Note:IfEscispressed fromthe
“Connection FailedScreen”, itis
possiblethatanincorrectservicedate
wouldberecorded,howeverthiswillnot
affectthefunctioningofthedetector.
TheIncremental Addressmodewillautomaticallyprogramdetectors
withsequential addresses.Usethe arrowstoselecttheinitialaddress
inasequence, andthenpressOK toprogramthedetector.On
completion,the nextaddresswillautomaticallybeselected,pressOKto
programthe nextdetector.
Important -See warning noteabove concerning use of Esc
button from the “Connection Failed”Screen.
7: S300SATSATELLITE TESTUNIT
TheS300SAT providesaradiolinkforcommunicationsbetweentheS300RPTUtoolanda series300
detectoroverdistancesuptoapproximately4.5m. Itclipsdirectlyintopositiononthedetector,with
theuseof eitherastandardSystem Sensoror,viaan adaptor,NoClimbProductsaccesspoles.
Toprevent crosscommunicationwheremore thanoneunitisinuseon asinglesite,the S300SATand
S300RPTUmaybesettoanaddressfor00to15- SeeRPTUsetupfordetails.
PowerOn/Off
Switch
Power
Indicator
LED
TolocatetheS300SAT,locatetheunit
overthe detector,androtateuntilit
dropsintoplace.Applygentle
pressureto presshome.Toremove
simplypullunitawayfromdetector
BatteryCompartment.
Takes2 xMN1604
(6LR61)9V alkaline
batteries(Not supplied)
Alarm
Sensitivity
-----------
Last
Service Date
DD MMM YYYY
Device's
LEDSetto:
------------
Produced
in:
MMM YYYY
Alarm
Method
------------
Last
ServiceDate
DDMMYY
Attempting
Connection
LINK?...>END
Connection
Failed
**Retry? **
Contaminated
Invalid
OK
OK
Fail
Write4
NEW
ServiceDate
!
I56-1720-003EN

This manual suits for next models

1

Other Honeywell Test Equipment manuals

Honeywell Posi 3 User manual

Honeywell

Honeywell Posi 3 User manual

Honeywell TESTAIR 4 User manual

Honeywell

Honeywell TESTAIR 4 User manual

Honeywell Posi3 USB User manual

Honeywell

Honeywell Posi3 USB User manual

Honeywell Vibrex 2000 User manual

Honeywell

Honeywell Vibrex 2000 User manual

Honeywell MicroDock II User manual

Honeywell

Honeywell MicroDock II User manual

Honeywell TKA295 User manual

Honeywell

Honeywell TKA295 User manual

Honeywell TB7200 Series User manual

Honeywell

Honeywell TB7200 Series User manual

Honeywell HPBLT Technical manual

Honeywell

Honeywell HPBLT Technical manual

Honeywell FG701 User manual

Honeywell

Honeywell FG701 User manual

Honeywell IQ Force Dock User manual

Honeywell

Honeywell IQ Force Dock User manual

Honeywell BW MicroDock II User manual

Honeywell

Honeywell BW MicroDock II User manual

Honeywell Posi3 USB User manual

Honeywell

Honeywell Posi3 USB User manual

Honeywell POL-200-TS User manual

Honeywell

Honeywell POL-200-TS User manual

Honeywell Enraf VITO 762 User manual

Honeywell

Honeywell Enraf VITO 762 User manual

Popular Test Equipment manuals by other brands

EMIT Limit Comparato Instructions for use

EMIT

EMIT Limit Comparato Instructions for use

Secure Care Products 135 user guide

Secure Care Products

Secure Care Products 135 user guide

MTS Sensors MH Series user guide

MTS Sensors

MTS Sensors MH Series user guide

Valhalla Scientific 4176 Operation manual

Valhalla Scientific

Valhalla Scientific 4176 Operation manual

VOLTCRAFT IRS-350 Blackbody operating instructions

VOLTCRAFT

VOLTCRAFT IRS-350 Blackbody operating instructions

Leister VACUUM BOX operating instructions

Leister

Leister VACUUM BOX operating instructions

Martel 19C1977 operating instructions

Martel

Martel 19C1977 operating instructions

Infinite Pasternack PE5CK1019 user manual

Infinite

Infinite Pasternack PE5CK1019 user manual

System Sensor RTS151KEY Installation and maintenance instructions

System Sensor

System Sensor RTS151KEY Installation and maintenance instructions

Atlas Copco STB user guide

Atlas Copco

Atlas Copco STB user guide

Associated 6039 Operator's manual

Associated

Associated 6039 Operator's manual

SW Stahl PROFI Tools 21010L instruction manual

SW Stahl PROFI Tools

SW Stahl PROFI Tools 21010L instruction manual

Keysight Technologies Z Series user guide

Keysight Technologies

Keysight Technologies Z Series user guide

Dickey-John M-3G Operator's manual

Dickey-John

Dickey-John M-3G Operator's manual

GW Instek GDS-1000-U Series Freewave Installation & User Guide

GW Instek

GW Instek GDS-1000-U Series Freewave Installation & User Guide

Transcat CheckMate 400 quick guide

Transcat

Transcat CheckMate 400 quick guide

Teledyne Lecroy 980 user guide

Teledyne Lecroy

Teledyne Lecroy 980 user guide

Apera Instruments Salt20 instruction manual

Apera Instruments

Apera Instruments Salt20 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.