1. Technical Specifications
Installation and Instruction Manual
3. Installation
1. Ceiling (drill hole φ66~68mm)
2. Carefully prise off the cable clamps.
3. Make connections to the pluggable
terminal blocks.
4. Insert plug connectors and secure using
the provided cable clamps, then clip
terminal covers to the base.
5. Fit detection blind (if required) and
desired lens.
6. Clip fascia to body.
7. Bend back springs and insert into ceiling.
Ø 78
75.2
70.5
62
4
5
2
3
1
Ø 66~68mm
* Install blind as required
A B
7
21
6
* Install lens as required
1 2 3
Mechanical Structure & Dimensions
HBIR30/CA HBIR30/CA/R
HBIR30/CA/H HBIR30/CA/RH
PIR Standalone Motion Sensor with Mesh
One DALI Channel Output
2. Download the App
HBIR30/CA-20210811-A0
Subject to change without notice.
Free smartphone App for set-up and commissioning
App Store
Download on the
Protocol
Max 4 dBm
2.4 GHz - 2.483 GHz
Operation frequency
Transmission power
Range (Typical indoor)
10~30m
Stand-by power
Operating voltage
<
0.2W
220~240VAC 50/60Hz
20s
Warming-up
360
O
Ta:-20
OC~+50OC
PIR detection
Sensor principle
Detection angle
Operation temperature
IP20IP rating
4.0
Detection range (Max.)*
HBIR30/CA
Detection range (Max.)*
HBIR30/CA/H
Installation height:15m (forklift)
12m (person)
Detection range (Ø):24m
Installation Height : 6m
Detection Range (Ø) :9m
Installation height:15m (forklift)
12m (person)
Detection range (Ø):40m
Detection range (Max.)*
HBIR30/CA/R
Installation Height : 6m
Detection Range(Ø) :10m
Detection range (Max.)*
HBIR30/CA/RH
EMC standard (EMC)
Safety standard (LVD)
Certification
EN55015, EN61000, EN61547
CB, CE , EMC, LVD, RCM
RED EN300328, EN301489-1,
EN301489-17
EN60669-1, EN60669-2-1
HBIR30/CA-20210811-A0
Subject to change without notice.
4. Detection Pattern & Optional Accessories
Radial (B)
Tangential (A)
2.5m
Mount height
6m
5m
4m
3m
insensitive sensitive insensitive sensitive
A: Tangential movement
Tangential: max. 9m
h = max.6m
A
B: Radial movement
Radial: max. 4m
h = max.6m
B
HBIR30/CA: Low-bay flat lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)
max 64m
2
(Ø = 9m) max 13m
2
(Ø = 4m)
max 13m
2
(Ø = 4m)
max 13m
2
(Ø = 4m)
max 13m
2
(Ø = 4m)
max 13m
2
(Ø = 4m)
max 50m
2
(Ø = 8m)
max 38m
2
(Ø = 7m)
max 38m
2
(Ø = 7m)
max 38m
2
(Ø = 7m)
Optional Accessory --- Ceiling/Surface Mount Box: HA03
1. HBIR30/CA (Low-bay)
Valid Range
Blind Option 1 --- Aisle Detection
Optional Accessory --- Blind Insert for Blocking Certain Detection Angles
75
Ø 94
Blind Option 2 --- 180º Detection
Valid Range
44
66
4.2
HBIR30/CA-20210811-A0
Subject to change without notice.
Radial (B)
Tangential (A)
2.5m
Mount height
6m
5m
4m
3m
HBIR30/CA/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)
max 79m
2
(Ø = 10m)
max 79m
2
(Ø = 10m)
max 64m
2
(Ø = 9m)
max 50m
2
(Ø = 8m)
max 50m
2
(Ø = 8m)
max 20m
2
(Ø = 5m)
max 20m
2
(Ø = 5m)
max 20m
2
(Ø = 5m)
max 20m
2
(Ø = 5m)
max 20m
2
(Ø = 5m)
2. HBIR30/CA/R (Reinforced Low-bay)
A: Tangential movement
Tangential: max. 10m
h = max.6m
A
B: Radial movement
Radial: max. 5m
h = max.6m
B
Optional Accessory --- Ceiling/Surface Mount Box: HA03
Optional Accessory --- Blind Insert for Blocking Certain Detection Angles
75
Ø 94
Valid Range
Blind Option 1 --- Aisle Detection Blind Option 2 --- 180º Detection
Valid Range
insensitive sensitive insensitive sensitive
44
66
4.2
HBIR30/CA-20210811-A0
Subject to change without notice.
Blind Option 1 --- Aisle Detection Blind Option 2 --- 180º Detection
3. HBIR30/CA/H (High-bay)
Tangential: max. 20m
h = max.12m
A
Radial: max. 3m
h = max.12m
B
Radial (B)
Tangential (A)
10m
Mount height
14m
15m
13m
12m
11m max 452m
2
(Ø = 24m)
max 380m
2
(Ø = 22m)
max 452m
2
(Ø = 24m)
max 452m
2
(Ø = 24m)
max 452m
2
(Ø = 24m)
max 452m
2
(Ø = 24m)
max 201m
2
(Ø = 16m)
max 201m
2
(Ø = 16m)
max 201m
2
(Ø = 16m)
max 177m
2
(Ø = 15m)
max 133m
2
(Ø = 13m)
max 113m
2
(Ø = 12m)
A: Tangential movement
Tangential: max. 24m
h = max.15m
A
B: Radial movement
Radial: max. 16m
h = max.15m
B
HBIR30/CA/H: High-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)
Optional Accessory --- Ceiling/Surface Mount Box: HA03
Optional Accessory --- Blind Insert for Blocking Certain Detection Angles
Valid Range Valid Range
Radial (B)
Tangential (A)
2.5m
Mount height
11m
12m
10m
8m
6m max 104m
2
(Ø = 11.5m)
max 50m
2
(Ø = 8m)
max 154m
2
(Ø = 14m)
max 227m
2
(Ø = 17m)
max 269m
2
(Ø = 18.5m)
max 314m
2
(Ø = 20m)
max 7m
2
(Ø = 3m)
max 7m
2
(Ø = 3m)
max 7m
2
(Ø = 3m)
max 7m
2
(Ø = 3m)
max 7m² (Ø = 3m)
max 7m² (Ø = 3m)
A: Tangential movement B: Radial movement
HBIR30/CA/H: High-bay lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-12m)
insensitive sensitive insensitive sensitive
insensitive sensitive insensitive sensitive
75
Ø 94
44
66
4.2
HBIR30/CA-20210811-A0
Subject to change without notice.
Radial (B)
Tangential (A)
10m
Mount height
14m
15m
13m
12m
11m
max 907m
2
(Ø = 34m)
max 962m
2
(Ø = 35m)
max 1075m
2
(Ø = 37m)
max 660m
2
(Ø = 29m)
max 346m
2
(Ø = 21m)
max 1256m
2
(Ø = 40m)
max 154m
2
(Ø = 14m)
max 177m
2
(Ø = 15m)
max 177m
2
(Ø = 15m)
max 154m
2
(Ø = 14m)
max 113m
2
(Ø = 12m)
max 113m
2
(Ø = 12m)
A: Tangential movement
Tangential: max. 40m
h = max.15m
A
B: Radial movement
HBIR30/CA/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC
(Recommended ceiling mount installation height 10m-15m)
Radial: max. 15m
h = max.15m
B
Optional Accessory --- Ceiling/Surface Mount Box: HA03
4. HBIR30/CA/RH (Reinforced High-bay with 3-Pyro)
Tangential: max. 30m
h = max.12m
A
Radial: max. 4m
h = max.12m
B
Radial (B)
Tangential (A)
2.5m
Mount height
11m
12m
10m
8m
6m max 154m
2
(Ø = 14m)
max 38m
2
(Ø = 7m)
max 314m
2
(Ø = 20m)
max 531m
2
(Ø = 26m)
max 615m
2
(Ø = 28m)
max 707m
2
(Ø = 30m)
max 7m
2
(Ø = 3m)
max 7m
2
(Ø = 3m)
max 7m
2
(Ø = 3m)
max 13m
2
(Ø = 4m)
max 13m
2
(Ø = 4m)
max 13m
2
(Ø = 4m)
A: Tangential movement B: Radial movement
HBIR30/CA/RH: Reinforced high-bay lens detection pattern for single person @ Ta = 20OC
(Recommended ceiling mount installation height 2.5m-12m)
insensitive sensitive insensitive sensitive
insensitive sensitive insensitive sensitive
75
Ø 94
44
66
4.2
Wire Preparation
Pluggable screw terminal. It is recommended to make
connections to the terminal before fitting to the sensor.
0.75 - 2.5mm
7-8mm
HBIR30/CA-20210811-A0
Subject to change without notice.
5. Additional Information / Documents
Wiring Diagram
L
N
P N L
Casambi Bluetooth
device
HBIR30/CA
1. To learn more about detailed product features/functions, please refer to www.hytronik.com/download ->knowledge ->Introduction of App Scenes and Product Functions
2. Regarding precautions for PIR Sensors installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->PIR Sensors - Precautions for Product Installation and Operation
3. Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Partnership
4. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy

This manual suits for next models

3

Other Hytronik Accessories manuals

Hytronik HEC7430 User manual

Hytronik

Hytronik HEC7430 User manual

Hytronik HIM30 User manual

Hytronik

Hytronik HIM30 User manual

Hytronik HIM31 Quick guide

Hytronik

Hytronik HIM31 Quick guide

Hytronik DUAL Sense HIM13 Quick guide

Hytronik

Hytronik DUAL Sense HIM13 Quick guide

Hytronik HMW12 Quick guide

Hytronik

Hytronik HMW12 Quick guide

Hytronik HC404VRC-KD User manual

Hytronik

Hytronik HC404VRC-KD User manual

Hytronik HIR23 Quick guide

Hytronik

Hytronik HIR23 Quick guide

Hytronik HIM30 Quick guide

Hytronik

Hytronik HIM30 Quick guide

Hytronik HC038V User manual

Hytronik

Hytronik HC038V User manual

Hytronik HMW32 User manual

Hytronik

Hytronik HMW32 User manual

Hytronik HCD418/DH User manual

Hytronik

Hytronik HCD418/DH User manual

Hytronik HMW24 User manual

Hytronik

Hytronik HMW24 User manual

Hytronik DS05 Quick guide

Hytronik

Hytronik DS05 Quick guide

Hytronik HEC7428 User manual

Hytronik

Hytronik HEC7428 User manual

Hytronik HMW14 Quick guide

Hytronik

Hytronik HMW14 Quick guide

Hytronik HMW30 User manual

Hytronik

Hytronik HMW30 User manual

Hytronik DS05 User manual

Hytronik

Hytronik DS05 User manual

Hytronik HEC7028 User manual

Hytronik

Hytronik HEC7028 User manual

Hytronik HC005S/IR Quick guide

Hytronik

Hytronik HC005S/IR Quick guide

Hytronik HIR23/D2 Quick guide

Hytronik

Hytronik HIR23/D2 Quick guide

Hytronik HMW39/RF Quick guide

Hytronik

Hytronik HMW39/RF Quick guide

Hytronik HMW14 Quick guide

Hytronik

Hytronik HMW14 Quick guide

Hytronik HIR28 User manual

Hytronik

Hytronik HIR28 User manual

Hytronik HC005S/BT Quick guide

Hytronik

Hytronik HC005S/BT Quick guide

Popular Accessories manuals by other brands

Quincy lab 140AE-1 operating manual

Quincy lab

Quincy lab 140AE-1 operating manual

HomePro ZIR000 user manual

HomePro

HomePro ZIR000 user manual

DOL 20SCR Technical user guide

DOL

DOL 20SCR Technical user guide

RAB Smart Task installation manual

RAB

RAB Smart Task installation manual

Kemppi KMS 300 quick guide

Kemppi

Kemppi KMS 300 quick guide

Stearns 57,500 Series Installation and service instructions

Stearns

Stearns 57,500 Series Installation and service instructions

iGuzzini TWILIGHT COPENAGHEN manual

iGuzzini

iGuzzini TWILIGHT COPENAGHEN manual

Adelaide Annexe & Canvas Avan Deluxe installation guide

Adelaide Annexe & Canvas

Adelaide Annexe & Canvas Avan Deluxe installation guide

OHAUS 5000 instruction manual

OHAUS

OHAUS 5000 instruction manual

HOME8 WLS1300 quick start guide

HOME8

HOME8 WLS1300 quick start guide

MAXBOTIX MaxSonar quick start guide

MAXBOTIX

MAXBOTIX MaxSonar quick start guide

ioSmart iSmart56 Installation and user guide

ioSmart

ioSmart iSmart56 Installation and user guide

Focusrite Scarlett 18i8 user guide

Focusrite

Focusrite Scarlett 18i8 user guide

Velleman ED38105 user manual

Velleman

Velleman ED38105 user manual

JumpSport SkyBounce user manual

JumpSport

JumpSport SkyBounce user manual

Prima-Temp PRIYA Instructions for use

Prima-Temp

Prima-Temp PRIYA Instructions for use

Tefcold BC85I-BC85I W user manual

Tefcold

Tefcold BC85I-BC85I W user manual

Vaisala WMS302 user guide

Vaisala

Vaisala WMS302 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.