1. Technical Specifications
Product type RF wireless microwave DALI sensor (tri-level control)
Operating voltage 120~277VAC 50/60Hz
Rated load Maximum 20pcs DALI devices, Maximum 40mA
Power consumption < 1.5W
Detection angle 360o
Detection area (DxH) 10 x 12m (Maximum)
Mounting height 12m (Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 2 ~ 500Lux, Disable
RF transmission distance 30 meters in the open area
RF frequency 868MHz (FSK mode)
Warming up time 20s
Operating temperature -20oC ~ +50oC
IP rating IP65
8
2. Installation
Warnings:
1. Installation must be carried out by a qualified engineer in accordance with local
regulations.
2. Disconnect power supply before installing.
3. Install to a solid surface - vibrations may cause mis-triggering.
4. Ensure environmental conditions are suitable for electronic equipment
Rotary switch
for RF grouping
HC034RF
(
RF receiver
)
RF antenna
Infrared remote receiver
1-10V+
1-10V- L’ NNL
71.5
4.2
37.5
38.3
25
11.8
78.2
87
Installation hole
Installation and Instruction Manual
HIGH BAY RF WIRELESS MICROWAVE DALI SENSOR HMW39/RF + HC034RF
HF
HMW39/RF-20181220-A1
Product type RF wireless receiver
Operating voltage 220-240V 50Hz
Rated load Capacitive:400W; Resistive:1200W
IP rating IP20
4. Functions
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas
it requires a light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time:
motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection
area.
4.1 Tri-level Control (Corridor Function)
15 channels are available for fast grouping via rotary switch on both HMW39/RF and HC034RF.
By simply selecting the same channel on each unit, the grouping is automatically completed.
Noted:channel "0" is not for fast grouping, and sensors can only be grouped by remote control.
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically
whenever artificial light is not required (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light
is sufficient.
4.2 Lux Off Function
The light will flash ONCE rapidly after receiving the command from the remote controller.
Note: There is no load indication (the light will not flash) when button ON/OFF, POWER
100% or POWER 80% is pressed.
4.3 Load Indication
HMW39/RF
HC034RF
3. Rotary Switch for RF grouping
commander receiver
A. Ceiling mount
B. Screw to the Luminaire by conduit
C. Attach to the shade by clamp
91.5
59.3
57.3
47.5
4.1
80.7
75
4.1
66.6
81.5
59.6
66.6
89.9
0.825”
75
64
59.3
57.3
35.2
47.5
84.5
59.3
ぶ
29
163.2
66.6
75
33.7
15
28.5
4.5
ぶ
4.5
59.6
Sensor module
Daylight sensor
LED indicator Infrared receiver
Rotary switch
Angle adjustment
Luminaire clamp
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
Installation rack
8.
Descriptions of the Button Functions
(remote control HRC-11)
HMW39/RF-20181220-A1
10%
30%
75%
50%
Ceiling mounted detection pattern (m)
Ceiling mounted height(m)



6. Wiring Diagram
7. Detection Pattern
HC034RF
L
N
DALI
+
DALI
-
L
N
Brown
LED
Driver
Blue
Red
Black
HMW39/RF
5. RF grouping
Step1
The receiver unit
Beeper is on for 3min
Short press “Learn/Erase” button on RC to the receiver to activate pairing mode, and
the receiver unit will beep once every second for 3min.
Note: up to 30 units can be paired.
Step2
Beeper beeps rapidly beep 3 times in 1s
when RF signal is received successfully
Step3
The receiver unit
Beeper is on
Short press “Transmit” button on RC to the commander, the red indicator on commander
unit will flash for 3 times to send the transmission signal.
The receiver unit
Upon receiving the transmission signal, the indicator on receiver unit will flash quickly then
slowly to indicate the success of pairing. One more short press on “Learn/Erase” button to the
receiver unit to complete the pairing process, the receiver unit will quit the pairing mode.
Erase:
Long press “Learn/Erase” button for 3s to the sensor unit, the indicator rapidly flashes 12
times, all commands that it has received before will be erased.
HRC-11
&
A
II

I
1
3
7
9
6
8
10
11
12
13
14
2
4
5
&
A
II

I
Short press ”Learn
/Erase” button
The commander unit
LED indicator flash 3 times
Short press
”Transmit” button
&
A
I
I

I
&
A
I
I

I
Short press ”Learn
/Erase” button
9. Troubleshooting
YDEMERESUACYDEMERESUACNOITCNUFLAM
The fixture does not light up
The fixture is always on
Check detection area setting
The fixture is on when it should not
Incorrect daylight threshold setting
Continous movement in the detection zone
Sudden change in temperature due to weather (wind, rain, snow)
or air expelled from fans, open windows
Detection zone not targeted
Faulty fixture
No power supply
Adjust daylight threshold setting
Replace fixture
Check power to sensor
Check detection area setting
Adjust zone, change installation site
Detection range [ zone ]
Press buttons in zone to set detection range at 100% / 75%
/ 50% / 10%.
Note: Disabled for HC034RF.
8
8
Scene prog. [ zone ] (One-key-commissioning)
1. Press button “start” to program.
2. Select the buttons in “Detection range”, / “Daylight
hreshold”, “Hold time”, “Stand-by time”, “Stand-by
dimming level” to set all parameters.
3. Press button “Memory” to save all the settings programmed
in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).
For example, to pre-set detection range 100%, daylight
threshold Disable, hold time 5min, stand-by time +∞,
stand-by dimming level 30%, the steps should be as follows:
Press button Start, button 100%, Disable, Shift,
5min, Shift, +∞, 30%, Memory. By pointing to
the sensor unit(s) and pressing Apply, all settings are
passed on the sensor(s).
7
7
7
7
3
3
8
8 9
10
10
11 1312
11 12 13
Permanent ON/OFF [ ]
Press button ,to select permanent ON or permanent OFF mode.
* Press button / to resume automatic operation.
The mode will change to AUTO Mode after power failure.
Power output [ button ]
Press button , the light output shifts between 80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.
button
Auto Mode [ button ]
Brightness +/- [ button ]
Press button to adjust the light brightness between 10%~100% .
Shift [ button ]
RESET[ button ]
Press button , all settings go back to the default setting:
HMW39RF:Detection range:100%, hold time:1min,
stand-by time:5min,stand-by dimming level:20%,
daylight sensor:lux disable, RX 100%
Press button to initiate automatic mode. The sensor starts
working and all settings remain as before the light was switched
ON/OFF.
Note: the function of semi-auto is disabled.
Press button , the LED on the top left corner will flash to indicate
mode selection.
All values / settings in RED are in valid for 20 seconds.
1
2
2
3
3
4
4
5
6
6
5
1
24
Ambient daylight threshold [ button ]
1. Press button Shift, the red LED is on for indication.
2. Press button , the ambient lux level is sampled and set as
the new daylight threshold.
3
10
Dual tech & RF mode [ zone ]
1. HF, PIR, HF+PIR, HF/PIR are disabled.
2. Short press button "Learn/Erase" to activate pairing mode on all
receiver (slave) units to be paired.
Note:up to 30 units can be paired.
3. Short press button "Transmit" at the commander unit(master), the
LED will flash for 3 times to indicate that the transmission signal has
been sent. The receiver units will rapidly beep for 3 times in 1s to
indicate the success of pairing.
4. Long press “Learn/Erase” button for 3s, and the receiver unit
clears all commands it has received before.
5. Press button RX100%, the light on receiver unit is 100% on upon
receiving RF on signal; Press “RX STBY%” button, the light(s) goes
to presset stand-by dimming level directly.
14
10
Daylight threshold [ zone ]
Press buttons in zone to set the daylight sensor at 2Lux /
10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable.
Note: 1. To set daylight sensor at 100Lux / 300 Lux / 500Lux,
press button Shift at first.
2. Disabled for HC034RF.
9
9
3
Stand-by time [ zone ]
Press buttons in zone to set the stand-by period at 0s / 10s /
1min / 5min / 10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control,
100% on when motion detected, and remains at the stand-by
dimming level when no presence is detected after hold-time.
Hold time [ zone ]
Press buttons in zone to set the hold time at 2s / 30s / 1min /
5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press
button Shift at first.
2. 2s is for testing purpose only, stand-by period and
daylight sensor settings are disabled in this mode.
*To exit from Test mode, press button or any button in zone .
3
11
12
12
11
11
2
Stand-by dimming level [ zone ]
Press buttons in zone to set the stand-by dimming level at
10% / 20% / 30% / 50%.
Note.the function of 24h / 12h / 4h / 30s are disabled.
13
13
Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai'gang road south,
Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877
HMW39/RF-20181220-A1
HC034RF: Detection range:100%, hold time:10min,
stand-by time:30min,stand-by dimming level:20%,
daylight sensor:lux disable, RX 100%

This manual suits for next models

1

Other Hytronik Accessories manuals

Hytronik HIM31 Quick guide

Hytronik

Hytronik HIM31 Quick guide

Hytronik HC419VRC/R User manual

Hytronik

Hytronik HC419VRC/R User manual

Hytronik HIR23 Quick guide

Hytronik

Hytronik HIR23 Quick guide

Hytronik HBIR30/CA Quick guide

Hytronik

Hytronik HBIR30/CA Quick guide

Hytronik HCD418/I User manual

Hytronik

Hytronik HCD418/I User manual

Hytronik Dual Sense HIM11 User manual

Hytronik

Hytronik Dual Sense HIM11 User manual

Hytronik HMW23 User manual

Hytronik

Hytronik HMW23 User manual

Hytronik HIR23 Quick guide

Hytronik

Hytronik HIR23 Quick guide

Hytronik HIM38/RF User manual

Hytronik

Hytronik HIM38/RF User manual

Hytronik HMW35 Quick guide

Hytronik

Hytronik HMW35 Quick guide

Hytronik HC403VRC-KD User manual

Hytronik

Hytronik HC403VRC-KD User manual

Hytronik HMW12 Quick guide

Hytronik

Hytronik HMW12 Quick guide

Hytronik HC005S/IR Quick guide

Hytronik

Hytronik HC005S/IR Quick guide

Hytronik HC404VRC-KD User manual

Hytronik

Hytronik HC404VRC-KD User manual

Hytronik HC401SRC/R User manual

Hytronik

Hytronik HC401SRC/R User manual

Hytronik HC009S-KD/I Quick guide

Hytronik

Hytronik HC009S-KD/I Quick guide

Hytronik HMW31 Quick guide

Hytronik

Hytronik HMW31 Quick guide

Hytronik SensorDIM HEC7030 User manual

Hytronik

Hytronik SensorDIM HEC7030 User manual

Hytronik HCD418/DH User manual

Hytronik

Hytronik HCD418/DH User manual

Hytronik HIR32 Quick guide

Hytronik

Hytronik HIR32 Quick guide

Hytronik HMW21 Quick guide

Hytronik

Hytronik HMW21 Quick guide

Hytronik HC019V/DH User manual

Hytronik

Hytronik HC019V/DH User manual

Hytronik HIM16 User manual

Hytronik

Hytronik HIM16 User manual

Hytronik HC419V User manual

Hytronik

Hytronik HC419V User manual

Popular Accessories manuals by other brands

Kuzma 4Point11 instruction manual

Kuzma

Kuzma 4Point11 instruction manual

Costway HB85211 manual

Costway

Costway HB85211 manual

NAPCO GEMC-BSLC-PIR installation instructions

NAPCO

NAPCO GEMC-BSLC-PIR installation instructions

Lion Precision LRD6110 user guide

Lion Precision

Lion Precision LRD6110 user guide

Trust SMART Home START-LINE ACDB-6600AC user manual

Trust

Trust SMART Home START-LINE ACDB-6600AC user manual

GIANTEX HLB-NFI-TF user manual

GIANTEX

GIANTEX HLB-NFI-TF user manual

Greenheck 474750 Installation, operation and maintenance manual

Greenheck

Greenheck 474750 Installation, operation and maintenance manual

PATONA Premium Outdoor 300 manual

PATONA

PATONA Premium Outdoor 300 manual

Honeywell RPW303 Quick manual

Honeywell

Honeywell RPW303 Quick manual

BS Bodensteckdosen Systemtechnik 8802B instruction manual

BS Bodensteckdosen Systemtechnik

BS Bodensteckdosen Systemtechnik 8802B instruction manual

Heat Controller 7602-444 Operation manual

Heat Controller

Heat Controller 7602-444 Operation manual

Alpine KCE-103V owner's manual

Alpine

Alpine KCE-103V owner's manual

Firetide HotPort 5020-M Mesh Node installation guide

Firetide

Firetide HotPort 5020-M Mesh Node installation guide

SSS Siedle NS 511-01 Product information

SSS Siedle

SSS Siedle NS 511-01 Product information

INNOLIVING INN-771 user manual

INNOLIVING

INNOLIVING INN-771 user manual

IFM O2D51 Series operating instructions

IFM

IFM O2D51 Series operating instructions

APG IRU-2 4 Series Operator's manual

APG

APG IRU-2 4 Series Operator's manual

Asterion Push-To Kit quick start guide

Asterion

Asterion Push-To Kit quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.