iNels Elko AirTM-100NB User manual

1 / 4
AirTM-100NB
02-22/2019 Rev.: 0
+
-
CH1
CH2
GND
+ -
3V3/
GND
12
1
4
6
8
6
5
3
7
11
2
9
10
21
8
Click!
3b
5a
+
-
5-12 V DC
5b
+
-
6
+
-
Pulse converter
• The Pulse converter counting quantities of pulses from the energy meters (electric-
ity, water, gas).
• The Pulse converter is designed for use on existing gauges even without impulse
output„S0“ (gauge must support sensing).
• AirTM-100 converts gauge consumption using sensors - LS (LED sensor), WS (mag-
netic sensor for water meter), MS (magnetic sensor) or pulse output.
• For each power meter it is necessary to have one Pulse converter AirTM-100.
• With the wireless solution and NB-IoT communication, it can communicate instant-
ly to your chosen location and be operated immediately.
• Data is sent to the server from which it can be subsequently displayed as a smart-
phone, application, or Cloud notication
• Anti-sabotage: If access to the device is unauthorized, a message is immediately
sent to the server.
• Power supply: 5-12 V DC or 1x 3.6 V batteries SAFT.
• In the case of external power, the battery is automatically disconnected and serves
as backup power.
• Protection degree IP65.
Characteristics
EN
It is done in your Smartphone application. Enter the relevant information on the product
cover into the application.
Set the sensing type (sensor LS, WS, MS or pulse output S0).
Description
1. Tamper
2. NanoSIM slot
3. Programming pins
4. Button SET
5. Setting pins for 3V3 / GND clamp
6. Hole for mounting on the wall Ø
4.3 mm / 0.2”
7. Power terminal
8. Antenna
9. Battery
10. LED indication
11. Sensor connection terminal
12. Bushing M16x1.5 for connecting
cable with max. diameter of 10 mm
Cloud app assignment
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: [email protected]
www.elkoep.com
Made in Czech Republic
General instrucions
Assembly
Internet of Things (IoT)
• The IOT wireless communications category describes the Low Power Wide Area
(LPWA). This technology is designed to provide full-range coverage both inside and
outside buildings, energy-saving and low-cost operation of individual devices. The
NarrowBand network is available to use this standard.
Information about the NarrowBand network
• The network provides two-way communication and the only one to use the licensed
LTE band. Our devices allow band 1 (2100MHz), Band 3 (1800MHz), Band 8 (900MHz),
Band 5 (850MHz), Band 20 (800MHz) and Band 28 (700MHz).
• It uses this SIM card technology for each device.
• The advantage of NarrowBand is the use of already built-up grids, which ensures suf-
cient reception outside and inside buildings.
• For more information on this technology, please visit www.vodafone.cz
Caution for proper operation:
• Products are installed according to the wiring diagram given for each product.
• For proper device functionality, it is necessary to have sucient coverage of the se-
lected network at the installation site.
• At the same time, the device must be registered in the network. Successful device reg-
istration on a given network requires a charge for trac.
• Each network oers dierent tari options - it always depends on the number of mes-
sages you want to send from your device. Information on these taris can be found in
the current version of the ELKO EP pricelist.
1. Using a at-blade screwdriver gradually slide it into one groove and the other in the lid
and swing open the cover.
2. Carefully insert nanoSIM (the device must not be energized when inserting or replacing
nanoSIM!)
3. The product can be attached in two ways:
a) Directly on a at surface by gluing * - apply a suitable adhesive to the bottom of the
base. Place the base in the desired location and let it dry.
b) Using a suitable fastener ** by screwing - drill holes into the base with two holes of
suitable diameter corresponding to the position of the holes in the bottom of the box.
Place the base at the desired location and attach it with suitable bonding material
according to the substrate.
4. Thread the sensor through the bushing and plug it in according to the required function
- see chapter Functions, remove jumper (only after setting the function).
5. Connect the supply voltage (via the power supply the transmitter functionality message
is sent to the application)
a. on the clamp
b. Insert the battery and check the correct location.

2 / 4
1
+
-
2 3
Click!
1.
S0
S0
- +
- +
OC(+)
2.
VCC
Signal
GND
+ OUT
+ -
SN
Function
When the power is connected, the transmitter sends the initial message to the server.
Any unauthorized interference with a device, regardless of the feature set, immediately
sends the message to the server.
1. S0 - pulse counting S0
• Checking the correct pulse readings: after setting the longer push (> 2) function of
the SET button, the LED will be activated, which will ash when counting the pulse.
The LED ashes with a short press or automatically after 5 minutes.
• Measured values send the sensor every 4 hours, or immediately when the 5000 pulse
limit is exceeded.
• Recommended accessories: cable for S0 output
2. Energy measurement - pulse counting from active sensor LS, MS, WS
• Checking the correct pulse readings: after setting the longer push (> 2) function of
the SET button, the LED will be activated, which will ash when counting the pulse.
The LED ashes with a short press or automatically after 5 minutes.
• Measured values send the sensor every 4 hours, or immediately when the 5000 pulse
limit is exceeded.
• Recommended accessories
- LS (LED sensor): is particularly suitable for power meters that support LED pulse
sensing
- MS (magnetic sensor): is particularly suitable for gas meters that support magnetic
sensing.
- WS (magnetic sensor for water meter): it is particularly suitable for water meters that
support magnetic sensing.
• Wiring of LS, MS and WS sensors: (+) brown wire, (-) white wire, (OUT) green wire.
Recommendations for installation
• Ensure the correct location - see Warning.
• Prior to attaching the AirTM-100, check the length of the connected sensor and the lo-
cation of the scanned device.
• The working position is arbitrary but the grommet should not be directed upwards.
• The product does not require special handling and maintenance.
When handling a device unboxed it is important to avoid contact with
liquids. avoid unnecessary contact with the components of the device. Do
not touch the metal objects inside the unit.
Safe handling
Restart
• Open the cover. Power interruption (remove the battery from the device).
• Press SET> 1min.
• Connect power (insert battery). Close the cover.
Replacing batteries
1. Using a at-blade screwdriver gradually slide it into one and then the other groove in
the lid and swing open the cover.
2. Remove the discharged battery and insert a new battery into the holder. Beware of
polarity. Both LEDs will ash 3 times (see device status indication).
3. Replace and snap the front cover.
Notice:
Only use batteries designed for this product correctly inserted in the device! Immediately replace
weak batteries with new ones. Do not use new and used batteries together. If necessary, clean the
battery and contacts prior to using. Avoid battery shorts! Do not dispose of batteries in water or
re. Do not dismantle batteries, do not try to charge them and protect them from extreme heating
- danger of leakage! Upon contact with acid, immediately rinse the aected area with a stream of
water and seek medical attention. Keep batteries out of the reach of children. If it is suspected that
the battery has been swallowed or somehow placed inside the body, consult a doctor immediately.
Give the doctor information about the type of battery (from battery case, device or its manual, etc.)
to determine the chemical composition of the battery. Batteries must be recycled or returned to an
appropriate location (e.g. collection container) in accordance with local legal provisions.
Setting functions:
• Long press SET (> 5s) to enter programming mode.
• The green LED will ash by function (function 1 - 1x, 2 - 2x ...).
• Short (<1s) by pressing the SET button to move upwards in the function selection, press
(> 2 / <5s) longer to go down the function selections.
• Pressing the button (> 5s) long saves the set function and restarts the device.
6. Set the required function (see chapter Function)
7. Fill the jumper onto the adjustment pins (see the Function chapter).
8. Replace and snap the front cover. When closing, the handles have to be snapped to their
original position. To ensure the degree of protection, tighten the grommet carefully.
* The glue must meet the optimal conditions for product placement (inuence of tem-
perature, humidity ...)
** For example, a screw or screw of max. Ø 4 mm can be used as a suitable fastener mate-
rial, 13 mm (distance to the partition in the box) must be added to the required length
for attachment to the substrate.
Device states
When the tamper is pressed, the LED is turned o!
Note:
R... LED red
G... LED green
* 1) Indicates only when you press SET> 2 s (setting mode)
* 2) Planned
power supply (external or battery),
reset unit
Connection to the network
SIM Error - cannot be loaded (SIM
card insertion and rotation check) /
or NB-IoT MODULE error
start unit ok
opening the cover
non contact / contact magnet
test, cancel,„long press“
setting mode (signaling of
measurement / pulses)
impulse LS / MS / WS / S0,
temperature measurement, ...
sending / receiving data
it is necessary to disconnect the power
supply (external or battery), after 60 seconds
after the LED goes out, insert the battery
the battery may be discharged
a discharged battery or a damaged
product
Unit initialization
Start
Search for BTS * 2)
SIM ERR *2)
ERR *2)
Successful network connection * 2)
Measurement
Tamper
Magnet
SET button short press (< 2s)
SET button longer press (> 2s
/ <5s)
Measurement signaling * 1)
Communication
Communication
Other known states
Does not respond to the SET
button
The unit is still in reset
The unit does not respond even
after removal insert the battery
Indication
3 x R + G blinks
2 x ashes R (2xR _ 2xR _ ...)
5 x ashes R (repeatedly)
1 x ashes R
without indication
3 x ashes G
1 x ashes G
2 x ashes G
1 x ashes G
1 x ashes R
any LED lights
still indicates start
without indication

3 / 4
UPLINK
DOWNLINK
UPLINK / DOWNLINK
Note
Graf
Byte 0-14 15 16 17 18 19 20 21
Bit 765432 1 0
S0
IMEI
0x01 -
notication
0x02 -
heartbeat
0x01
Reserved for future use
Tamper:
1 - opened
0 - closed
Battery:
1 - low level
0 - OK
Counter[0] Counter[1] Counter[2] Counter[3]
ENERGY_METERING 0x02 Counter[0] Counter[1] Counter[2] Counter[3]
Function
Function 0 1 2 3 4567
S0 0x01 Heartbeat period 0x00 0x00 Threshold 1H Threshold 1L Threshold 2H Threshold 2L
ENERGY_METERING 0x02 Heartbeat period 0x00 0x00 Threshold 1H Threshold 1L 0x00 0x00
Heartbeat period 0 - 127 [x min]
heartbeat message period
128 - 255 [(x - 127) h]
Threshold 1H 1L 0 - 65535 Input 1 - pulses threshold
Threshold 2H 2L 0 - 65535 Input 2 - pulses threshold
Name Unit Example
Counter [0 – 3] pulse
Counter[0] = 0x01
Counter[1] = 0x02
Counter[2] = 0x03
Counter[3] = 0x04
Counter = 0x01020304
= 16909060 pulses

4 / 4
AirTM-100NB
WarningTechnical parameters
* Values are calculated under ideal conditions and may vary depending on the type of sensor
connected
** Not included in the package
*** Multiple frequency bands of B1 / B3 / B5 / B8 / B20 / B28
**** Depending on network coverage
Read the operating instructions before installing the device and putting it into opera-
tion. Instruction manual is designated for mounting and also for user of the device. It is
always a part of its packing. Installation and connection can be carried out only by a per-
son with adequate professional qualication upon understanding this instruction man-
ual and functions of the device, and while observing all valid regulations. Trouble-free
function of the device also depends on transportation, storing and handling. In case you
notice any sign of damage, deformation, malfunction or missing part, do not install this
device and return it to its seller. It is necessary to treat this product and its parts as elec-
tronic waste after its lifetime is terminated. Before starting installation, make sure that all
wires, connected parts or terminals are de-energized. While mounting and servicing ob-
serve safety regulations, norms, directives and professional, and export regulations for
working with electrical devices. Do not touch parts of the device that are energized – life
threat. To ensure the transmission of the radio signal, make sure that the devices in the
building where the installation is installed are correctly located. Unless otherwise stated,
the devices are not intended for installation in outdoor and damp areas, they must not
be installed in metal switchboards or in plastic cabinets with metal doors - this prevents
transmission of the radio frequency signal. iNELS Air is not recommended for control-
ling life-saving instruments or for controlling hazardous devices such as pumps, heaters
without thermostat, lifts, hoists, etc. - radio frequency transmission may be overshad-
owed by obstruction, interference, transmitter battery may be discharged etc., thereby
disabling the remote control.
1x 3.6V LS 14500 Li-SOCl2AA
1.9 years
3.2 years
3.6 years
3.6 years
5 – 12 V DC (on terminal)
+10 %; -15%
0.2 mW
850 mW
With a message from the server
using setting pins,
SET button, programming cable
message to the server
only when the battery is powered by a message
on the server
button SET
Tamper
IN1, IN2
LS (LED sensor)**
MS, WS (magnetic sensor)**
SO (Contact, open collector)
NB-IoT
LTE Cat NB1***
Approx. 30 km****
200 mW / 23 dBm
-30…+60°C (Pay attention to the operating
temperature of batteries)
-30…+70°C
any
glue / screws
IP65
terminals, wires 0.5 – 1 mm2
terminals, wires 0.5 – 1 mm2
M16 x 1.5 for cable ø max. 10 mm
136 x 62 x 34 mm
100 g (without battery)
Power supply
Battery power:
Battery life by frequency *:
1x 10 minutes
1x 60 minutes
1x 12 hours
1x 24 hours
External power supply:
Supply voltage tolerance:
Standby consumption:
Transmitting power consumption:
Setting
Setting:
Alarm Detection:
Battery status view:
Control
Control:
Digital inputs
Inputs:
Supported sensors for energy
measurements:
Communication
Protocol:
Transmitter frequency:
Range in open space:
Transmission power (max.):
Other parameters
Working temperature:
Storage temperature:
Operating position:
Mounting:
Protection degree:
Connecting External Power:
Connection of the sensor:
Cable gommet:
Dimension:
Weight:
The company ELKO EP, as the manufacturer, is entitled to make technical modications to the product, in the technical specication and product manual, without prior notication.
Other iNels Media Converter manuals

iNels
iNels RFSG-1M User manual

iNels
iNels RFSG-1M User manual

iNels
iNels RFTM-1 User manual

iNels
iNels DAC2-04M User manual

iNels
iNels TI3-60M User manual

iNels
iNels RFSG-1M User manual

iNels
iNels RFIM-20B User manual

iNels
iNels RFSG-1M User manual

iNels
iNels Elko AirTM-100L User manual

iNels
iNels Elko AirTM-100S User manual
Popular Media Converter manuals by other brands

Baumer
Baumer HOG 75 K Installation and operating instructions

Texas Instruments
Texas Instruments LM5181-Q1 user guide

Z3 Technology
Z3 Technology Sitara Z3-AM572x-RPS User instructions

Analytic Systems
Analytic Systems VTC1505 SERIES Installation and operation manual

Nexgrill
Nexgrill 710-0778A Installation Instructions and Use & Care Guide

IXXAT
IXXAT CANlink II Hardware manual