4 / 4 P/N 144420999-2 (EN) • REV B • ISS 28FEB19
10
EN: Installation Sheet
Description
AS502 is an outdoor siren with a beacon. AS522 is an outdoor
siren with two beacons.
Wiring
First, wire the control panel (power down) to the siren as
shown in Figure 9, before connecting the battery. When the
battery is connected for the first time, the siren will give a short
beep. The siren cannot be activated until all inputs (input
power and hold-off voltages) are correct. The siren will be
activated if the input power is removed or drops significantly or
if the siren hold-off voltage is removed.
Specifications
Current
Standby
Operating
40 mA typical
350 mA typical (including beacon)
114 dB at 1 m (3.3 ft.), 85 dB at 3 m (10 ft.)
Battery
Type
Load voltage
Lead acid, BS121N, 12 V, 1.2 Ah
13.6 to 14.2 V
−25 to +55°C without battery)
0 to +40°C (with battery)
Spike suppression
network
* To be connected to an external current limited power supply.
(Advised: 5 A).
Battery removal/disposal
This product may contain one a sealed, rechargeable, BS-type
lead-acid battery. Because removing batteries may affect the
product's configuration settings or trigger an alarm, only a
qualified installer should remove them.
To remove the battery:
1. Make sure that your product settings allow you to open its
cover without starting the tamper alarm.
2. Switch off the mains power, if necessary, and remove the
cover.
3. Disconnect battery connectors.
4. Remove the battery from the holder.
For proper recycling, dispose of all batteries as required by
local ordinances or regulations.
WARNING: Danger of explosion if battery is incorrectly
replaced. Replace only with the same or equivalent type
recommended by the manufacturer.
Regulatory information
PLACED ON THE MARKET BY:
UTC Fire & Security Americas Corporation, Inc.
3211 Progress Drive, Lincolnton, NC, 28092, USA
AUTHORIZED EU REPRESENTATIVE:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
Product warnings
and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE
TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS. UTC FIRE & SECURITY
CANNOT PROVIDE ANY ASSURANCE THAT
ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY “AUTHORIZED
DEALER” OR “AUTHORIZED RESELLER”, IS
PROPERLY TRAINED OR EXPERIENCED TO
CORRECTLY INSTALL FIRE AND SECURITY
RELATED PRODUCTS.
For more information on warranty disclaimers and
product safety information, please check
https://firesecurityproducts.com/policy/product-
warning/ or scan the QR code.
UTC Fire & Security hereby declares that this
device is in compliance with the applicable
requirements and provisions of the Directive
2014/30/EU and/or 2014/35/EU. For more
information see www.utcfireandsecurity.com or
www.interlogix.com.
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as
unsorted municipal waste in the European Union.
For proper recycling, return this product to your
local supplier upon the purchase of equivalent
new equipment, or dispose of it at designated
collection points. For more information see:
www.utcfssecurityproducts.eu/recycle/
Contact information
www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.utcfssecurityproducts.eu