The JA-80S wireless fire detector MHS51505
1
The JA-80S wireless fire detector
This device is designed to detect the presence of fire inside residential or
commercial buildings. It should not be installed in industrial premises. The battery-
powered detector has a built-in local warning siren combined with a red LED
indicator.AlarminformationcanalsobetransferredviaawirelessconnectiontoJA-80
OASiSsystems.
TheJA-80S detectorcombines an optical smoke sensor with a heat sensor. Both
sensors have their outgoing signals processed digitally, resulting in higher false
alarm immunity. The optical sensor works using a light diffusion principle and is
very sensitive to the presence of large-sized particles which are characteristic of
dense smokes. By contrast, the sensor is less sensitive to small-sized particles
which are typical of cleanly burning fires. In particular, the smoke sensor is not
capable of detecting the by-products of cleanly-burning fluids such as alcohols, for
instance. This deficiency is compensated for by the built-in heat sensor. This
sensor provides a slower reaction when compared to the smoke sensor, but is
muchbetterat reactingtofires with rapidlyrisingheat producingonly alittle smoke.
Smoke/heatsensorparticipationisconfigurablebyjumper-settings.
Detection range, detector positioning
The smoke detector must be installed so that any smoke easily drifts into the
detector, such as on the ceiling. It is suitable for residential buildings, but not
suitable for free spaces or an outdoor environment. However, the detector is not
suitable for installation in outdoor spaces or interiors with an extremely high ceiling
(more than 5 m) where fire by-products would not reach the detector position.
The detector must always be placed in the section leading to the exit of the
apartment (escape route), see Figure 1. If the apartment has a floor area greater
than 150 m2, an additional detector is required in the apartment, see Fig.2.
An apartment block must be equipped with a detector in each apartment. In
family houses and residential flats or maisonettes a detector must also be placed
at the highest point of common hallways or spaces (escape routes), see Fig.3.
KITCHEN
MINIMUMSECURITY
FORMORESECURITY
LIVINGROOM
BEDROOM
BEDROOMS
Fig.1
BEDROOMS
BEDROOM
BEDROOM
LIVINGROOM
KITCHEN
MINIMUMSECURITY
FORMORESECURITY
Fig.2
It is recommended to place
additional detectors in rooms where
people sleep or in rooms with an
increased risk of fire, see Fig.2.
Positioning on level ceilings
Place the detector in the center of
the room, as level as possible.
Detectors must not be recessed into
the ceiling (worse conditions for the
spread of smoke). Never place the
detector in a room corner (ensure a
distance of at least 0.5 meters from
the corner), see Fig 4.
BED
ROOM
KITCHEN
MINIMUMSECURITY
BED
ROOM
BED
ROOM
Fig.3
Installation on sloping ceilings
If the ceiling is not suitable for mounting on a level surface (e.g. a room under a
roof ridge), the detector can be installed as in Figure 5.
0.5m
CEILING
BESTLOCATION
(CENTREOFCEILING)
ACCEPTABLE
LOCATION
Fig.4
90cm
Fig.5
Walls, partitions, barriers and lattice ceilings
The JA-80S must not be installed closer than 0.5 m from any wall or partition. A
narrow room with a width of less than 1.2m requires the detector(s) to be placed at a
distance of at least one third of the room’s width away. In the case of separating walls
(partitions, warehouse objects) which do not reach the ceiling, the space is considered
to be fully separated if the gap between the top of the separating wall and the
ceiling does not exceed 0.3 m. A free space of at least 0.5m is required under the
detector. Irregularities in ceiling shape which do not exceed 5% of ceiling height are
consideredinsignificant–the ceilingcan be regarded as beingevenandlimitsfrom
the table are applicable. However, any irregularity (including beams) exceeding 5%
of the ceiling height is considered to be a wall with the consequences stated
above.
Ventilation and air circulation
The detectors must not be installed directly by a fresh air inlet, e.g. air
conditioning vents. In the case of air being supplied through a perforated ceiling, each
detectormust beplaced so that no perforation hole occurswithin 0.6m of the detector.
Avoid installing the detector in the following locations:
Placeswithpoorair circulation(niches, corners, apexesof A-shapedroofs).
Placesexposedto dust,cigarettesmokeor steam.
Places with over-intense air circulation (close to ventilators, heat sources or air
conditioningoutlets).
Kitchens and other cooking places (because steam, smoke or oily
fumes can reduce detector sensitivity).
Beside lights (electrical interference can cause a false alarm)
Areas with lots of small insects
Caution: Most false alarms are due to detector misallocation
See CEN/TS 54-14 standards for detailed installation guidelines.
Installation
1. Open the detector by turning the rear cover to the left and remove the battery
2. Screw the rear cover onto the desired location
3. Set the required function using the jumpers –see the table below
4. Pleasereadthereceiving device(controlpanel)installationmanualbefore youconnectthe
battery(removetheinsulationtape)andsetthecontrolpaneltoenrollmentmode
5. Whenthebatteryisconnected,thedetectorsendsasignaltoconnecttothesystem
6. After installing the detector, allow approx. 20 seconds for stabilisation. This
period is indicated by the LED being continuously lit and is followed by an
auto-test. Successful performance of the auto-test is confirmed acoustically.
o
p
e
n
c
l
o
s
e
LITHIUM
3,6V AA
TEST
1
1
ON
INSTANT alarmmode
3
OFF
Smoke(EN 14064)
or heat(EN 54-5)
OFF
FIRE alarm mode
4
OFF
2
ON
Memory ON
3
ON
Only smoke (EN 14604)
(heat indifferent)
OFF
Memory OFF
4
OFF
11 2 3 4
ON
OFF
3
OFF
Only heat (EN 54-5)
(smoke indifferent)
4
ON
3
ON
Smoke and heat
(both simultaneously)
4
ON
Testing the detector is automatically performed up to 10 secs after
battery insertion. New settings are saved directly afterwards.
J1: The FIRE / INST alarm mode jumper sets the reaction of the system. FIRE
= alarm is triggered even if the system is disarmed while INST = alarm is
triggered only in an armed system. The FIRE / INST jumper only has an effect if
the detector has a natural reaction assigned to its address in the Oasis control
panel. It also has no effect when used with a UC-8x or AC-8x receiver.
Warning: In the INST position, while the system is disarmed, it is not
protecting against fire. This setting also fully disables the optical and
acoustic indication on the detector itself.
J2: Alarm memory: If the event memory is ON at the time of alarm, alarm LED
indication continues even if normal conditions are restored. The indication can be
stopped by pressing the button (indication is valid only for FIRE settings).
J3 and J4: Smoke/ heat sensor participation
Optical smoke sensor: Smoke entry into the detector is indicated as a pre-alarm
state by the LED flashing. If the smoke threshold density is exceeded, a siren
sound is generated (indication is valid only for FIRE settings).
Heat sensor: indication logic is equal to that of the smoke sensor.
Whenever the detector cover is opened, a tamper signal is sent.
Testing the detector
The functioning of the detector can be tested by pressing and holding the test
button (e.g. for 1 sec). This activates the siren and the LED flashes (LED only if
The JA-80S wireless fire detector MHS51505
2
the fire reaction is set). The strength and quality of detector signals can be
measured by the control panel in Service mode. During testing by the test button,
the detector transmits signals which can not trigger fire alarms in the control
panel.
Warning: Never start a fire in a building to test the detector. Instead, use
smoke-simulating aerosols for realistic testing.
Silencing the siren during an alarm
During a fire alarm, the detector LED flashes 2 times briefly and the built-in siren sounds
(atahigher intensitythan duringa test).Undertheseconditionsthesirencanbe silencedby
pressing the test button for approx. 3 sec. The LED will continue to flash until the
smoke clears from the room (indicationis validonlyforFIREsettings).
However,ifnormalconditionsarenotrestored within approx.10minutes(thesmokedoes
notclearfrom theroomorthetemperaturedoesnotdrop),thesirenre-activates.
Fault indication
The detector performs regular self-testing. If a fault is detected in the detector,
its LED will start to flash rapidly. In such a case, disconnect the battery from the
detector, and after about 20 secs, re-connect it. If after a minute the LED still
flashes, then send the detector off for repair.
Battery replacement
The detector monitors its battery voltage and if too low, a transmission is sent to
the control panel to inform the installer or user. The detector continues to function
but with a short LED flash every minute. Battery replacement should not be delayed
by more than two weeks. This should be done by a qualified technician with the
control panel in Service mode.
After battery replacement, test the functioning of the detector using its test button.
Expired batteries should not be thrown into the garbage, but disposed of according
to local regulations.
Removing the detector from the system
If a detector is removed, the control panel announces the removal. The detector
has to be deleted in the control panel before intentional removal.
Technical parameters
Voltage: Lithium battery type or LST14500 (AA 3.6V / 2,4 Ah)
Typical battery lifetime approx. 3 years
Communication band 868,5 MHz, Oasis protocol
Smoke detection optical, scattered light
Smoke sensor sensitivity m = 0.11 - 0.13 dB/m to EN 54-7
Temperature detection class A2 to EN 54-5
Fire-alarm temperature +60 °C to + 70 °C
Acoustic power of the built-in siren 80 dB/m
Operational temperature range -10°C to +80 °C
Dimensions, weight diameter: 126 mm, height: 65 mm, 200 g
Complies with EN 54-7, EN 54-5 class A2, EN 54-25,
ETSI EN 300220, EN 50130-4, EN 55022, EN 60950-1
Can be operated according to ERC REC 70-03
1293-CPD-0263
JABLOTRON ALARMS a.s. hereby declares that the JA-80S is in compliance
with the essential requirements and other relevant provisions of Directives
1999/5/EC and 1989/106/EC. The original of the conformity assessment can be
found at www.jablotron.com, Technical support section.
Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer or directly
to the producer after use.

Other jablotron Security Sensor manuals

jablotron JA-160PC User manual

jablotron

jablotron JA-160PC User manual

jablotron JA-159P User manual

jablotron

jablotron JA-159P User manual

jablotron JA-152P User manual

jablotron

jablotron JA-152P User manual

jablotron LARGO JS-20 User manual

jablotron

jablotron LARGO JS-20 User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-85P User manual

jablotron

jablotron JA-85P User manual

jablotron JA-160PC User manual

jablotron

jablotron JA-160PC User manual

jablotron JA-160PC User manual

jablotron

jablotron JA-160PC User manual

jablotron CA-550 User manual

jablotron

jablotron CA-550 User manual

jablotron JA-60V User manual

jablotron

jablotron JA-60V User manual

jablotron JA-115P User manual

jablotron

jablotron JA-115P User manual

jablotron JA-158P User manual

jablotron

jablotron JA-158P User manual

jablotron JA-181M User manual

jablotron

jablotron JA-181M User manual

jablotron JA-83P User manual

jablotron

jablotron JA-83P User manual

jablotron JA-159P User manual

jablotron

jablotron JA-159P User manual

jablotron JA-155P User manual

jablotron

jablotron JA-155P User manual

jablotron JA-80IR User manual

jablotron

jablotron JA-80IR User manual

jablotron JA-60V User manual

jablotron

jablotron JA-60V User manual

jablotron JA-187P User manual

jablotron

jablotron JA-187P User manual

jablotron JA-60P User manual

jablotron

jablotron JA-60P User manual

jablotron JA-150P User manual

jablotron

jablotron JA-150P User manual

jablotron JA-181M User manual

jablotron

jablotron JA-181M User manual

jablotron JA-111ST User manual

jablotron

jablotron JA-111ST User manual

jablotron GS-133 User manual

jablotron

jablotron GS-133 User manual

Popular Security Sensor manuals by other brands

IOTA ICE-80 instruction manual

IOTA

IOTA ICE-80 instruction manual

System Sensor 8100A FAAST Installation and maintenance instructions

System Sensor

System Sensor 8100A FAAST Installation and maintenance instructions

Tatsuta Electric Wire & Cable AD-AS-1LCM-A Operation manual

Tatsuta Electric Wire & Cable

Tatsuta Electric Wire & Cable AD-AS-1LCM-A Operation manual

EMX Industries VMD202 quick start guide

EMX Industries

EMX Industries VMD202 quick start guide

BW Technologies GasAlertMicro 3 user manual

BW Technologies

BW Technologies GasAlertMicro 3 user manual

PCB Piezotronics W138A06 Installation and operating manual

PCB Piezotronics

PCB Piezotronics W138A06 Installation and operating manual

Dodotronic Batango user guide

Dodotronic

Dodotronic Batango user guide

NA-DE 01000 quick start guide

NA-DE

NA-DE 01000 quick start guide

SORHEA SOLARIS installation manual

SORHEA

SORHEA SOLARIS installation manual

CAMP Rapida manual

CAMP

CAMP Rapida manual

iPROTECT 1217 manual

iPROTECT

iPROTECT 1217 manual

Sebury F1 user manual

Sebury

Sebury F1 user manual

Clas Ohlson Dropp-Stop 600 instruction manual

Clas Ohlson

Clas Ohlson Dropp-Stop 600 instruction manual

ALGE-Timing RLS1nd manual

ALGE-Timing

ALGE-Timing RLS1nd manual

iNels RFMD-100 quick start guide

iNels

iNels RFMD-100 quick start guide

Burster 8655 Operation manual

Burster

Burster 8655 Operation manual

Pyronix XDL12TT-WB installation manual

Pyronix

Pyronix XDL12TT-WB installation manual

Jung PMK 360 WW operating instructions

Jung

Jung PMK 360 WW operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.