Application
The JOVENTA SILENCE electric
damper-actuator series have been
developed to operate small and
medium air dampers in ventilation
and air conditioning systems.
The compact design and universal
adapter fitted with limitation of
rotation angle make this JOVENTA
actuator highly versatile.
Key features
2- or 3-point control
Load-independent running time
Up to 5 actuators in parallel
operation possible
Plug-in terminal block connection
Simple direct mounting with
universal adapter for fitting to
Ø6-mm to 16-mm shaft or with
Z01DN adapter kit for 8,10,11
and 12 mm square shaft.
45-mm min shaft length
Selectable direction of rotation
Limitation of rotation angle
Manual release button
2 adjustable auxiliary switches
See back page for settings
Automatic shut-off at end
position (overload switch)
Energy saving at end positions
Actuators available
with 1m halogen-free cable
Customized versions available
Devices meet
CE requirements
SILENCE
Nomenclature/Specification/Technical data
DAN1.N AC/DC24V
DAN1.SN AC/DC24V with 2 auxiliary switches
DAN2.N AC230V
DAN2.SN AC230V with 2 auxiliary switches
. . . . . . .K with 1 m halogen-free cable
Actuator DAN1.(S)N DAN2.(S)N
Torque 4 Nm 4 Nm
Damper area* 0.8 m20.8 m2
Running time 35 s 35 s
Supply voltage AC/DC24V AC230V
Frequency 50-60 Hz 50-60 Hz
Power consumption
- operating 2.5 W 4.0 W
- At end position 0.75 W 3.0 W
Dimensioning 4.1VA/2A@2ms 5.0VA/0.1A@2ms
Weight 0.9 kg 0.9 kg
Control signal 2-point and 3-point
Position signal None
Angle of rotation / working range 90° (93° mech.)
Angle of rotation / limitation 0°...30° and 90°...60°
Service lifetime 60,000 rotations
Auxiliary switches 3(1.5)A, AC230V
Setting range / adjustable 5°...85° < infinity
Noise level 40 d B (A)
Protection class II
Degree of protection IP 50
Cable aperture connection M16 x 1.5
Mode of action Type 1
Ambient conditions
- Operating temperature –20...+50°C / IEC 721-3-3
- Storage temperature –30...+60°C / IEC 721-3-2
- Humidity 5...95% r.F.
Service Maintenance free
Standards Mechanics EN 60 529 / EN 60 730-2-14
Electronics EN 60 730-2-14
EMC Emissions EN 50 081-1:92 / IEC 61 000-6-3:96
EMC Immunity EN 50 082-2:95 / IEC 61 000-6-2:99
2- and 3-POINT Actuators 2.11
*Caution: Please note damper manufacturer’s information concerning the open/close torque.Subject to design modifications without notice.