
TK30/TK60
10
The automatic circuit breaker
of the building’s protection
fuse interrupts the mains
supply to the dehumidier.
5The building’s fuse protection
is too weak. The building’s fuse fuse
protection has to be checked
and/or be changed.
6There is an electrical pro-
blem in the dehumidier’s
electric circuit.
The power supply of the de-
humidier must be interrup-
ted (pull o the mains plug)!
The defect must be repaired
by an authorized service
center.
The unit’s fan is not working. 7The dehumidier is defros-
ting. The dehumidier will nor-
mally start working again
automatically after a couple
of minutes. If not, take the
unit to an authorized service
center (do not try to repair it
by yourself!).
The noise level is louder than
usually. 8The lter holding device is
not put on properly. Put on the lter holding de-
vice properly.
9One or more screws of the
casing are not tightened
properly.
Tighten the loose screw(s)
properly.
The dehumidier is not
working. 10 The dehumidier is not swit-
ched on. Switch the dehumidier on.
11 The degree of humidity set
at the hygrostat has been
reached.
The dehumidier will turn on
again automatically when
the degree of humidity set
on the hygrostat has been
exceeded.
12 The drip pan is full. Take o the drip pan, empty
it and remount it.
13 The dehumidier is defective. An authorized service center
has to repair the defect.
The dehumidier creates
too much ice at the cooling
register (evaporator), a block
of ice is created.
14 The room temperature was/
is temporarily or always
below +30° C.
Put the dehumidier into a
room with at least +10° C
and wait until the ice has
completely defrosted. Then
switch the unit on and let it
run for about 3 hours. If ice is
created again, contact your
supplier. In general make
sure that the unit is only used
in rooms with at least +5° C
room temperature. Ice may
also be created if the unit is
stored in a colder room and
then switched on immedia-
tely.
15 Maybe the automatic defros-
ting is defective. Contact your supplier.