CONNECT LOW VOLTAGESTEP 3
Page 6
Occupancy Sensor Disabled /
Emergency Input
A
Label: OCC DISABLE / EMERGENCY
Set by DIP Switch: Block 1 Number 1
This is a +24V input signal. Function can be set to
either mode exclusively.
Occupancy Disable Mode
When the input goes high (+24V) the Power Pack
will disable the Occupancy Sensor input and there
will be no change in the current state. When the
input signal is removed, the Occupancy Sensor will
return to the normal mode.
Emergency Mode
Emergency mode is triggered when the emergency
input is connected to the common. When the signal
is received, the Power Pack will turn on all zones
by turning on all relays and raising any 0 – 10V
outputs to 10 V. The Power Pack zones will remain
fully illuminated until the Emergency signal is
removed.
Photocell Disable / Force Off Input
Label: PC DISABLE / FORCE OFF
Set by DIP Switch: Block 1 Number 2
This is a +24V input signal. Function can be set to
either mode exclusively.
Photocell Disable Mode
When the input goes high (+24V) the Power Pack
will disable the Photocell input, along with daylight
operation, and there will be no change in the
current state. The On switch functionality, when the
photocell is disabled, turns lights on to the
maximum level. When the input signal is removed,
the Photocell will return to the normal mode.
Force Off Mode
When the input goes high (+24V) the Power Pack
will turn off all zones. The Power Pack zones will
remain fully off until the Force Off signal is
removed.
B
Time Clock Input
Label: CLOCK
This signal will originate from a supervisory time
clock system and is a +24V input signal. When the
input goes high (+24V) the Power Pack will turn off
all zones. If the Blink Warn function has been
configured, the Power Pack will trigger the Blink
Warn cycle. If a switch is used to turn on the lights
during a period that the time clock has the lights
off, the system will go into a Blink Warn override
mode.
If both the Occupancy Sensor and the Time Clock
inputs are used, an active (+24 VDC) signal at the
Time Clock input only has the affect of changing
an Auto On configuration to a Manual On.
CLoad Shed Input
Label: SHED
This signal would originate from an energy
management system and is a +24V input signal.
When the input goes high (+24V) the Power Pack
will reduce the output load levels based upon the
position of the Shed trim pot.
In the event that you are in daylighting mode and
less artificial light is required to meet the target than
is required by load shed, the lights will remain at the
lower lighting level – meeting the target.
D