manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Leviton
  6. •
  7. Surge Protector
  8. •
  9. Leviton R Series User manual

Leviton R Series User manual

R, P, B, and M Series
Surge Protective Devices
INSTALLATION INSTRUCTIONS ENGLISH
PK-A3478-10-00-4A
WARNINGS:
• HAZARD OF ELECTROCUTION AND SHOCK. CAREFULLY READ AND FOLLOW INSTRUCTIONS.
• Only electricians should install or service Surge Protective Devices (SPDs).
• Hazardous voltages exist within SPDs.
• SPDs should never be installed or serviced when energized.
• Use appropriate safety precautions including Personal Protection Equipment.
• Failure to follow these instructions can result in death, serious injury, and/or equipment damage.
• Read this manual in its entirety prior to installing.
Bonding and Grounding Hazard
Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electric Code (NEC®)
and all applicable codes. During installation into an electrical system the SPD must not be energized until the electrical system is completely
installed, inspected and tested. All conductors must be connected and functional including the neutral (if required).
The voltage rating of the SPD and system must be veried before energizing the SPD. Failure to follow these guidelines can lead to abnormally
high voltages at the SPD. This may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor
in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC.
Do Not Hi-Pot Test SPDs
Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage such as high-potential insulation testing, or
any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage
(MCOV) must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also
be disconnected prior to performing high-potential testing. Failure to disconnect the SPD and associated components during elevated voltage
testing will damage the SPD and will void the warranty.
CAUTIONS:
SPDs on Ungrounded Systems
Ungrounded systems are inherently unstable and can produce excessively high line-to-ground voltages during certain fault conditions. During
these fault conditions, any electrical equipment, including an SPD, may be subjected to voltages which exceed their designated ratings. An SPD
designated specically for ungrounded systems should be used.
Unpacking and Preliminary Inspection
Inspect the entire shipping container for damage or signs of mishandling. Remove the packing materials and further inspect the unit for any
obvious shipping damages. If any damage was found, and is a result of shipping or handling, immediately le a claim with the shipping company
and forward a copy to Leviton at industrial@leviton.com.
Storage Environment
This SPD should be stored in a clean, dry environment. Storage temperature range is -49°F to 140°F (-45°C to 60°C). Avoid exposure to
high condensation.
© 2023 Leviton Mfg. Co., Inc.
1
Pre-Installation
Operating Environment
Series R, P, and B are NEMA 4X enclosures and Series M is NEMA 4 enclosure. Before installing, ensure that your enclosure type and
application are appropriate with regard to moisture, dirt, excessive dust, ammable materials or atmospheres, corrosive vapors, etc. Please
consult factory if enclosure needs to be changed. The R and P Series are designed to work in a temperature range of -31°F to +185°F (-35°C to
+85°C), and the B and M Series -40°F to +185°F (-40°C to +85°C) with a relative humidity of 0% to 95% (noncondensing). Excessive temperature
may inadvertently operate internal thermal over-temperature protectors.
Line Side versus Load Side Installation
The R and P Series SPDs are Type 1, and the B and M Series SPDs are Type 2, as dened in UL 1449 and the National Electrical Code. Type 1
SPDs are intended to be installed on the line side of the service disconnect overcurrent device but may also be installed on the load side. Type 2
SPDs are intended to be installed on the load side of the service disconnect overcurrent device.
NOTE: Devices with UL1293 Filtering are qualied to the same standards, but can only be installed as Type 2 devices per UL specication.
Audible Noise
SPD background noise is negligible or non-existent, and does not restrict the location of installation.
4
For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only)
www.leviton.com
FOR CANADA ONLY:
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada
ULC to the attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone
at 1-800-405-5320.
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benet of anyone else that this product at the time of its sale by Leviton is free
of defects in materials and workmanship under normal and proper use for ve years from the purchase date. Leviton’s only obligation is to correct
such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty excludes and
there is disclaimed liability for labor for removal of this product or reinstallation.This warranty is void if this product is installed improperly or in an
improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not
in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and tness
for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including
merchantability and tness for a particular purpose, is limited to ve years.Leviton is not liable for incidental, indirect,special,or consequential
damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or prots or delay or failure to perform this
warranty obligation.The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
FCC STATEMENT:
This device complies with Part 15 of the FCC Rules and ISED License-exempt RSS standard(s). Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference
that may cause undesired operation. Changes or modications not expressly approved by Leviton could void the user’s authority to operate
the equipment.
These limits are designed to provide reasonable protection against harmful interference in a commercial installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference
to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the
following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
-
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This Class A digital apparatus complies with Canadian CAN ICES-3(A)/NMB-3(A).
FCC SUPPLIER’S DECLARATION OF CONFORMITY:
Models R, B, P, and M Series Surge Protective Devices are sold by Leviton Manufacturing Inc. 201 N Service Rd, Melville, NY 11747. This device
complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including interference that may cause undesired operation.
TRADEMARK DISCLAIMER:
Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only,
are/may be the trademarks of their respective owners; such use is not meant to imply affiliation, sponsorship, or endorsement.
WEB VERSION
2 3
Pre-Installation Continued
Lead Lengths and Maximizing SPD Performance
SPDs must be located as close to the circuit as possible to minimize parasitic losses. Use the shortest and straightest possible leads for pre-plan
installations and ensure that nearest breaker positions are used. If new construction, adjust breaker locations as appropriate. When longer leads
are unavoidable, gently twist leads together (one to two twists per foot), or tie-wrap leads together.
Voltage Rating
Before installing the SPD, verify that it has the same voltage rating as the power distribution system. Compare the SPDs nameplate voltage or
model number and ensure that SPD conguration matches the intended power source.
Circuit Breaker Connected
When connected on the load side of the main disconnect, we suggest connecting via a circuit breaker. The circuit breaker is the intended
disconnect switch and provides short circuit protection to the connecting conductors. These SPDs have internal overload protection elements
within the product. These SPDs have demonstrated 200kA Short Circuit Current Ratings (SCCRs).
Operating Environment Continued
System Grounding
An equipment grounding conductor must be used on all electrical circuits connected to the SPD. For the best performance, use a single point
ground system where the service entrance grounding electrode system is connected to and bonded to all other available electrodes, building steel,
metal water pipes, driven rods, etc. (For reference see, IEEE Std 142-2007.) For sensitive electronics and computer systems, we recommend that
the ground impedance measurement be as low as possible.
When metallic raceway is used as an additional grounding conductor, an insulated grounding conductor should be run inside the raceway.
Adequate electrical continuity must be maintained at all raceway connections. A separate isolated ground for the SPD is NOT recommended.
Proper equipment connections to the grounding system and ground grid continuity should be veried via inspections and testing on a regular
basis, as part of a comprehensive electrical maintenance program. On 4-Wire Power Systems, neutral to ground bonding (Main Bonding Jumper)
must be installed per the NEC. Failure to do so, WILL damage SPDs.
Retrot into Existing Panel with No Available Breaker Positions
Follow all applicable codes: Consider consolidating loads that might free breaker positions. A 10 ft tap rule in NEC 240.21(B)(1), allows you to
tap the bus as long as the tap conductors are rated at least 10% of the ampacity of the panel. In the case where the ampacity of the panel is larger
than the wires of the SPD, consider tapping the bus per NEC 240.21(B)(1) and running appropriate size conductors to a safety switch fused to
30A.
Mount the SPD immediately adjacent to the safety switch.
Installation
Pre-Plan Your Installation
• Meet all National and Local codes (NEC Article 285 addresses SPDs).
• Mount SPD as close to panel or equipment as possible to keep leads short.
• Ensure leads are as short and straight as possible, including neutral and ground.
• Consider breaker positions that are closest to the SPD and the panel’s neutral and ground wires.
• Suggested breaker size for the R, P, and B Series is 20A, and 30A for the M Series.
• Make sure system is grounded per NEC and clear of faults before energizing SPD.
BLACK
WHITE
GREEN
BLACK
BROWN
GROUND
NEUTRAL
LINES
Connect to Alarming
Connect to Mains
Common
NC (Normally Closed)
NO (Normally Open)
WHITE
Installation Instructions
1. Use a voltmeter to check all voltages to ensure correct SPD.
2. If SPD has Dry Contact, pre-plan its installation.
3. Turn OFF power at panel. Conrm panel is de-energized.
4. Identify connection and breaker location and SPD location.
5. Make sure leads are short.
6. Remove an appropriately-sized knockout from panel.
7. Mount SPD. Connect to equipment using an approved wiring method, including seals appropriate for the enclosure rating.
8. Connect conductors as appropriate – short and straight as possible.
NOTE: Hi-Legs are Phase B (ORANGE).
9. Label or mark conductors, as appropriate.
Energized: BLACK
Neutral: WHITE
Ground: GREEN
Hi-Leg (Delta units only): ORANGE
10. Make sure system is bonded per NEC and is clear of hazards or faults before energizing. (N-G bonding, not per NEC, will fail SPDs.)
11. Energize and conrm proper operation of indicators and/or options. If Audible Alarm cycles, turn OFF power immediately and contact Leviton
at 1-800-824-3005 for help.
Operation
LED Operation
• When the LEDs are GREEN, complete protection is present.
• Upon a MOV stack failure, the LED that corresponds to the failed mode turns OFF.
Audible Alarm
Similar to the LEDs, the audible alarm will sound upon a suppression element failure. The alarm can be silenced only by removing power to the
SPD via the breaker. Removing power leaves the system unprotected.
Dry Contacts
Three, #22 AWG wires are included through the nipple as dry contacts. Dry contacts change state when any suppression element reaches end of
life, including the loss of power. Any change in status can be monitored elsewhere via the dry contacts.
NOTES:
• Dry contacts are designed for low-voltage or control signals only.
• Maximum switching current is 2A.
• Maximum switching voltage is 240V AC.
• Higher energy applications require additional relay implementation outside the SPD.
• WHITE is Common, BLACK is Normally Open, and BROWN is Normally Closed.
• If the dry contacts are not used, insulate the lead ends, coil, and secure.
Maintenance
SPDs require minimal maintenance. We recommend periodic inspection of diagnostic indicators to ensure proper operation. We also recommend
keeping the SPD clean, as appropriate.
Troubleshooting
Please contact Leviton for any service-related issues at 1-800-824-3005.
WEB VERSION

This manual suits for next models

7

Other Leviton Surge Protector manuals

Leviton 51120-1 User manual

Leviton

Leviton 51120-1 User manual

Leviton 51015-WM User manual

Leviton

Leviton 51015-WM User manual

Leviton 52412-DS3 User manual

Leviton

Leviton 52412-DS3 User manual

Leviton 50240-MSA User manual

Leviton

Leviton 50240-MSA User manual

Leviton 5280 User manual

Leviton

Leviton 5280 User manual

Leviton 5480-IG User manual

Leviton

Leviton 5480-IG User manual

Leviton 3803-MOD User manual

Leviton

Leviton 3803-MOD User manual

Leviton 51020-WMT User manual

Leviton

Leviton 51020-WMT User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton 51240-WM User manual

Leviton

Leviton 51240-WM User manual

Leviton 52000 Series User manual

Leviton

Leviton 52000 Series User manual

Leviton 47120-7 User manual

Leviton

Leviton 47120-7 User manual

Leviton 51005-WM User manual

Leviton

Leviton 51005-WM User manual

Leviton 3862-CON User manual

Leviton

Leviton 3862-CON User manual

Leviton 3812 User manual

Leviton

Leviton 3812 User manual

Leviton 32120-DY3 User manual

Leviton

Leviton 32120-DY3 User manual

Leviton 51005-WM User manual

Leviton

Leviton 51005-WM User manual

Leviton 37120-7 User manual

Leviton

Leviton 37120-7 User manual

Leviton 51110-PTC User manual

Leviton

Leviton 51110-PTC User manual

Leviton 3880-DIN User manual

Leviton

Leviton 3880-DIN User manual

Leviton 51120-3R User manual

Leviton

Leviton 51120-3R User manual

Leviton 5480 User manual

Leviton

Leviton 5480 User manual

Leviton SmartlockPro GSIA2 User manual

Leviton

Leviton SmartlockPro GSIA2 User manual

Popular Surge Protector manuals by other brands

Patton electronics 546 user manual

Patton electronics

Patton electronics 546 user manual

Panamax MAX 4310 instructions

Panamax

Panamax MAX 4310 instructions

MCG Surge Protection XT Series installation instructions

MCG Surge Protection

MCG Surge Protection XT Series installation instructions

Nivus DataPro-TAE/NFN-aP operating instructions

Nivus

Nivus DataPro-TAE/NFN-aP operating instructions

CPT PSM2 Series installation instructions

CPT

CPT PSM2 Series installation instructions

Transtector APEX Series installation manual

Transtector

Transtector APEX Series installation manual

Ditek ZEUS Series installation instructions

Ditek

Ditek ZEUS Series installation instructions

Citel MJ8-POE-A installation instructions

Citel

Citel MJ8-POE-A installation instructions

Philips SPP4220WA Specifications

Philips

Philips SPP4220WA Specifications

brennenstuhl Primera-Tec Comfort Switch Plus 19.500 A operating instructions

brennenstuhl

brennenstuhl Primera-Tec Comfort Switch Plus 19.500 A operating instructions

Dynex DX-AVSP8, DX-SF125, DX-SF126, DX-SF127 Quick setup guide

Dynex

Dynex DX-AVSP8, DX-SF125, DX-SF126, DX-SF127 Quick setup guide

Monster MDP 650 Instructions and warranty information

Monster

Monster MDP 650 Instructions and warranty information

Ilsco SSI SpecPRO CRM 3 Series manual

Ilsco

Ilsco SSI SpecPRO CRM 3 Series manual

Energenie SIS-PWM Silver Shield user manual

Energenie

Energenie SIS-PWM Silver Shield user manual

Siemens 5SD7 498-3 operating instructions

Siemens

Siemens 5SD7 498-3 operating instructions

QVS PP124 Specification sheet

QVS

QVS PP124 Specification sheet

Weidmüller VPU IoT AC manual

Weidmüller

Weidmüller VPU IoT AC manual

UTEPO USP2108 quick start guide

UTEPO

UTEPO USP2108 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.