M-system B3FV User manual

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7513 Rev.8 P. 1 / 5
INSTRUCTION MANUAL
SIGNAL TRANSMITTER
(eld-congurable) MODEL B3FV
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH UL
•This equipment is suitable for use in a Pollution Degree
2 environment.
•This equipment is to be used with the maximum operat-
ing voltage 30 V rms and 42.4 V peak or 60 V DC.
•The equipment must be mounted inside a suitable fire
enclosure.
•Operating temperature: -40 to +55°C (-40 to +131°F)
•Altitude up to 2000 meters.
■CONFORMITY WITH EU DIRECTIVES
•Functional insulation is maintained between signal input
and output.
•The input voltage across the terminals must be 70 V or
less.
•The equipment must be mounted inside a panel.
•The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
•Install lightning surge protectors for those wires connect-
ed to remote locations.
■GENERAL PRECAUTION
•Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -40 to +85°C
(-40 to +185°F) with relative humidity within 0 to 95%
RH in order to ensure adequate life span and operation.
•Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
•The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Body
SW Configuration
Zero Adj.
Span Adj.
Specifications
(side)
■HOW TO OPEN THE COVER WHEN SETTING DIP SW
Hold at the top and bottom of the unit as shown below and
slide the housing cover gently to open until it hits the latch-
ing inside the unit.
• Housing Cover Fully Opened
Caution: DO NOT PULL beyond where the housing cover is latched.
The plastic housing may be damaged.

B3FV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7513 Rev.8 P. 2 / 5
■HOW TO SEPARATE THE EURO TYPE CONNECTOR
TERMINAL BLOCKS
When you need to separate the euro type connector termi-
nal blocks from the transmitter body for wiring, insert a mi-
nus driver between the euro type connector terminal block
and the housing body, pull up the driver and pull out the
euro type connector terminal block.
INSTALLATION
■DIN RAIL MOUNTING
Set the unit so that its DIN rail adaptor is at the bottom.
Position the upper hook at the rear side of the unit on the
DIN rail and push in the lower. When removing the unit,
push down the DIN rail adaptor utilizing a minus screw-
driver and pull.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
10 11 12
456
106 (4.17)
18 (.71) 110.5 (4.35)
62 (2.44)
[5 (.20)]
DIN RAIL
35mm wide
• When mounting, no extra space is needed between units.
■CONNECTION DIAGRAM
12
mA
MONITOR
–
4
5+
–
LOAD
11
10
OUTPUT
24 V DC
4 – 20 mA DC
+
–
INPUT
*
* DC ammeter’s internal resistance 10 ohms max.

B3FV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7513 Rev.8 P. 3 / 5
■WIRING INSTRUCTIONS
•Applicable wire size
Solid: 0.2 to 2.5 mm2(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm2(Tinning wire ends may cause
contact failure and therefore is not recom-
mended.)
Ferruled: 0.2 to 1.5 mm2(0.55 to 1.35 dia.)
The following Phoenix Contact terminals are
recommended:
AI 0,25-8YE 0.2 to 0.25 mm2
AI 0,34-8TQ 0.25 to 0.34 mm2
AI 0,5-8WH 0.34 to 0.5 mm2
AI 0,75-8GY 0.5 to 0.75 mm2
AI 1,0-8RD 0.75 to 1.0 mm2
AI 1,5-8BK 1.0 to 1.5 mm2
•Expose wire conductors by 8 mm (0.31”).
8 mm 8 mm
4 mm dia.
max.
4 mm dia.
max.
Wire exposure Recommended
ferruled wire
EXTERNAL VIEWS
ON
1
SW1
SW2
2345678
Input Config. DIP SW
10 11 12
456
Zero Adj.
Span Adj.
■ FRONT VIEW ■ SIDE VIEW
RANGE CONFIGURATION
CAUTION !
•With the current input configuration (SW1-1 ON), DO NOT apply voltage input.
•DO NOT apply voltage exceeding the maximum value of the selected range.
•Applying voltage input greater than the maximum value of the selected range may cause failure of the unit. Check the
setting before applying the input signal.
■GENERAL PROCEDURE
First select a coarse range using the internal DIP switches (SW1 and SW2) according to Tables 2 through 5 below.
Then apply simulated 0% and 100% inputs and fine-tune the output range to 4 mA and 20 mA using the front zero and span
adjustments.
■INPUT TYPE & RANGE Table 1
INPUT TYPE MAXIMUM RANGE SPAN OFFSET
DC Current -30 to +30 mA DC Min. 16 µA, Max. 60 mA -100 to +80%
DC Voltage -100 to +100 V DC *1Min. 4 mV, Max. 100 V of the selected range *2
*1. Refer to Table 3 for the maximum value of selectable ranges.
*2. Max. voltage across the input terminals: 70 V for conform with EU Directive; 60 V for UL approval.

B3FV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7513 Rev.8 P. 4 / 5
■SELECTING DIP SW (coarse adjustment)
INPUT TYPE
Choose Current or Voltage according to Table 2.
INPUT RANGE
Choose the desired range matching the maximum value
and the span according to Table 3.
•For a current input, convert the range to a voltage with
the following equation:
Table 2 ■= ON
INPUT TYPE SW1
1
Current ■
Voltage
Voltage = (100% Current – 0% Current) ×250 Ω
•When the 0% and 100% values have the same polarity, select the absolute greater value as Span.
•When the 0% and 100% values have opposite polarity, select the absolute difference of the two values (100% – 0%) as Span.
•If the Span value is available in two range selections, select the smaller range. (e.g. Set to the 1 V range for 0 – 1 V, though
the maximum value 1 V can be selectable both in 2 V and 1 V range.)
•The minimum span and offset requirements in the table must be met when choosing the desired range.
Table 3 ■= ON
MAX. VALUE OF
USABLE RANGE SPAN OFFSET SW1 SW2
234567878
100 V 20 V ≤ Span ≤ 100 V
-100 to +80%
of the selected range
■
20 V 4 V ≤ Span ≤ 20 V ■
10 V 2 V ≤ Span ≤ 10 V ■
2 V 400 mV ≤ Span ≤ 2 V ■ ■
1 V 200 mV ≤ Span ≤ 1 V ■ ■ ■
200 mV 40 mV ≤ Span ≤ 200 mV ■ ■ ■
100 mV 20 mV ≤ Span ≤ 100 mV ■■■■
20 mV 4 mV ≤ Span ≤ 20 mV ■■■
OFFSET
See Table 4.
The offset is defined by the following equation:
Offset = [0% Input] × 100 (%)
[Max. value of usable range: Table 3]
Table 4 ■= ON
OFFSET
SW2
1234
+60% < Offset ≤ +80% ■ ■
+30% < Offset ≤ +60% ■
+10% < Offset ≤ +30% ■
-10% ≤ Offset ≤ +10% ■ ■
-30% ≤ Offset < -10% ■
-60% ≤ Offset < -30% ■
-100% ≤ Offset < -60% ■ ■
GAIN
See Table 5.
The gain is defined by the following equation:
Gain = [Max. value of usable range: Table 3] × 100 (%)
[100% Input – 0% Input]
Table 5 ■= ON
GAIN SW2
5 6
270% < Gain ≤ 500%
150% < Gain ≤ 270% ■
100% ≤ Gain ≤ 150% ■
■EXAMPLE
Calibrated input range: 1 – 5 V DC
1) Input type: According to Table 2, choose ‘Voltage.’
➠Set SW1-1 to OFF.
2) Input range:
5 V > 1 V ➠5 V is used as the maximum value.
According to Table 3, choose ‘10 V.’
➠Set SW1-4 to ON.
3) Offset
1 V ×100 = 10 (%)
10 V
➠According to Table 4, SW2-2 and SW2-3 to ON.
4) Gain
10 V ×100 = 250 (%)
5 V – 1 V
➠According to Table 5, set SW2-6 to ON.
ON
1
SW2
2345678
ON
1
SW1
2345678
■ZERO & SPAN ADJUSTMENTS (ne adjustments)
Referring to ‘ADJUSTMENT PROCEDURE,’ apply 0% and
100% input signals and adjust the Zero to have 4 mA output
and Span to have 20 mA output respectively.

B3FV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7513 Rev.8 P. 5 / 5
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) DIP SW setting: Check that the switches are set to ap-
propriate positions.
3) Input: Check that the input voltage is within 0 – 100% of
full-scale.
4) Output: Check that the load is within the permissible
limit including wiring resistance.
Load Resistance (Ω) = Supply Voltage (V) – 12 (V)
0.02 (A)
(including leadwire resistance)
5) When you check the output signal, connect an ammeter
of which the internal resistance is of 10 Ω max. to the
monitor terminals.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.
Table of contents
Other M-system Transmitter manuals

M-system
M-system 17PE User manual

M-system
M-system W2CA User manual

M-system
M-system W2PA User manual

M-system
M-system 6R User manual

M-system
M-system 6M User manual

M-system
M-system M1EXV-1 User manual

M-system
M-system Mini-MW Series User manual

M-system
M-system 10VK User manual

M-system
M-system Mini-M M2UDS2 User manual

M-system
M-system M6SVS User manual

M-system
M-system Mini-MW Series User manual

M-system
M-system 10JM User manual

M-system
M-system CTS2 User manual

M-system
M-system M6SCTC User manual

M-system
M-system M3LR User manual

M-system
M-system 27TS User manual

M-system
M-system M3LT User manual

M-system
M-system MFS2 User manual

M-system
M-system M5XPA User manual

M-system
M-system W2SP User manual