Mandik FDMC User manual


2
These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers)
FDMC. It is valid for production, designing, ordering, delivery, assembly and operation.
1. Description.........................................................................................................................
3
2. Damper Design..….............................................................................................................
4
3. Communication and control devices..............…..................................................................
7
4. Dimensions, weights...........................................................................................................
10
5. Placement and Assembly....................................................................................................
11
6. Statement of installations....................................................................................................
13
7. Suspension of fire dampers.................................................................................................
19
8. Pressure loss......................................................................................................................
22
9. Coefficient of local pressure loss.........................................................................................
22
10. Noise data.........................................................................................................................
23
11. Material.............................................................................................................................
25
12. Inspection, testing.............................................................................................................
26
13. Logistic terms....................................................................................................................
26
14. Assembly..........................................................................................................................
26
15. Entry into service and revisions.........................................................................................
26
16. Ordering key.....................................................................................................................
27
17. Data label.........................................................................................................................
28

3
Fire dampers are shutters in duct systems of air-conditioning devices that prevent spreading the
fire and combustion products from one fire segment to the other one by means of closing the air
duct in the points of fire separating constructions.
Dampers blade automatically closes air duct using a shutting spring or an actuating mechanism
back spring. The back spring of the actuating mechanism is started when the thermoelectrical
starting mechanism BAT72B-S is activated, when a reset button on BAT72B-S is pushed or when
a power supply of the actuating mechanism is stopped.
The damper is sealed with a silicon packing against smoke penetration after closing the blade. At
the same time, the damper blade is bedded in a material which enlarges its capacity and air
proofs the air duct.
Dampers have one inspection hole, since the shutting device and the inspection hole can be set
into the most advantageous position (with respect to the operation and manipulation with the
control device).
Damper characteristics
• CE certified acc. to EN 15650
• Tested in accordance with EN 1366-2
• Classified acc. to EN 13501-3+A1
• Fire resistance EIS 60
• External Casing leakage class min. C, Internal leakage class 3 (D=200 - 400 mm) and class 2
(D=180 mm) and class 1 (D=100 - 160 mm) acc. to EN 1751
• Cycling test in class C 10000 acc. to EN 15650
• Corrosion resistant acc. to EN 15650
• ES Certificate of conformity No. 1391-CPR-0090/2014
• Declaration of Perfomance No. PM/FDMC/01/16/1
• Hygienic assessment of fire dampers - Report No. 1.6/13/16/1
Working conditions
Exact damper function is provided under the following conditions:
a) Maximum air circulation speed: 12 m.s
Maximum pressure difference: 1500 Pa
b) The air circulation in the whole damper section must be secured as steady on whole
surface.

4
Operation of the dampers does not depend on the direction of air circulation. The dampers can
be located in an arbitrary position.
Dampers are suitable for systems without abrasive, chemical and adhesive particles.
Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.
Temperature in the place of installation is permitted to range from - 30°C to + 50°C.
Design with actuating mechanism
Actuating mechanism
BAT
FDMC is always equipped by electric actuating mechanism BFL (further only "actuating
mechanism"). After being connected to power supply AC/DC 24V or 230V, the actuating
mechanism displaces the damper blade into operation position "OPEN" and at the same time it
pre-stretches its back spring. When the actuating mechanism is under voltage, the damper blade
is in the position "OPEN" and the back spring is pre-stretched. Time needed for full opening of the
flap blade from the position "CLOSED" to the position "OPEN" is maximum 60 sec. If the actuating
power supply is cut off (due to loss of supply voltage, or pushing the reset button on the
thermoelectrical starting mechanism BAT), the back spring displaces the damper blade into the
breakdown position "CLOSED". The time of displacing the blade from the position "OPEN" to the
position "CLOSED" takes maximum 20 sec. In case that the power supply is restored again (the
blade can be in any position), the actuating mechanism starts to re-displace the damper blade
into the position "OPEN".
A thermoelectrical starting mechanism BAT, which contains two thermal fuses Tf1 and Tf2, is a
part of the actuating mechanism. These fuses are activated when temperature +72 °C has been
exceeded (the fuse Tf1 when the temperature around the damper and the fuses Tf2 when the
temperature inside the air-conditioning piping has been exceeded). After the thermal fuse Tf1 or
Tf2 has been activated, the power supply is permanently and irreversibly cut off and the actuating
mechanism, by means of the pre-stretched spring, displaces the damper blade into the
breakdown position "CLOSED".
Signalisation of damper blade position "OPEN" a "CLOSE" is provided by two limit switches.

5
Nominal voltage AC 230 V 50/60 Hz AC 24 V 50/60 Hz
DC 24 V
Power consumption - motoring
- holding
3,5/5 W
1,1/2,1 W
2,5/4 W
0,8/1,4 W
Dimensioning 6,5/10 VA (Imax 4 A @ 5 ms) 4/6 VA (Imax 8,3 A @ 5 ms)
Protection class II III
Degree of protection IP 54
Running time - motor
- spring return
<60 s
~ 20 s
Ambient temperature
- normal duty
- safety duty
- non-operating temperature
- 30°C … +55°C
The safe position will be attained up to max. +75°C
- 40°C … +55°C
Connecting - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm² (BFL 24-T-ST) with 3-pin plug-in connectors
cable 1 m, 6 x 0,75 mm² (BFL 24-T-ST) with 6-pin plug-in connectors
Thermal trips duct outside temperature +72°C
duct inside temperature +72°C
12 S3
S1 S2 S5S4 S6
NL1
<5° <80°
BAT
Tf Tf LED
12 S3
S1 S2 S5S4 S6
<5° <80°
BAT
Tf Tf LED
~
- +

6
Design with the communication and supply device
Design with the communication and supply device BKN 230-24 and the actuating mechanism
BFL 24-T-ST. It simplifies electrical wiring and interconnection of fire damper. It facilitates on site
check and enables central control and checks of fire damper by means of a simple 2-conductor
wiring.
BKN 230-24 functions as a decentralized network device for supplying the actuating mechanism
BFL 24-T-ST with a spring back drive on one hand and on the other hand it transmits the signal
information about the fire damper position OPERATION and FAILURE through 2-conductor
wiring to the central. Control command SWITCHED ON - SWITCHED OFF from the central
through BKN 230-24 goes through the same wiring to the actuating mechanism.
To simplify the connection, the actuating mechanism BFL 24-T-ST is equipped with connecting
plugs that are inserted directly to BKN 230-24. BKN 230-24 is supplied with a conductor and an
EURO plug to be connected to the 230V mains.
2- conductor wiring is connected to BKN 230-24 by means of terminals 6 and 7.
If the drive is supposed to be controlled without any signal from the central, it can be switched on
by means of a bridge between the terminals 3 and 4. A green LED pilot light on BKN 230-24 is
on when voltage is present in the drive (AC 24V). If the button on BAT72B-S is switched on or if
the power supply (e.g. by a signal from ELECTRICAL FIRE SIGNALISATION) is disconnected,
the fire damper position will be "FAILURE".
Communication and supply device BKN 230-24 has to be placed near the damper. It is necessary
for easy connection of actuating system equipped by BKN 230-24 device.
BAT
BKN
Actuating mechanism
Nominal voltage AC 230V 50/60Hz
Power consumption 3,5 W (operating position)
Dimensioning 11 VA (including actuating mechanism)
Protection Class II
Degree of protection IP 42
Ambient Temperature
Storage Temperature
- 30 °C … + 50 °C
- 40 °C … + 50 °C
Connection - mains
- drive
- terminal board
Cable 0,9 m with EURO plug of 26 type
6 pole plug, 3 pole plug
screw terminals for conductor 2x1,5 mm

7
BKS 24-9A communication and control device is used for group control and checks of 1 to 9 fire
dampers with the actuating mechanism BFL 24-T-ST in connection with the supply and
communication device BKN 230-24. Signalisation of the damper position is individual; the
dampers can be controlled and tested only as a group. BKS 24-9A is intended for use in the
distribution board and displays the operation situations and failure reports of the connected fire
dampers. It is possible to signalise functions such as the damper position and failure reports or to
transmit them further to the system by means of integrated auxiliary switches. BKS 24-9A
receives signals from BKN 230-24 through the two-conductor wiring and issues control
commands. Proper damper operation is indicated by two light LED diodes:
Control ON = position OPERATION
Control OFF = position FAILURE
If the fire dampers do not reach the given position in time tolerable for displacing, the appropriate
light diode FAILURE starts to flash and K1 contact is opened (current failure). In case that the
faulty damper finally reaches its given position, K1 is closed and the failure report lights up shines
(the failure is saved in memory).
K2 - the auxiliary contact - is used for signalisation of the flap position to the master device. Function
of this auxiliary contact can be programmed through the terminal 14 according to the Tab. 3.1.1.
Nominal voltage AC 230V 50/60Hz
Power consumption 3,5 W (operating position)
Dimensioning 11 VA (including actuating mechanism)
Protection Class II
Degree of protection IP 42
Ambient Temperature
Storage Temperature
- 30 °C … + 50 °C
- 40 °C … + 50 °C
Connection - mains
- drive
- terminal board
Cable 0,9 m with EURO plug of 26 type
6 pole plug, 3 pole plug
screw terminals for conductor 2x1,5 mm
1
2
3
4
5
6
7b
a
1)1)
2)
BAT
1) Bridge has been installed by the manufacturer. If needed, it can be
removed ad replaced with a thermoelectric starting mechanism. If
terminals 1 and 2 are not interconnected, safety function is initiated.
2) Bridge can be used only for starting and without BKS24… !
Two conductor wiring to BKS24

8
Current Failure 15 16
No Failure 15 16
K2 contact is on if all the
damperss are open 14 11
17 18
K2 contact is on if the damper
No. 1 is open
14 12
K2 contact is on if all the
dampers are closed 14 open
Function check can be done in the position OPERATION by means of pushing the TEST button.
While the button is pushed, the flap blade is turning into the position FAILURE. Fault function is
indicated by a report "FAILURE".
Nominal voltage AC 24 V 50/60Hz
Power consumption 3,5 W (operating position)
Dimensioning 5,5 VA
Protection Class III (safe small voltage)
Degree of protection IP 30
Ambient Temperature 0 … + 50 °C
Connection Terminals for conductor 2 x 1,5 mm
BKS 24-1B communication and control device is used for control and checks of fire dampers with the
BFL 24-T-ST actuating mechanism in conjunction with the BKN 230-24 supply and communication
device. BKS 24-1B receives information about the situation of the fire damper through the BKN
230-24 supply and communication device and issues controlling commands. The device is intended
for building in into the distribution board. Light diodes on the front side of the device indicates the
operating situations of the damper and breakdowns of the whole system. Nonpotential auxiliary
contacts enable connection to the master control system (indication of the damper position, failure
reports, release of the ventilators etc.).

9
Nominal voltage AC 24 V 50/60Hz
Power consumption 2,5 W (operating position)
Dimensioning 5 VA
Protection Class III (safe small voltage)
Degree of protection IP 30
Ambient Temperature 0 … + 50 °C
Connection Into ZSO-11 connector which is not a part of BKS 24-1B.
ZSO-11 connector has screw terminals 11 x 1,5 mm
4
7
8
2
10
1
5
9
an insulation
transformer
~
damper position
breakdown
Notice: Relay contacts are drawn
without power
11
b
a
2-conductor wiring
to BKN230-24
Control
on /off
Reset
Test
External buton
optional
be interchanged
6
3
AC
24V
damper position
operation
Reset
Test
open
closed
alarm
failure
Connection through
conection can
, starting with switching AC 24 on or pressing
«Reset/Test» button
possible cause: • short circuit or interruption of 2-conductor wiring
or damper failure (at BKN..) • Power supply AC 230V missing • defective
thermoelectrical starting • smoke detector activated • exceeded operation time
• Fault in system signalled, system check should be
done
Damper (drive) turning into of breakdown position
Damper (drive) in
Damper (drive) turning into of operating position
Damper (drive) in
light diodes contacts Description
Cause/Course
state
open closed alarm
closed
flashing
63
63
67
64
64
63
63
67
switched
closed closed
closed closed
closed closed
closed
closed
closed
closed
closed
closed
closed
closed
open open open
open
open
open
flashing
flashing
• damper blocked
not available
While a flashing green LED pilot light signalises flap blade motion towards the given position, the
same pilot light reports reaching the required position when shining constantly. If the damper, with
respect to the given time, does not reach the required position, then a red LED pilot light starts to
flash and at the same time, the failure contact is active. Once the damper blade reaches the given
position, this contact is deactivated. The LED pilot light keeps flashing unless the failure is unblocked
by means of the RESET button.

10
1 Damper casing
2 Damper blade
10 Inspection hole covering
14 BAT thermoelectrical starting
mechanism
15 Actuating mechanism
BUILT-IN EDGE
Weight and effective area
- 3,1 0,0036 BFL
- 3,4 0,0068 BFL
- 3,6 0,0092 BFL
- 3,7 0,0109 BFL
- 3,8 0,0129 BFL
- 4,1 0,0172 BFL
- 4,4 0,0222 BFL
- 4,7 0,0293 BFL
9 5,5 0,0374 BFL
24 6,0 0,0484 BFL
41,5 6,6 0,0630 BFL
59 7,0 0,0793 BFL
61,5 7,3 0,0821 BFL
84 8,2 0,1065 BFL
Dimensions

11
Blades overlaps
Side without act. mechanism "a" Tab. 4.2.1
Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages
of fire separating constructions. Damper assembly procedures must be done so as all load
transfer from the fire separating constructions to the damper body is absolutely excluded.
Back-to-back air-conditioning piping must be hung or supported so as all load transfer from the
back-to-back piping to the damper is absolutely excluded. Installation gap must be filled by
approved material perfectly in all the installation space volume (installation gap).
To provide needed access space to the control device, all other objects must be situated at least
350 mm from the control parts of the damper. Inspection hole must be accessible.
Damper blade has to be inside of construction (labelled with BUILD IN EDGE on the damper
body) after installation. The fire damper can also be installed outside the wall construction. Duct
and the damper part between the wall construction and the damper blade (labelled with BUILD
IN EDGE on the protective covering) must be protected with firefighting insulation (see fig. 12).
The distance between the fire damper and the construction (wall, ceiling) must be minimal in
range from 10 to 50 mm. In case that two or more dampers are supposed to be installed in one
fire separating construction, the distance between the adjacent dampers must be at least 50 mm.
Exceptions are given in chapter 6.

12
260
420
(50)
BUIL-IN EDGE
BUILT-IN EDGE
BUILT-IN EDGE
The control mechanism has to be protected (covered) against damage and pollution during
installation process. All fire dampers has to be closed during installation process. The damper
body should not be deformed in the course of bricking in. Once the damper is built in, its blade
should not grind on the damper body during opening or closing.
Installation opening dimensions (see Fig. 13-14)
The control mechanism has to be protected (covered) against damage and pollution during
installation process.
All fire dampers has to be closed during installation process. The damper body should not be
deformed in the course of bricking in. Once the damper is built in, its blade should not grind on
the damper body during opening or closing.

13
Statement of installations the fire dampers FDMC and their fire resistance Tab. 6.1.1.
100 Mortar or gypsum EIS 60 14
100 Stuffing box + mastic and cement lime plate EIS 60 14
100
Installation next to wall - mortar or gypsum and
mineral wool
EIS 60 15
110 Mortar or gypsum EIS 60 16
110 Stuffing box + mastic and cement lime plate EIS 60 16
100 Mortar or gypsum EIS 60 17
100 Stuffing box + mastic and cement lime plate EIS 60 17
100
Installation next to wall - mortar or gypsum and
mineral wool
EIS 60 18

14
≥ 50
≥ 40
≥ 100
≥ 40
≥ 100
POSITION:
1 Fire damper FDMC
2 Solid wall construction
3 Mortar or gypsum
4 Duct
POSITION:
1 Fire damper FDMC
2 Solid wall construction
3 Mineral stone wool min. density 140 kg/m
4 Fire protection mastic min. thickness 1 mm
5
Glass fiber felt with aluminium foil width 50 mm, thickness 5 mm
6 Duct
3
Used materials - example*:
3 - Promapyr, Rockwool Steprock HD
4 - Promastop - P, K
* Stuffing box and fire protection mastic can be replaced by another approved
fire sealing system for damper installation with equivalent material properties.

15
≥ 100
(≥ 100)+50
POSITION:
1 Fire damper FDMC
2 Mortar or gypsum
3 Mineral stone wool min. density 140 kg/m 3
D-20
≥ D+100
D-20
D-20
≥ 100
≥ D+100
●Gap between damper and construction is filled by mortar or
gypsum and mineral wool
●Wool is fixed to damper body and construction by fire protection
mastic.
●Mineral wool thickness = construction thickness + 50 mm
●Installation is valid for ceiling construction
≥ 10
≥ 10
≥ 10
≥ 10

16
≥ 40
150*
≥ 50
POSITION:
1 Fire damper FDMC
2 Solid ceiling construction
3 Mineral stone wool min. density 140 kg/m
4 Fire protection mastic min. thickness 1 mm
5 Glass fiber felt with aluminium foil width 50 mm, thickness 5 mm
6 Duct
Used materials - example**:
2 - Promapyr, Rockwool Steprock HD
3 - Promastop - P, K
3
POSITION:
1 Fire damper FDMC
2 Solid ceiling construction
3 Mortar or gypsum
4 Duct
150*
≥ 40
* min. 110 - Concrete/ min. 125 - Aerated concrete
* min. 110 - Concrete/ min. 125 - Aerated concrete
** Stuffing box and fire protection mastic can be replaced by another approved
fire sealing system for damper installation with equivalent material properties.

17
≥ 40
≥ 100
≥ 50
POSITION:
1 Fire damper FDMC
2 Gypsum plate
3 Mineral wool (type depending on the type of construction)
4 Mineral stone wool min. density 140 kg/m
5 Fire protection mastic min. thickness 1 mm
6 Glass fiber felt with aluminium foil width 50 mm, thickness 5 mm
7 Duct
Used materials - example*:
4 - Promapyr, Rockwool Steprock HD
5 - Promastop - P, K
≥ 40
≥ 100
POSITION:
1 Fire damper FDMC
2 Gypsum plate
3 Mineral wool (type depending on the type of construction)
4 Mortar or gypsum
5 Duct
* Stuffing box and fire protection mastic can be replaced by another approved
fire sealing system for damper installation with equivalent material properties.
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
3

18
≥ 100
(≥ 100)+50
≥ D+100
D-20
≥ 100
≥ D+100
D-20
D-20
POSITION:
1 Fire damper FDMC
2 Mortar or gypsum
3 Mineral stone wool min. density 140 kg/m3
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
●Gap between damper and construction is filled by mortar or
gypsum and mineral wool
●Wool is fixed to damper body and construction by fire protection
mastic.
●Mineral wool thickness = construction thickness + 50 mm
●Installation is valid for ceiling construction
≥ 10
≥ 10
≥ 10
≥ 10

19
Mounting to the ceiling wall
M8 36,6 22 44
M10 58,0 35 70
M12 843 52 104
M14 115 70 140
M16 157 96 192
M18 192 117 234
M20 245 150 300
120
2x 9
M8 to M16
50
4x 9
M20
100
150
Position:
1 Threaded rod M8 – M20
2 Nut
3 Washer
4 Coupling Nut
5 Anchor
6 Hinge plate - min. thickness 10 mm
80
Fire dampers can be suspended by using threaded rods and a mounting profiles. Load the
suspension system depend on weight of the fire damper.
Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Threaded rod fixing to the ceiling construction - see fig. 23

20
Position:
1
Fire damper
2 Damping pad
3
Extension piece
4
Threaded rod
5
Suspension ring
Examples of using materials:
Fire dampers can be suspended by using threaded rods and a mounting profiles.
Load the suspension system depend on weight of the fire damper.
Damper can be suspended from the ceiling construction or supported above the ceiling construc-
tion. Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Other manuals for FDMC
3
This manual suits for next models
1
Table of contents
Other Mandik Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

Specified Technologies
Specified Technologies EZ PATH Installation sheet

Greenheck
Greenheck FSD Series Installation, operation and maintenance manual

Swegon
Swegon Actionair A60 manual

aldes
aldes Isone manual

pottorff
pottorff CD-81 Installation, operation and maintenance manual

SMAY
SMAY SCD Operation and maintenance manual