Mandik MSD User manual


2
These technical specifications state a row of manufactured sizes and models of multi smoke dampers (further only
dampers) MSD. It is valid for production, designing, ordering, delivery, maintenance and operation.
1. Description.........................................................................................................................
3
2. Design................................................................................................................................
4
3. Dimensions, weights...........................................................................................................
16
4. Placement and Assembly....................................................................................................
31
5. Statement of installations....................................................................................................
33
6. Suspension systems...........................................................................................................
46
7. Pressure loss......................................................................................................................
52
8. Coefficient of local pressure loss.........................................................................................
53
9. Noise data..............….………………………………….........................................................
54
10. Material.............................................................................................................................
56
11. Inspection, testing.............................................................................................................
57
12. Logistic terms....................................................................................................................
57
13. Assembly..........................................................................................................................
57
14. Entry into service and revisions.........................................................................................
59
15. Spare parts.......................................................................................................................
59
16. Data label.......................….…..........................................................................................
60
17. Ordering key.....................................................................................................................
61

3
Multi smoke dampers are shutters in the smoke exhaust duct systems. The dampers are designed to remove
heat and combustible products (e.g. smoke) from effected fire compartments. In the event of fire the Smoke
and Fire ventilation system opens the damper in the affected section and removes combustion products and
heat from this section.
The damper blade is controlled by electrical actuating mechanism.
Dampers are fire resistant and are intended for systems with automatic activation.
Dampers can be installed in construction of the fire compartment.
Basic types of dampers square:
• MSD Cycling test with load (possible design .44, .54, .65 and .66)
• MSD-W Cycling test without load (possible design .44, .54, .66, .4M0, .4M1, .5M0 and .5M1)
Basic types of dampers round:
• MSD Cycling test with load (possible design .44, .54 and .66)
• MSD-W Cycling test without load (possible design .4M0, .4M1, .5M0 and .5M1)
Dampers MSD can be open against flow and pressure.
Dampers MSD-W has to be open with the help of flow or without flow present.
Damper characteristics
• CE certified acc. to EN 12101-8
• Tested in accordance with EN 1366-10
• Classified acc. to EN 13501-4+A1
• Fire resistance according Tab. 1.2.1. and 1.2.2.
• External casing leakage class min. C acc. to EN 1751
• Internal leakage: round dampers - class min. 2, diameters from 560 mm to 630 mm min. class 3 acc. to EN 1751
square dampers - class min. 2, for max. dimension 1500 x 800 mm min. class 3 acc. to EN 1751
• Cycling test: MSD square dampers - Cmod acc. to EN 12101-8
MSD, MSD-W round dampers - C10000 acc. to EN 12101-8
MSD-W square dampers - C10000 acc. to EN 12101-8 (tested without load acc. to EN 1366-10)
• ES Certificate of conformity No. 1391-CPR-2021/0084 for MSD
• ES Certificate of conformity No. 1391-CPR-2021/0012 for MSD-W
• Declaration of Perfomance No. PM/MSD/01/21/2, PM/MSD-W/01/21/1
• Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19c
Porous concrete ceiling construction, th. 150 mm
Porous concrete wall construction, th. 100 mm
Gypsum wall EI 120, th. min 125 mm
Porous concrete ceiling construction, th. 150 mm
Porous concrete wall construction, th. 100 mm
Gypsum wall EI 120, th. min 125 mm

4
Working conditions
Exact damper function is provided under the following conditions:
a) maximum air velocity 15 m/s
b) underpressure max. -1500 Pa or overpressure max. 500 Pa.
Dampers can be installed in arbitrary position (horizontal or vertical blade axis).
Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.
Temperature in the place of installation is permitted to range from - 30°C to + 50°C.
Design with actuating mechanism
Belimo actuators are used for dampers, series BEN, BEE, BE for 230V AC resp. 24 V AC/DC,
Schischek InMax 50.75-S actuators (universal 24V or 230V supply) are used for large size of
dampers.
After connection to the power supply voltage, the actuator moves the damper blade to the
"OPEN" position or "CLOSED" (according to the corresponding connection, see wiring diagram).
If the power supply is interrupted, the actuator stops at the current position. The signalling of the
"OPEN" and "CLOSED" damper blade positions is ensured by two built-in fixed “potential-free”
end- limit switches.
The actuator for operating the damper blade can be mounted in an insulated cover/box. It is
accessible after removing the cover lid. The electrical connection of the actuator is made with a
non-flammable cable (or a cable located in the adjoining cable duct), which passes through an
opening made in the wall of the insulated cover/box when installing the damper or when
connecting the actuator power cable. The cable entry must meet a minimum fire resistance of 30
minutes.
Belimo modulating actuators, BEN (BEE)-SR series for 24V AC/DC are specially designed for
remote control of fire dampers. The position of the damper blade is adjustable by means of control
voltage 0 (2)...10V DC.
The signalling of the "OPEN" and "CLOSED" damper blade positions is ensured by two built-in
fixed “potential-free” limit switches.
The actuator for operating the damper blade is mounted in an insulated cover/box. It is accessible
after removing the cover lid. The electrical connection of the actuator is made with non-flammable
cables (or cables located in the adjoining cable duct), which pass through an opening made in the
wall of the insulated cover when installing the damper or when connecting the power cables of
the actuator. The cable entry must meet a minimum fire resistance of 30 minutes.

5
only for square MSD
Power voltage AC/DC 24 V
50/60Hz
AC/DC 24 V
50/60Hz
AC 230 V
50/60Hz
Power consumption - in operation
- in the end position
3 W
0,1 W
3 W
0,3 W
4 W
0,4 W
Dimensioning 6 VA (Imax 8,2 A @ 5 ms) 6,5 VA (Imax 8.2 A @ 5 ms) 7 VA (Imax 4 A @ 5 ms)
Protection class III III II
Degree of protection IP 54
Adjustment time for 95° < 30 s
Ambient temperature
Storage temperature
-30°C … +55°C
-40°C … +80°C
Connection - drive
- auxiliary switch
Cable 1 m, 3 x 0,75 mm2
Cable 1 m, 6 x 0,75 mm2
(BEN 24-ST) with plug
connectors
Cable 1 m, 4 x 0,75 mm2
Cable 1 m, 6 x 0,75 mm2
Cable 1 m, 3 x 0,75 mm2
Cable 1 m, 6 x 0,75 mm2
S2S1 S3 S5S4 S6
2
13
<5° <80°
S2S1 S3 S5S4 S6
2
13
<5° <80°
N L1
S2S1 S3 S5S4 S6
2
13
<5° <80°
5
Y
U
DC (0)2...10 V
DC 2...10 V

6
S2S1 S3 S5S4 S6
2
13
<5° <80°
S2S1 S3 S5S4 S6
2
13
<5° <80°
N L1
S2S1 S3 S5S4 S6
2
13
<5° <80°
5
Y
U
DC (0)2...10 V
DC 2...10 V
only for square MSD
Power voltage AC/DC 24 V
50/60Hz
AC/DC 24 V
50/60Hz
AC 230 V
50/60Hz
Power consumption - in operation
- in the end position
2,5 W
0,1 W
3 W
0,3 W
3,5 W
0,4 W
Dimensioning 5 VA (Imax 8,2 A @ 5 ms) 5,5 VA (Imax 8.2 A @ 5 ms) 6 VA (Imax 4 A @ 5 ms)
Protection class III III II
Degree of protection IP 54
Adjustment time for 95° < 60 s
Ambient temperature
Storage temperature
-30°C … +55°C
-40°C … +80°C
Connection - drive
- auxiliary switch
Cable 1 m, 3 x 0,75 mm2
Cable 1 m, 6 x 0,75 mm2
(BEE 24-ST) with plug
connectors
Cable 1 m, 4 x 0,75 mm2
Cable 1 m, 6 x 0,75 mm2
Cable 1 m, 3 x 0,75 mm2
Cable 1 m, 6 x 0,75 mm2

7
S2S1 S3 S5S4 S6
2
13
<3° <87°
S2S1 S3 S5S4 S6
2
13
<3° <87°
N L1
Power voltage AC/DC 24 V
50/60Hz
AC 230 V
50/60Hz
Power consumption - in operation
- in the end position
12 W
0,5 W
8 W
0,5 W
Dimensioning 18 VA (Imax 8,2 A @ 5 ms) 15 VA (Imax 7,9 A @ 5 ms)
Protection class III II
Degree of protection IP 54
Adjustment time for 95° < 60 s
Ambient temperature
Storage temperature
-30°C … +50°C
-40°C … +80°C
Connection - drive
- auxiliary switch
Cable 1 m, 3 x 0,75 mm2
Cable 1 m, 6 x 0,75 mm2
(BE 24-ST) with plug connectors

8
Nominal voltage 24-240 VAC/DC
50/60Hz
Power consumption - motoring
- heating
10 W
16 W (start at -20°C)
Protection class I
Degree of protection IP 66
Running time for 95° < 60 s
Ambient temperature range
Non-operating temperature
-40°C … +50°C
-40°C … +70°C
Connecting Cable 1 m, 0,5 mm2

9
BKNE 230-24
BKNE 230-24
Actuating mechanism
Actuating mechanism
Design with the communication and supply device BKNE 230-24
Design with communication and power supply device BKNE 230-24 and with actuator BEN (BEE,
BE)-ST for 24V.
The BKNE 230-24 serves on the one hand as a decentralized network device for powering the
actuator and on the other hand transmits the signal of the communication and control device
BKSE 24-6.
It simplifies electrical installation and connection of dampers. In the meantime, it facilitates
“on-site inspection” and allows central control and inspection of dampers using a simple 2-wire
line.
The BKNE 230-24 transmits the "OPEN" / "CLOSED" damper position (switches in the actuator)
and fault messages to the BKSE 24-6. It also receives commands from the control device and
controls the adjustment of the actuator to the desired position. The last control command will be
retained even after a temporary network failure..
The BKNE 230-24 controls the switching position of the actuator, its adjustment time and the data
exchange with the BKSE 24-6. In addition, it controls the actuator current (actuator connection)
and the power supply.
To simplify the connection, the actuator is equipped with plug connectors that plug directly into
the BKNE 230-24.
The actuator, communication and power supply device BKNE 230-24 can be mounted in an
insulated cover, they are accessible after removing the cover. The electrical connection of the
actuator and the BKNE 230-24 communication and power supply device is made with a non-
flammable cable (or a cable located in an adjoining cable duct), the two-wire BKNE 230-24 cable
should be connected to terminals 6 and 7. It is also recommended to use cable, which is used for
fire signalling network. The cables pass through an opening made in the wall of the insulated
cover when installing the damper or when connecting the actuator power cable. The cable entry
must meet a minimum fire resistance of 30 minutes.
For more information on actuators and devices, see the Belimo catalogue.
This variant is not available for dampers with Schischek InMax 50.75-S actuator.

10
1
2
3
4
5
6
7b
a
AC 230 V
Power voltage AC 230V 50/60Hz
Power consumption 10 W (including actuator)
Dimensioning 19 VA (including actuator)
Protection class II
Ambient operation temperature
Storage temperature
-30°C … +50°C
-40°C … +80°C
Connection - network
- drive
- terminal blocks
cable 1 m without plug
6-pin plug, 3-pin plug
screw terminals for 2x1.5 mm2 conductor
yellow flashing damper rotates to the open position
yellow lit-up damper is open
green flashing damper rotates to the closed position
green lit-up damper is closed
yellow or green flashes twice as often fault
yellow + green dark network outage
1 to 5 should not be
connected
two-wire line to
BKSE 24-6
Communication and supply device

11
Power voltage AC 24 V 50/60Hz
Power consumption 3,5 W (operating position)
Dimensioning 5,5 VA 18 VA (Imax 6.4 A @ 2.5 ms)
Protection class III (low voltage)
Degree of protection IP 20
Ambient operation temperature 0 … +50°C
Connection screw terminals for 2x1.5 mm2 conductor
17
~
AC 24 V
18
15
16
13
14
2
1
4
3
6
5
7
9
8
11
12
10
+
-
U
a1...a6
BKNE 230-24
a1...a6
Input 1
SMOKING
AUTO
END OF SMOKING
COM
delay 0 s (fan)
delay 60 s (fan)
OPEN
CLOSED
* Error
* reverse output: fault = contact open
Input 2
(galvanically isolated)
Communication and control devices
indicates operating condition and faults of flue dampers. These conditions can be
signalled or transmitted to the higher-level control system via the auxiliary built-in contacts.
Signals from individual BKNE 230-24 are evaluated separately. All BKNE 230-24 are controlled
simultaneously. A maximum of 6 BKNE 230-24 can be connected to the BKSE 24-6.
Damper control is ensured with a simple 2-wire line. The damper's correct function is indicated by
two LEDs. The operating status of the entire control system and any errors are indicated by these
LEDs and the corresponding error LED.
Mounting and connection of BKSE 24-6 can be done on a 35mm DIN rail. It's connected using
two 9-pin terminal blocks (plug connectors).

12
MSD-W is always equipped by electric actuating mechanism BFN 230-T, BFN 24-T, DAF2.20S
or DAF1.20S (further only "actuating mechanism") and is complemented with initiation by means
of an electromagnet (solenoid). After being connected to power supply AC/DC 24V or 230V, the
actuating mechanism displaces the damper blade into operation position "CLOSED" and at the
same time it pre-stretches its back spring. When the actuating mechanism is under voltage, the
damper blade is in the position "CLOSED" and the back spring is pre-stretched. Time needed for
full closing of the flap blade from the position "OPEN" to the position "CLOSED" is maximum
60 sec. This possition is secured by initional lever. If the actuating power supply is cut off damper
is still in the position "CLOSED". After activation of electromagnet is released initiation lever and
the back spring displaces the damper blade into the breakdown position "OPEN". The time of
displacing the blade from the position "OPEN" to the position "CLOSED" takes maximum 16 sec.
In case that the power supply is restored again (the blade can be in any position), the actuating
mechanism starts to re-displace the damper blade into the position "CLOSED".
By voltage AC 230 V is damper equipped by electromagnet EM230. By voltage AC/DC 24 V is
damper equipped by electromagnet EM230 with pre-pulse switch SIEM24. SEIM24 activates the
electromagnet after capacitor charge witch is placed inside of SIEM24. It takes about 10 sec.
Charging time depends on the current supply. For reliable operation is necessary connect to
electromagnet or pre-pulse switch appropriate supply for 2 sec (230 V) or 20 to 30 sec (24 V).
Design with electric actuating mechanism with emergency function and electromagnet
Actuating mechanism
Electromagnet (solenoid)
Actuating mechanism
Pulse switch
Electromagnet (solenoid)
Pulse switch

13
12 S3
S1 S2 S5S4 S6
NL1
<5° <80°
12 S3
S1 S2 S5S4 S6
<5° <80°
~
- +
Nominal voltage AC 24V 50/60Hz
DC 24 V AC 230 V 50/60Hz
Power consumption - motoring
- holding
5 W
2,5 W
5W
3W
Dimensioning 7 VA (Imax 5,8 A @ 5 ms) 7 VA (Imax 150 mA @ 10 ms)
Protection class III II
Degree of protection IP 54
Running time - motor
- spring return
< 120 s
~ 16 s
Ambient temperature
- normal duty
- safety duty
- non-operating temperature
-30°C … +50°C
The safe position will be attained up to max. 75°C
-40°C … +50°C
Connecting - motor
- auxiliary switch
cable 1 m, 2 x 0,75 mm2
cable 1 m, 6 x 0,75 mm2

14
NL1
BLK
1
RED
2
BLK
1
RED
2
~
+-
S1
BLK/
21 22
RED
BLK/
BLU
BLK/
GRY
23
WHT/
24 25
RED
WHT/
BLU
WHT/
GRY
26
S2
21
21
22
23
24
24
25
26
COM NC NO COM NC NO
Nominal voltage AC 24V 50/60Hz
DC 24 V AC 230 V 50/60Hz
Power consumption - motoring
- holding
26 VA (AC); 15,6 W (DC)
9,3 VA (AC); 2,6 W (DC)
0,15 A
0,09 A
Dimensioning 14 VA 14 VA
Protection class II II
Degree of protection IP 54
Running time - motor
- spring return
24…57 s
11…15 s
Ambient temperature
- normal duty
- non-operating temperature
-40°C … +55°C
-65°C … +85°C
Connecting - motor
- auxiliary switch
cable 1,2 m halogen-free; 2-wires
cable 1,2 m halogen-free; 6-wires

15
Nominal voltage AC 230 V / 50 Hz
Dimensioning 1,2 A
Degree of protection IP 40
Ambient temperature
range -10°C … +40°C
Connecting cable 1m, 3x0,75mm2
Nominal voltage AC 24 V / 50 Hz
DC 24 V
Dimensioning 1 A
Degree of protection IP 40
Ambient temperature
range -10°C … +40°C
Switching frequency max. 1x per minute
Connecting cable 1m, 3x0,75mm2
Electromagnet connection

16
Dimensions
375
A
B
Position:
1 MSD
2
Actuating mechanism
3 Damper blade
4
Access door/ inspection cover
5 Electromagnet (solenoid)
6 Pulse switch SIEM24
375
A
B
Position:
1 MSD
2
Actuating mechanism
3 Damper blade
4
Access door/ inspection cover

17
Position:
1 MSD
2 Insulation box
3 Damper blade
4
Access door/ inspection cover
5 Protective cladding boards
375
A
B
168 / 171 / 220 *
250 / 260 / 260 *
300 / 370 / 430 *
Position:
1 MSD
2 Insulation box
3 Damper blade
4
Access door/ inspection cover
375
A
B
168 / 171 / 220 *
250 / 260 / 260 *
300 / 370 / 430 *

18
375
ØD
5050
475
Position:
1 MSD
2
Actuating mechanism
3 Damper blade
4
Access door/ inspection cover
375 5050
475
ØD
Position:
1 MSD
2
Actuating mechanism
3 Damper blade
4
Access door/ inspection cover
5 Electromagnet (solenoid)
6 Pulse switch SIEM24

19
Weight and effective area - square dampers
- 19 0,0162 11,2 BELIMO BEN 11,7 BELIMO BFN 12,2 BELIMO BEN
- 29 0,0191 11,6 BELIMO BEN 12,1 BELIMO BFN 12,6 BELIMO BEN
- 41,5 0,0228 12,1 BELIMO BEN 12,6 BELIMO BFN 13,1 BELIMO BEN
- 54 0,0264 12,6 BELIMO BEN 13,1 BELIMO BFN 13,6 BELIMO BEN
- 69 0,0307 13,3 BELIMO BEN 13,8 BELIMO BFN 14,3 BELIMO BEN
- 79 0,0336 13,7 BELIMO BEN 14,2 BELIMO BFN 14,7 BELIMO BEN
- 86,5 0,0358 14 BELIMO BEN 14,5 BELIMO BFN 15 BELIMO BEN
-
106,5
0,0416 14,8 BELIMO BEN 15,3 BELIMO BFN 15,8 BELIMO BEN
- 129 0,0481 15,8 BELIMO BEN 16,3 BELIMO BFN 16,8 BELIMO BEN
- 154 0,0554 16,8 BELIMO BEN 17,3 BELIMO BFN 17,8 BELIMO BEN
- 179 0,0626 17,8 BELIMO BEN 18,3 BELIMO BFN 18,8 BELIMO BEN
- 204 0,0699 18,9 BELIMO BEN 19,4 BELIMO BFN 19,9 BELIMO BEN
- 209 0,0713 19,1 BELIMO BEN 19,6 BELIMO BFN 20,1 BELIMO BEN
- 229 0,0771 19,9 BELIMO BEN 20,4 BELIMO BFN 20,9 BELIMO BEN
- 244 0,0815 20,5 BELIMO BEN 21 BELIMO BFN 21,5 BELIMO BEN
9 254 0,0844 20,9 BELIMO BEN 21,4 BELIMO BFN 21,9 BELIMO BEN
34 279 0,0916 22 BELIMO BEN 24,3
JOVENTA DAFx.20S
23 BELIMO BEN
39 284 0,0931 22,2 BELIMO BEN 24,5
JOVENTA DAFx.20S
23,2 BELIMO BEN
59 304 0,0989 23 BELIMO BEN 25,3
JOVENTA DAFx.20S
24 BELIMO BEN
84 329 0,1061 24 BELIMO BEN 26,4
JOVENTA DAFx.20S
25 BELIMO BEN
- 19 0,0185 11,6 BELIMO BEN 12,1 BELIMO BFN 12,6 BELIMO BEN
- 29 0,0218 12 BELIMO BEN 12,5 BELIMO BFN 13 BELIMO BEN
- 41,5 0,0259 12,5 BELIMO BEN 13 BELIMO BFN 13,5 BELIMO BEN
- 54 0,0300 13,1 BELIMO BEN 13,6 BELIMO BFN 14,1 BELIMO BEN
- 69 0,0350 13,7 BELIMO BEN 14,2 BELIMO BFN 14,7 BELIMO BEN
- 79 0,0383 14,2 BELIMO BEN 14,7 BELIMO BFN 15,2 BELIMO BEN
- 86,5 0,0408 14,5 BELIMO BEN 15 BELIMO BFN 15,5 BELIMO BEN
-
106,5
0,0474 15,3 BELIMO BEN 15,8 BELIMO BFN 16,3 BELIMO BEN
- 129 0,0548 16,3 BELIMO BEN 16,8 BELIMO BFN 17,3 BELIMO BEN
- 154 0,0630 17,4 BELIMO BEN 17,9 BELIMO BFN 18,4 BELIMO BEN
- 179 0,0713 18,5 BELIMO BEN 19 BELIMO BFN 19,5 BELIMO BEN
- 204 0,0795 19,6 BELIMO BEN 20,1 BELIMO BFN 20,6 BELIMO BEN
- 209 0,0812 19,8 BELIMO BEN 20,3 BELIMO BFN 20,8 BELIMO BEN
- 229 0,0878 20,6 BELIMO BEN 21,1 BELIMO BFN 21,6 BELIMO BEN
- 244 0,0927 21,3 BELIMO BEN 21,8 BELIMO BFN 22,3 BELIMO BEN
9 254 0,0960 21,7 BELIMO BEN 22,2 BELIMO BFN 22,7 BELIMO BEN
34 279 0,1043 22,8 BELIMO BEN 25,1
JOVENTA DAFx.20S
23,8 BELIMO BEN
39 284 0,1059 23 BELIMO BEN 25,3
JOVENTA DAFx.20S
24 BELIMO BEN
59 304 0,1125 23,9 BELIMO BEN 26,2
JOVENTA DAFx.20S
24,9 BELIMO BEN
84 329 0,1208 25 BELIMO BEN 27,3
JOVENTA DAFx.20S
26 BELIMO BEN
- 19 0,0207 11,9 BELIMO BEN 12,4 BELIMO BFN 12,9 BELIMO BEN
- 29 0,0244 12,4 BELIMO BEN 12,9 BELIMO BFN 13,4 BELIMO BEN
- 41,5 0,0290 12,9 BELIMO BEN 13,4 BELIMO BFN 13,9 BELIMO BEN
- 54 0,0337 13,5 BELIMO BEN 14 BELIMO BFN 14,5 BELIMO BEN
- 69 0,0392 14,2 BELIMO BEN 14,7 BELIMO BFN 15,2 BELIMO BEN
- 79 0,0429 14,6 BELIMO BEN 15,1 BELIMO BFN 15,6 BELIMO BEN
- 86,5 0,0457 15 BELIMO BEN 15,5 BELIMO BFN 16 BELIMO BEN
-
106,5
0,0531 15,9 BELIMO BEN 16,4 BELIMO BFN 16,9 BELIMO BEN
- 129 0,0614 16,9 BELIMO BEN 17,4 BELIMO BFN 17,9 BELIMO BEN
- 154 0,0707 18 BELIMO BEN 18,5 BELIMO BFN 19 BELIMO BEN
- 179 0,0799 19,1 BELIMO BEN 19,6 BELIMO BFN 20,1 BELIMO BEN
- 204 0,0892 20,3 BELIMO BEN 20,8 BELIMO BFN 21,3 BELIMO BEN
- 209 0,0910 20,5 BELIMO BEN 21 BELIMO BFN 21,5 BELIMO BEN

20
- 229 0,0984 21,4 BELIMO BEN 21,9 BELIMO BFN 22,4 BELIMO BEN
- 244 0,1040 22,1 BELIMO BEN 22,6 BELIMO BFN 23,1 BELIMO BEN
9 254 0,1077 22,5 BELIMO BEN 23 BELIMO BFN 23,5 BELIMO BEN
34 279 0,1169 23,6 BELIMO BEN 26
JOVENTA DAFx.20S
24,6 BELIMO BEN
39 284 0,1188 23,9 BELIMO BEN 26,2
JOVENTA DAFx.20S
24,9 BELIMO BEN
59 304 0,1262 24,8 BELIMO BEN 27,1
JOVENTA DAFx.20S
25,8 BELIMO BEN
84 329 0,1354 25,9 BELIMO BEN 28,2
JOVENTA DAFx.20S
26,9 BELIMO BEN
- 19 0,0235 12,4 BELIMO BEN 12,9 BELIMO BFN 13,4 BELIMO BEN
- 29 0,0277 12,8 BELIMO BEN 13,3 BELIMO BFN 13,8 BELIMO BEN
- 41,5 0,0330 13,4 BELIMO BEN 13,9 BELIMO BFN 14,4 BELIMO BEN
- 54 0,0382 14 BELIMO BEN 14,5 BELIMO BFN 15 BELIMO BEN
- 69 0,0445 14,7 BELIMO BEN 15,2 BELIMO BFN 15,7 BELIMO BEN
- 79 0,0487 15,2 BELIMO BEN 15,7 BELIMO BFN 16,2 BELIMO BEN
- 86,5 0,0519 15,6 BELIMO BEN 16,1 BELIMO BFN 16,6 BELIMO BEN
-
106,5
0,0603 16,5 BELIMO BEN 17 BELIMO BFN 17,5 BELIMO BEN
- 129 0,0697 17,6 BELIMO BEN 18,1 BELIMO BFN 18,6 BELIMO BEN
- 154 0,0802 18,7 BELIMO BEN 19,2 BELIMO BFN 19,7 BELIMO BEN
- 179 0,0907 19,9 BELIMO BEN 20,4 BELIMO BFN 20,9 BELIMO BEN
- 204 0,1012 21,1 BELIMO BEN 21,6 BELIMO BFN 22,1 BELIMO BEN
- 209 0,1033 21,3 BELIMO BEN 21,8 BELIMO BFN 22,3 BELIMO BEN
- 229 0,1117 22,3 BELIMO BEN 22,8 BELIMO BFN 23,3 BELIMO BEN
- 244 0,1180 23 BELIMO BEN 25,3
JOVENTA DAFx.20S
24 BELIMO BEN
9 254 0,1222 23,4 BELIMO BEN 25,8
JOVENTA DAFx.20S
24,4 BELIMO BEN
34 279 0,1327 24,6 BELIMO BEN 26,9
JOVENTA DAFx.20S
25,6 BELIMO BEN
39 284 0,1348 24,9 BELIMO BEN 27,2
JOVENTA DAFx.20S
25,9 BELIMO BEN
59 304 0,1432 25,8 BELIMO BEN 28,1
JOVENTA DAFx.20S
26,8 BELIMO BEN
84 329 0,1537 27 BELIMO BEN 29,3
JOVENTA DAFx.20S
28 BELIMO BEN
- 19 0,0263 12,8 BELIMO BEN 13,3 BELIMO BFN 13,8 BELIMO BEN
- 29 0,0310 13,3 BELIMO BEN 13,8 BELIMO BFN 14,3 BELIMO BEN
- 41,5 0,0369 13,9 BELIMO BEN 14,4 BELIMO BFN 14,9 BELIMO BEN
- 54 0,0428 14,6 BELIMO BEN 15,1 BELIMO BFN 15,6 BELIMO BEN
- 69 0,0498 15,3 BELIMO BEN 15,8 BELIMO BFN 16,3 BELIMO BEN
- 79 0,0545 15,8 BELIMO BEN 16,3 BELIMO BFN 16,8 BELIMO BEN
- 86,5 0,0580 16,1 BELIMO BEN 16,6 BELIMO BFN 17,1 BELIMO BEN
-
106,5
0,0674 17,1 BELIMO BEN 17,6 BELIMO BFN 18,1 BELIMO BEN
- 129 0,0780 18,2 BELIMO BEN 18,7 BELIMO BFN 19,2 BELIMO BEN
- 154 0,0898 19,4 BELIMO BEN 19,9 BELIMO BFN 20,4 BELIMO BEN
- 179 0,1015 20,7 BELIMO BEN 21,2 BELIMO BFN 21,7 BELIMO BEN
- 204 0,1133 21,9 BELIMO BEN 22,4 BELIMO BFN 22,9 BELIMO BEN
- 209 0,1156 22,1 BELIMO BEN 22,6 BELIMO BFN 23,1 BELIMO BEN
- 229 0,1250 23,1 BELIMO BEN 25,4
JOVENTA DAFx.20S
24,1 BELIMO BEN
- 244 0,1321 23,8 BELIMO BEN 26,2
JOVENTA DAFx.20S
24,8 BELIMO BEN
9 254 0,1368 24,3 BELIMO BEN 26,7
JOVENTA DAFx.20S
25,3 BELIMO BEN
34 279 0,1485 25,6 BELIMO BEN 27,9
JOVENTA DAFx.20S
26,6 BELIMO BEN
39 284 0,1509 25,8 BELIMO BEN 28,1
JOVENTA DAFx.20S
26,8 BELIMO BEN
59 304 0,1603 26,8 BELIMO BEN 29,1
JOVENTA DAFx.20S
27,8 BELIMO BEN
84 329 0,1720 28 BELIMO BEN 30,3
JOVENTA DAFx.20S
29 BELIMO BEN
- 19 0,0297 13,4 BELIMO BEN 13,9 BELIMO BFN 14,4 BELIMO BEN
- 29 0,0350 13,9 BELIMO BEN 14,4 BELIMO BFN 14,9 BELIMO BEN
- 41,5 0,0416 14,5 BELIMO BEN 15 BELIMO BFN 15,5 BELIMO BEN
- 54 0,0482 15,2 BELIMO BEN 15,7 BELIMO BFN 16,2 BELIMO BEN
- 69 0,0562 15,9 BELIMO BEN 16,4 BELIMO BFN 16,9 BELIMO BEN
- 79 0,0615 16,5 BELIMO BEN 17 BELIMO BFN 17,5 BELIMO BEN
- 86,5 0,0655 16,8 BELIMO BEN 17,3 BELIMO BFN 17,8 BELIMO BEN
-
106,5
0,0761 17,9 BELIMO BEN 18,4 BELIMO BFN 18,9 BELIMO BEN
Other manuals for MSD
3
Table of contents
Other Mandik Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

Lindab
Lindab WK45 Series Technical manual

Ingersoll-Rand
Ingersoll-Rand ARO SB30 Series Operator's manual

pottorff
pottorff BD-50-SS installation instructions

Comfort365
Comfort365 WLDCK installation manual

Specified Technologies
Specified Technologies EZ PATH Installation sheet

klimaoprema
klimaoprema FDC Series product manual

VENCO
VENCO ES Series Installation, operation and maintenance manual

KOOLAIR
KOOLAIR SAFEAIR BDK60 Technical documentation

Swegon
Swegon actionair FireShield manual

Nailor
Nailor 0714 OPERATIONS AND MAINTENANCE PROCEDURES

Swegon
Swegon REACT Pa Instructions for use

actionair
actionair Smoke/Shield PTC Installation and operating instructions