EM-0489 Rev.2 P. 1 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
CONTROL OUTPUT ISOLATOR MODEL 18KYC
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 50mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Body
Specifications
Front Cover
(Connection diagram
behind)
■FRONT VIEW (with cover open)
• Without Power Switch
Span Adj.
Zero Adj.
1
78
56
2
34
• With Power Switch
Power Switch
Span Adj.
Zero Adj.
1
78
56
2
34
ON
OFF
INSTALLATION
Use Standard Rack (model: 18KBXx).
18KYC
EM-0489 Rev.2 P. 2 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram behind the front cover.
■EXTERNAL DIMENSIONS unit: mm (inch)
110 (4.33 )
93 (3.66)
24 (.94)
7 (.28)
78 (3.07)32 (1.26)
8–M3.5
SCREW
7 (.28)
2–M3
SCREW
■CONNECTION DIAGRAM
5
6
1
2
DCS OUTPUT
+
−
INPUT MONITOR
1
2
OUTPUT
+
−
Use either of module or external field terminals.
To External
Field Terminals
(Section A)
Module
Field Terminals
(Section A)
CONNECTOR
Section A. Field Terminals
POWER
■TERMINAL ASSIGNMENTS
12
34
78
56
18KYC
EM-0489 Rev.2 P. 3 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage supplied to the rack
(model: 18KBXx). For the DC power source, be sure that
the ripple level is within 10% p-p.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.

Other MG Control Unit manuals

MG R30NCIT1 User manual

MG

MG R30NCIT1 User manual

MG R80YVT4N User manual

MG

MG R80YVT4N User manual

MG R7E-EA16 User manual

MG

MG R7E-EA16 User manual

MG R7ML-EA8 User manual

MG

MG R7ML-EA8 User manual

MG R3-CT4B User manual

MG

MG R3-CT4B User manual

MG R3-AS8 User manual

MG

MG R3-AS8 User manual

MG R5-RS1A User manual

MG

MG R5-RS1A User manual

MG R80DAT16A2 User manual

MG

MG R80DAT16A2 User manual

MG R7L-EC16B User manual

MG

MG R7L-EC16B User manual

MG R7L-EA16 User manual

MG

MG R7L-EA16 User manual

MG R3Y-SS8N User manual

MG

MG R3Y-SS8N User manual

MG R7LWTU User manual

MG

MG R7LWTU User manual

MG R6S-SV2 User manual

MG

MG R6S-SV2 User manual

MG R7L-EC16A User manual

MG

MG R7L-EC16A User manual

MG R6S-SS2 User manual

MG

MG R6S-SS2 User manual

MG R3S-YS4 User manual

MG

MG R3S-YS4 User manual

MG R3-YS4 User manual

MG

MG R3-YS4 User manual

MG 10BW User manual

MG

MG 10BW User manual

MG R7K4FML-6-DC32B User manual

MG

MG R7K4FML-6-DC32B User manual

MG R30US4 User manual

MG

MG R30US4 User manual

MG R7F4HC-DAC32C-K User manual

MG

MG R7F4HC-DAC32C-K User manual

MG R6-NE2 User manual

MG

MG R6-NE2 User manual

MG R8-SST8 User manual

MG

MG R8-SST8 User manual

MG R7L-YS2 User manual

MG

MG R7L-YS2 User manual

Popular Control Unit manuals by other brands

Nexo GEO S12 EN54 Series System manual

Nexo

Nexo GEO S12 EN54 Series System manual

Firmtech FB155BC datasheet

Firmtech

Firmtech FB155BC datasheet

Baker Hughes Masoneilan 35002 Series Camflex II instruction manual

Baker Hughes

Baker Hughes Masoneilan 35002 Series Camflex II instruction manual

Edwards 3-ASU Installation sheet

Edwards

Edwards 3-ASU Installation sheet

TOPP TF24R Installation and use instructions

TOPP

TOPP TF24R Installation and use instructions

NI SCC Series quick start guide

NI

NI SCC Series quick start guide

Burkert 3363 quick start

Burkert

Burkert 3363 quick start

KROHNE ESK4 Series Supplementary instructions

KROHNE

KROHNE ESK4 Series Supplementary instructions

PRASTEL M2000PE quick start guide

PRASTEL

PRASTEL M2000PE quick start guide

Bray RF15 Installation and maintenance manual

Bray

Bray RF15 Installation and maintenance manual

saia-burgess PCD3 Series Hardware manual

saia-burgess

saia-burgess PCD3 Series Hardware manual

Quectel GNSS Module Series user guide

Quectel

Quectel GNSS Module Series user guide

ABNOX AXDV-V1-SV Translation of the original operating manual

ABNOX

ABNOX AXDV-V1-SV Translation of the original operating manual

Vag GA INDYSTRIES FIGURE 929SS Installation, operation and maintenance manual

Vag

Vag GA INDYSTRIES FIGURE 929SS Installation, operation and maintenance manual

Fastwel CPB904 user manual

Fastwel

Fastwel CPB904 user manual

iseg EBS Technical documentation

iseg

iseg EBS Technical documentation

Yoshitake PD-1 manual

Yoshitake

Yoshitake PD-1 manual

GE CR194 installation instructions

GE

GE CR194 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.