manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. MG
  6. •
  7. Control Unit
  8. •
  9. MG R3S-YS4 User manual

MG R3S-YS4 User manual

Other MG Control Unit manuals

MG Devicenet R7F4DD-DA16A-H User manual

MG

MG Devicenet R7F4DD-DA16A-H User manual

MG R7K4FML3-6-DAC32A User manual

MG

MG R7K4FML3-6-DAC32A User manual

MG R3Y-SS8N User manual

MG

MG R3Y-SS8N User manual

MG R5-RS1A User manual

MG

MG R5-RS1A User manual

MG R80YVT4N User manual

MG

MG R80YVT4N User manual

MG R3-YS4 User manual

MG

MG R3-YS4 User manual

MG R80DAT16A2 User manual

MG

MG R80DAT16A2 User manual

MG JFK User manual

MG

MG JFK User manual

MG R7E-EC16A User manual

MG

MG R7E-EC16A User manual

MG R5-SS1A User manual

MG

MG R5-SS1A User manual

MG R8-SST8 User manual

MG

MG R8-SST8 User manual

MG R7L-YS2 User manual

MG

MG R7L-YS2 User manual

MG R30NCIT1 User manual

MG

MG R30NCIT1 User manual

MG R3-CT4B User manual

MG

MG R3-CT4B User manual

MG R6-NE2 User manual

MG

MG R6-NE2 User manual

MG R7L-EA16 User manual

MG

MG R7L-EA16 User manual

MG R3-NCIE1 User manual

MG

MG R3-NCIE1 User manual

MG R3-CT4B User manual

MG

MG R3-CT4B User manual

MG R7LWTU User manual

MG

MG R7LWTU User manual

MG R6D-SS2 User manual

MG

MG R6D-SS2 User manual

MG R3-AS8 User manual

MG

MG R3-AS8 User manual

MG R6S-SV2 User manual

MG

MG R6S-SV2 User manual

MG R3-DC64C User manual

MG

MG R3-DC64C User manual

MG 18KYC User manual

MG

MG 18KYC User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

EM-8939 Rev.2 P. 1 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
DC CURRENT OUTPUT MODULE
(4 points, isolated, tension clamp terminal block) MODEL R3S-YS4
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
DC current output module..................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■HOT SWAPPABLE MODULES
• Replacing the module does not affect other modules on
the same base. Thus, the module can be replaced while
the power is ON. However, replacing multiple modules
at once may greatly change live voltage levels. We highly
recommend to replace them one by one.
■GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■UNUSED OUTPUT CHANNEL
• Close across the unused output terminals or set unused
channels to “unused” with PC Configurator software
(model: R3CON).
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
R3S-YS4
EM-8939 Rev.2 P. 2 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
1
20
RUN LED
ERR LED
■ FRONT VIEW ■ SIDE VIEW
SW3
4
3
2
1Output
Hold
ON
■STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with output abnormality;
Green in normal operating conditions.
■SIDE DIP SW
• Output Hold: SW31
SW OUTPUT HOLD
HOLD (*)OFF
SW3-1 OFF ON
(*) Factory setting
Note: Be sure to set unused SW3-2 through 3-4 to OFF.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■CHANNEL INDIVIDUAL SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Zero Scale -32000 to +32000 0
Full Scale -32000 to +32000 10000
Zero Adjust -320.00 to +320.00 0.00
Full Adjust -32000 to +32000 1.0000
Unused 0: Enable
1: Disable
0: Enable
R3S-YS4
EM-8939 Rev.2 P. 3 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
1
20
130 (5.12)
27.5 (1.08) 109 (4.29)
120 (4.72)
POSITIONING
GUIDE
■CONNECTION DIAGRAM
INTERNAL BUS A
*1INTERNAL BUS B
Unused channels left open are equal to the wire breakdown,
which turns the red ERR LED on and sets a burnout flag at
the PLC or the host device.
Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing to
short at the field terminals.
• Unused Output Channels
Close across the unused output terminals as shown below.
*1. For dual redundant communication.
*2. To
use shield line, connect it to SLD terminal and ground the terminal 20.
Note: Do not use void terminals.
1
2
INTERNAL POWER
+
–
OUTPUT 1
5
6
+
–
OUTPUT 2
11
12
+
–
OUTPUT 3
15
16
+
–
OUTPUT 4
1
2
OUTPUT 1
Cross-wire
5
6
OUTPUT 2
11
12
OUTPUT 3
15
16
OUTPUT 4
SLD
SLD
SLD
SLD
SLD
SLD
*2
4
8
18
19
20
14
BUS CONNECTOR
R3S-YS4
EM-8939 Rev.2 P. 4 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
WIRING INSTRUCTIONS
■APPLICABLE WIRE SIZE
• Solid: 0.2 to 1.0 mm2(0.55 to 1.12 dia.)
• Stranded: 0.2 to 1.5 mm2
(Tinning wire ends may cause contact failure and therefore
is not recommended.)
• Ferruled:
Unsheathed: 0.25 to 1.5 mm2
Sheathed: 0.25 to 0.75 mm2
• Expose wire conductors by 10 mm (0.39”).
Stripped length
10mm
■CONNECTION PROCEDURE
Insert the wire end until it comes to a full stop while push-
ing slot with the tip of a screw driver as shown below. Be
sure wire insulation is not inside the terminal.
Screw Driver
Power wire
OUTPUT PIN ASSIGNMENT
PIN No. FUNCTION
1 I1
2 COM1
3 NC
4 SLD
5 I2
6 COM2
7 NC
8 SLD
9 NC
10 NC
11 I3
12 COM3
13 NC
14 SLD
15 I4
16 COM4
17 NC
18 SLD
19 SLD
20 SLD
FUNCTIONS
■OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
• Output Hold
If both are in error, the module holds the signal and stands
by until one of the communications recovers.
• Output OFF
If both are in error, the module outputs -15 % and stands by
until one of the communications recovers.
At the startup, it outputs -15 % until the communication is
established and normal data is received.