MG R3Y-YS4 User manual

Other MG Control Unit manuals

MG R3-DC32C User manual

MG

MG R3-DC32C User manual

MG R7L-YS2 User manual

MG

MG R7L-YS2 User manual

MG R6-NE2 User manual

MG

MG R6-NE2 User manual

MG R7E-EC16A User manual

MG

MG R7E-EC16A User manual

MG 10BW User manual

MG

MG 10BW User manual

MG R30NCIT1 User manual

MG

MG R30NCIT1 User manual

MG R3-DC64C User manual

MG

MG R3-DC64C User manual

MG R7E-EA16 User manual

MG

MG R7E-EA16 User manual

MG R7L-EA16 User manual

MG

MG R7L-EA16 User manual

MG R7E-EC16B User manual

MG

MG R7E-EC16B User manual

MG R5-RS1A User manual

MG

MG R5-RS1A User manual

MG R6S-TS2A User manual

MG

MG R6S-TS2A User manual

MG R7L-EC16A User manual

MG

MG R7L-EC16A User manual

MG R7F4HC-DAC32C-K User manual

MG

MG R7F4HC-DAC32C-K User manual

MG R80YVT4N User manual

MG

MG R80YVT4N User manual

MG M8YCH User manual

MG

MG M8YCH User manual

MG R3-AS8 User manual

MG

MG R3-AS8 User manual

MG R3-YS4 User manual

MG

MG R3-YS4 User manual

MG 18KYC User manual

MG

MG 18KYC User manual

MG R7LWTU User manual

MG

MG R7LWTU User manual

MG R8-SV4N User manual

MG

MG R8-SV4N User manual

MG R5-TS1A User manual

MG

MG R5-TS1A User manual

MG R5-SS1A User manual

MG

MG R5-SS1A User manual

MG Devicenet R7F4DD-DA16A-H User manual

MG

MG Devicenet R7F4DD-DA16A-H User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

EM-8961 Rev.5 P. 1 / 3
INSTRUCTION MANUAL
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
DC current output module..................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■HOT SWAPPABLE MODULES
• Replacing the module does not affect other modules on
the same base. Thus, the module can be replaced while
the power is ON. However, replacing multiple modules
at once may greatly change live voltage levels. We highly
recommend to replace them one by one.
■GENERAL PRECAUTIONS
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■UNUSED OUTPUT CHANNEL
• Close across the unused output terminals or set unused
channels to “unused” with PC Configurator software
(model:R3CON).
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
DC CURRENT OUTPUT MODULE
(4 points, isolated, connector type) MODEL R3Y-YS4
R3Y-YS4
EM-8961 Rev.5 P. 2 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
B
20
A
20
B
1
A
1
RUN LED
ERR LED
Output Connector
■ FRONT VIEW
• Pin Assignment
■ SIDE VIEW
SW3
4
3
2
1Output
Hold
■STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with output abnormality;
Green in normal operating conditions.
■SIDE DIP SW
• Output Hold: SW3-1
SW OUTPUT HOLD
HOLD (*)OFF
SW3-1 OFF ON
(*) Factory setting
Note: Be sure to set unused SW3-2 through 3-4 to OFF.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■CHANNEL INDIVIDUAL SETTING
PARAMETER AVAILABLE RANGE DEFAULT SETTING
Zero Scale -32000 to +32000 0
Full Scale -32000 to +32000 10000
Zero Adjust -320.00 to +320.00 0.00
Full Adjust -32000 to +32000 1.0000
Unused 0: Enable
1: Disable
0: Enable
R3Y-YS4
EM-8961 Rev.5 P. 3 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
130 (5.12)
27.5 (1.08) 110 (4.33)
POSITIONING
GUIDE
■CONNECTION DIAGRAM
INTERNAL BUS A
*INTERNAL BUS B
+
–
+
–
+
–
+
–
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
INTERNAL POWER
BUS CONNECTOR
20A/20B
6A /6B
8A /8B
4A /4B
10A/10B
14A/14B
16A/16B
18A/18B
*For dual redundant communication.
• Unused Output Channels
Close across the unused output terminals as shown below.
20A / 20B
18A / 18B
OUTPUT 1
16A / 16B
14A / 14B
OUTPUT 2
10A / 10B
8A / 8B
OUTPUT 3
6A / 6B
4A / 4B
OUTPUT 4
Unused channels left open are equal to the wire breakdown,
which turns the red ERR LED on and sets a burnout flag at
the PLC or the host device.
Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing to
short at the field terminals.
OUTPUT CONNECTOR (40-pin)
PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT
1A NC 1B NC
2A NC 2B NC
3A NC 3B NC
4A – OUT4 4B – OUT4
5A NC 5B NC
6A + OUT4 6B + OUT4
7A NC 7B NC
8A – OUT3 8B – OUT3
9A NC 9B NC
10A + OUT3 10B + OUT3
11A NC 11B NC
12A NC 12B NC
13A NC 13B NC
14A – OUT2 14B – OUT2
15A NC 15B NC
16A + OUT2 16B + OUT2
17A NC 17B NC
18A – OUT1 18B – OUT1
19A NC 19B NC
20A + OUT1 20B + OUT1
FUNCTIONS
■OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from
the preferred bus A.
When an error is detected, the output is switched to the
data from the bus B.
• Output Hold
If both are in error, the module holds the signal and
stands by until one of the communications recovers.
• Output OFF
If both are in error, the module outputs -15 % and stands
by until one of the communications recovers.
At the startup, it outputs -15 % until the communication
is established and normal data is received.