MG R7F4HC-DAC32C-K User manual

EM-8009-B Rev.2 P. 1 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Discrete I/O module ............................................................(1)
DIN rail mounter slider......................................................(2)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
■CSP+ le
CSP+ file is downloadable at our web site or CC-Link Part-
ner Association’s web site (https://www.cc-link.org).
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures* to ensure the CE con-
formity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, ≤ 50 mA
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and I/O signal for safety.
• Before you remove the connector or mount it, make sure
to turn off the power supply and I/O signal for safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• With vertical mounting, for heat dissipation leave at least
10 mm (.39 in.) at the both side of the unit.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
CC-Link I/O MODULE
(NPN/PNP discrete input, NPN discrete output,
16 points each, FCN connector)
MODEL
R7F4HC-DAC32C-K

R7F4HC-DAC32C-K
EM-8009-B Rev.2 P. 2 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
Terminator DIP SW
Discrete I/O
Status Indicator LED
A20
B20
A1
B1
SW1
PowerError RD
1234
×10 ×1
STATION ADD.
SLD
FE 21 DB
3DG
4DA
5
NC
NC 45 FE1
3
PWR
-
2
PWR
+
1
RunSD
Connector for Power Supply
CC-Link Connector
I/O Connector
Station Address
Setting Rotary SW
Operation Mode Setting
DIP SW (SW1)
Status Indicator LED
■TOP VIEW
■FRONT VIEW
■STATUS INDICATOR LED
ID
S TAT U S
COLOR FUNCTION
Power ON Green Internal 5V power is in normal
status.
Run ON Green The refresh data is received
normally
Error ON Red The received data is abnormal.
SD ON Green The module is transmitting.
RD ON Green The module is receiving.
■DISCRETE I/O STATUS INDICATOR LED
Green LED shows the I/O status.
ON : LED ON
OFF : LED OFF
■STATION ADDRESS
The left switch determines the tenth place digit, while the
right one does the ones place digit of the station address
(1 - 64).
(Factory setting: 00)
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Station Address Setting (x1)
Station Address Setting (x10)
■OPERATING MODE
(*) Factory setting
• Read Rate (SW1-1, 1-2, 1-3)
BAUD RATE SW1
123
0: 156 kbps (*) OFF OFF OFF
1: 625 kbps ON OFF OFF
2: 2.5 Mbps OFF ON OFF
3: 5 Mbps ON ON OFF
4: 10 Mbps OFF OFF ON
• OUTPUT AT THE LOSS OF COMMUNICATION (SW1-4)
OUTPUT AT THE LOSS OF COMMUNICATION
SW1
4
Output clear (output OFF) OFF
Hold the output (*)
(maintains the last data received normally)
ON
■TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFF to invalidate. (Factory setting OFF)

R7F4HC-DAC32C-K
EM-8009-B Rev.2 P. 3 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■
CC-Link, POWER SUPPLY ASSIGNEMENT
Unit side connect
or: MC1,5/5-GF-3,5 (Phoenix Contact)
Ca
ble side connector: TFMC1,5/5-STF-3,5 (Phoenix Contact)
Aplicab
le wire size: 0.2 - 1.5mm2, stripped length 10mm
AI0,25-1
0YE 0.25mm2(Phoenix Contact)
A0,34-1
0TQ 0.34mm2(Phoenix Contact)
AI0,5-1
0WH 0.5mm2(Phoenix Contact)
AI0,75-1
0GY 0.75mm2(Phoenix Contact)
AI1
-10 1.0mm2(Phoenix Contact)
AI1,5-1
0 1.5mm2(Phoenix Contact)
· CC-Link
12345
NO.ID FUNCTION
1FEFunctional earth
2 SLD Shield
3DB DB (white)
4DG DG (yellow)
5DADA (blue)
· POWER SUPPLY
12345
NO.ID FUNCTION
1 PWR+ Power supply +
2 PWR- Power supply -
3 FE1 Grounding
4NCUnused
5NCUnused
Not
e: The numbers marked on the connector have no relationship to the pin number of the unit.
Wire according to the instruction manual of the unit.
■
I/O, SENSOR EXC. ASSIGNMENT
Unit side connect
or: N365P040AU (OTAX) (FCN-365P040-AU (Fujitsu)...discontinued)
Ca
ble side connector: N36( )J040AU(OTAX) (FCN-36( )J040-AU (Fujitsu)...discontinued)
(The cable connector is not included in the package. Specify wire size instead of ( ); refer to the specifications of the product)
B20
A20
B1
A1
PIN NO.ID FUNCTION PIN NO.ID FUNCTION
A1 VS+ Exc. supply +B1 VS+ Exc. supply +
A2 VS- Exc. supply -B2 VS- Exc. supply -
A3 Y15 Output 15 B3 Y7 Output 7
A4 Y14 Output 14 B4 Y6 Output 6
A5 Y13 Output 13 B5 Y5 Output 5
A6 Y12 Output 12 B6 Y4 Output 4
A7 Y11 Output 11 B7 Y3 Output 3
A8 Y10 Output 10 B8 Y2 Output 2
A9 Y9 Output 9B9Y1 Output 1
A10Y8 Output 8B10 Y0 Output 0
A11NCUnused B11NCUnused
A12 COM Common B12 COM Common
A13X15 Input 15 B13X7 Input 7
A14X14 Input 14 B14X6 Input 6
A15X13 Input 13 B15X5 Input 5
A16X12 Input 12 B16X4 Input 4
A17X11 Input 11 B17X3 Input 3
A18X10 Input 10 B18X2 Input 2
A19X9 Input 9B19 X1 Input 1
A20 X8 Input 8 B20 X0 Input 0

R7F4HC-DAC32C-K
EM-8009-B Rev.2 P. 4 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MOUNTING INSTRUCTIONS
■DIN RAIL MOUNTING (PARALLEL)
• Mounting
A)Set the upper hook at the rear side of the unit on the DIN
rail.
B)Push in the lower.
A
B
• Dismounting
A)Push down the DIN rail mounter slider with tip of a mi-
nus screwdriver.
B)Pull the lower of the unit.
C)Remove the upper hook of the unit from the DIN rail.
A
C
B
■DIN RAIL MOUNTING (RIGHT ANGLE)
• Mounting
A)Insert the longer DIN rail mounter slider until it clicks
twice, as shown below.
A
B)Set the upper hook at the rear side of the unit on the DIN
rail.
C)Push in the lower.
B
C
Note: leave at least 10 mm (.39 in.) at the both side of the unit.
• Dismounting
A)Push down the DIN rail mounter slider with tip of a mi-
nus screwdriver.
B)Pull the lower of the unit.
C)Remove the upper hook of the unit from the DIN rail.
C
A
B
■SURFACE MOUNTING
A)Insert the two DIN rail mounter sliders until it clicks
once, as shown below.
A
A
B)Mount the unit with M4 screws referring the External
Dimensions. (Torque: 1.4 N∙m)

R7F4HC-DAC32C-K
EM-8009-B Rev.2 P. 5 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm [inch]
115 [4.53] 55 [2.17]
72 [2.83]
123 [4.84]
138 [5.43]
50 [1.97]
5 [.20]3 [.12]
DIN rail
(35mm wide)
(4 [.16])
2-4.3 [.17] dia. 4 [.16] deep

R7F4HC-DAC32C-K
EM-8009-B Rev.2 P. 6 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.
B10
B6
B7
B8
B9
B5
A17
A18
A19
A20
A16
A12
A13
A14
A15
A11
A7
A8
A9
A10
A6
A5
B20
B16
B17
B18
B19
B15
B11
B12
B13
B14
B4
B1
B2
B3
A1
A2
A3
A4
X0
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
X14
X15
Y1
Y2
Y3
Y4
Y5
Y6
Y7
Y8
Y9
Y10
Y11
Y12
Y13
Y14
Y15
Y0
COM
+–
+–
VS+
VS+
VS–
VS–
COM
3
4
1
2
5
3
4
1
2
5
PWR–
PWR+
PWR–
PWR+
–
+
FE1
NC
NC
FE1
NC
NC
+
–
DA
DG
DB
SLD
FE
To other
CC-link device
POWER (IN)
POWER (OUT)
Exc. supply

R7F4HC-DAC32C-K
EM-8009-B Rev.2 P. 7 / 7
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
MOUNTING REQUIREMENTS unit: mm (inch)
125 [4.92]
2-M4
DATA ALLOCATION
F
RX (n+0) F - RX (n+0) 0
Unused
Interval timed Response (X)
0
1F
F
Refresh Data (Y)
0
1F
Unused
RY (n+1) F - RY (n+1) 0
I/O DATA DESCRIPTIONS
■DISCRETE I/O
015
Input 0 (Output 0)
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
Input 15 (Output 15)
0: OFF / 1: ON
0: OFF / 1: ON
0: OFF / 1: ON
0: OFF / 1: ON
0: OFF / 1: ON
COMMUNICATION CABLE WIRING
DA
DB
DG
SLD
FG
Master module
DA
DB
DG
SLD
FG
R7F4HC
DA
DB
DG
SLD
FG
R7F4HC
*1Terminating
Resistor
blue
white
yellow
*1. Turn on the terminator DIP switch to activate the internal terminating resistor.
■MASTER CONNECTION
*1Terminating
Resistor
Table of contents