EM-5012 Rev.17 P. 1 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
Mini-M™
THERMOCOUPLE TRANSMITTER MODEL M2TS
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner (body + base socket + CJC sensor)......(1)
Sealing label (option /VN).........................................(1 sheet)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■WARNING
• If the equipment is used in a manner not specified by this
manual, the protection provided by the equipment may
be impaired.
■NONINCENDIVE APPROVAL OPTION
• This equipment is suitable for use in Class I, Div. 2,
Groups A, B, C and D or Non-Hazardous Locations only.
• WARNING! Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
• WARNING! – Explosion Hazard –
Substitution of Components May Impair Suitability for
Class I, Div. 2.
• WARNING! – Explosion Hazard –
Do Not Disconnect Equipment Unless Power Has Been
Switched Off or The Area is Known To Be Non-Hazardous.
• The equipment was evaluated for use in the ambient tem-
perature and relative humidity as mentioned in ‘ENVI-
RONMENT’ section.
• The input and output wiring must be in accordance with
Class I, Div. 2 wiring methods and in accordance with the
authority having jurisdiction for use in these hazardous
locations.
■CONFORMITY WITH EU DIRECTIVES, UK LEGISLATION OR UL
• This equipment is suitable for Pollution Degree 2 and In-
stallation Category II (transient voltage 2500V). Rein-
forced insulation (signal input or output to power input:
300V) and basic insulation (signal input to output: 300V)
are maintained. Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.
• The equipment must be mounted inside a suitable fire
enclosure.
• Altitude up to 2000 meters.
• Insert noise filters for the power source, input and output
connected to the unit. COSEL Model NAC-04-472, TDK
Model ZCAT 3035-1330 or equivalent is recommended.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE/UKCA/UL requirements. Failure to observe
these requirements may invalidate the CE/UKCA/UL
conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in a
panel system. The user may have to review the CE/UKCA
requirements in regard to the whole system and employ
additional protective measures* to ensure the CE/UKCA
conformity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V and 85 – 264V AC rating: 85 – 264V
(90 – 264V for UL), 47 – 66 Hz, approx. 3 – 5VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W
■GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
• With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to
endure it without breakdown, however, it may shorten ap-
propriate life duration.
M2TS
EM-5012 Rev.17 P. 2 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
CJC
Sensor
Model
SPAN
ZERO
Zero Adj.
Span Adj.
Body Base Socket
Connection
Diagram
Specifications
Fixing Screw
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
Attach the CJC sensor together with input wiring to the input terminals. The CJC sensor is not interchangeable. Check that
its serial number is identical to that of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
5
9
21.5 (.85)
70.5 (2.78)
84 (3.31)10 (.39) 15 (.59)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
• When mounting, no extra space is needed between units.
4
8
12
14 13
1
4 (.16)
■CONNECTION DIAGRAM
1
+
–
T / C
CJC
SENSOR
metal leg
model: CJM
comp. leadwire
5
4
+
–
+
–
OUTPUT
9
12
U(+)
V(–)
POWER
13
14
■TERMINAL ASSIGNMENTS unit: mm (inch)
8
9
12
14 13
CJC SENSOR
(model: CJM)
14 (.55)
1 14
5
M2TS
EM-5012 Rev.17 P. 3 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
13 – 14 with a multimeter.
3) Input: Check that the input voltage is within 0 – 100% of
full-scale.
If the thermocouple or its extension wires are broken, the
output goes over 100% (below 0% with downscale) due to
burnout function. Check leadwires in such a case.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
Note: Remove the sealing label for /VN option.
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.

Other MG Transmitter manuals

MG M3-UNIT Series User manual

MG

MG M3-UNIT Series User manual

MG M6NWVS User manual

MG

MG M6NWVS User manual

MG 10RS User manual

MG

MG 10RS User manual

MG M3SVS User manual

MG

MG M3SVS User manual

MG KWRS2 User manual

MG

MG KWRS2 User manual

MG M3-UNIT Series User manual

MG

MG M3-UNIT Series User manual

MG B5MS User manual

MG

MG B5MS User manual

MG HR User manual

MG

MG HR User manual

MG Mini-M M2CA User manual

MG

MG Mini-M M2CA User manual

MG 17PE User manual

MG

MG 17PE User manual

MG M6DCTC User manual

MG

MG M6DCTC User manual

MG M6SWVS User manual

MG

MG M6SWVS User manual

MG M6SXM User manual

MG

MG M6SXM User manual

MG M6NVF User manual

MG

MG M6NVF User manual

MG BR User manual

MG

MG BR User manual

MG M60EWVS User manual

MG

MG M60EWVS User manual

MG 10JRE User manual

MG

MG 10JRE User manual

MG SVF User manual

MG

MG SVF User manual

MG W5VS User manual

MG

MG W5VS User manual

MG W5TS User manual

MG

MG W5TS User manual

MG M6NPA User manual

MG

MG M6NPA User manual

MG 18JPA User manual

MG

MG 18JPA User manual

MG W5LCS User manual

MG

MG W5LCS User manual

MG Mini-M M2VF3 User manual

MG

MG Mini-M M2VF3 User manual

Popular Transmitter manuals by other brands

Vega VEGABAR 86 operating instructions

Vega

Vega VEGABAR 86 operating instructions

rojaflex RHSM1 Original assembly and operating instructions

rojaflex

rojaflex RHSM1 Original assembly and operating instructions

Kramer VP-200XLT user manual

Kramer

Kramer VP-200XLT user manual

ADEMCO 5869 Installation and setup guide

ADEMCO

ADEMCO 5869 Installation and setup guide

Mutec MTP200ib-E manual

Mutec

Mutec MTP200ib-E manual

M-system B5RS instruction manual

M-system

M-system B5RS instruction manual

SKF CMPT CTU instruction manual

SKF

SKF CMPT CTU instruction manual

Jensen JEN99BT3BCF4 user manual

Jensen

Jensen JEN99BT3BCF4 user manual

Inovonics Frequency Agile FA200W installation instructions

Inovonics

Inovonics Frequency Agile FA200W installation instructions

Evikon PluraSens E2611-NH3 user manual

Evikon

Evikon PluraSens E2611-NH3 user manual

AirLink Communications PinPoint CDMA user guide

AirLink Communications

AirLink Communications PinPoint CDMA user guide

Intelix AVO-A4-F installation manual

Intelix

Intelix AVO-A4-F installation manual

M-system Mini-M M2VF2 instruction manual

M-system

M-system Mini-M M2VF2 instruction manual

Novalynx 225-RHP-2S Series user manual

Novalynx

Novalynx 225-RHP-2S Series user manual

Emerson CSI 9420 Reference manual

Emerson

Emerson CSI 9420 Reference manual

Mod-tronic API 6380 G Series quick start guide

Mod-tronic

Mod-tronic API 6380 G Series quick start guide

Endress+Hauser Deltabar M PMD55 operating instructions

Endress+Hauser

Endress+Hauser Deltabar M PMD55 operating instructions

Meriam MDT500 user manual

Meriam

Meriam MDT500 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.