manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. MG
  6. •
  7. Transmitter
  8. •
  9. MG M6SXM User manual

MG M6SXM User manual

EM-7979 Rev.7 P. 1 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
POTENTIOMETER TRANSMITTER
(PC programmable) MODEL M6SXM
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
The M6SXM is programmable using the PC Configurator
Software. For detailed information on the PC configuration,
refer to the M6CFG users manual. The M6CFG PC Con-
figurator Software is downloadable at our web site.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside a panel.
• Insert a noise filter for the power source, input and out-
put connected to the unit. COSEL Noise Filter Model
NAC-04-472, TDK Noise Filter Model ZCAT 3035-1330 or
equivalent is recommended.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 0.5W
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -20 to +55°C
(-4 to +131°F) with relative humidity within 30 to 90%
RH in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Body
Front Cover
DIN Rail Adaptor
Specifications
M6SXM
EM-7979 Rev.7 P. 2 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTALLATION
Set the unit so that its DIN rail adapter is at the bottom. When the unit is installed to an Installation Base (model M6SBS),
refer to its instruction manual.
■MOUNTING THE UNIT ON A DIN RAIL
A)Hang the upper hook at the rear side of unit on the DIN
rail.
B)Push in the lower in keeping pressing the unit to the DIN
rail.
ADIN Rail
B
■REMOVING THE UNIT
A)Pull down the DIN rail adaptor using a minus screwdriv-
er.
B)Pull out the lower part of the unit.
C)Remove the upper part from the DIN rail.
A
DIN Rail Adaptor
CB
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
94 (3.70)
5.9 (.23)
DIN RAIL
35mm wide
DIN RAIL HOOK
*Use a minus screwdriver: tip width 3.8 mm max., tip thickness 0.5 to 0.6 mm
102 (4.02)
[0.5 (.02)]
SCREWDRIVER
INSERTION ANGLE
: approx. 40°
WIRE INSERTION ANGLE
: approx.35°
TEST PROBE
max. 2 (.08) dia.
SCREWDRIVER
*
INSERTION ANGLE
: approx. 35°
5678
1234
• When mounting, no extra space is needed between units.
M6SXM
EM-7979 Rev.7 P. 3 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■CONNECTION DIAGRAM
+
–
+
–
OUTPUT
5
6
7
8
POWER
1
2
4
CONFIGURATOR JACK
+
–
3
2
1
POTENTIOMETER
max.
min.
POWER
CONNECTOR
■WIRING INSTRUCTIONS
• Applicable wire size
Solid: 0.2 to 2.5 mm2(0.55 to 1.75 dia.)
Stranded: 0.2 to 2.5 mm2(Tinning wire ends may
cause contact failure and therefore is not
recommended.)
Ferruled: 0.2 to 1.5 mm2(0.55 to 1.35 dia.)
• Expose wire conductors by 8 mm (0.31”).
Expose 8 mm
• How to Connect Wires
Screwdriver
Wire
1) Insert a minus screwdriver into the wire entry opening,
between the clamp and the housing, until its tip hits the
bottom where it is firmly held.
Tension Clamp
Screwdriver
2) Insert a wire. Push the screwdriver toward the direction
indicated with the arrow in the figure below to widen the
opening if necessary.
Wire Entry
Wire
3) Confirm that the wire tip hits the bottom and pull out the
screwdriver in holding it in position.
Confirm that the wire’s insulation tube is not caught in
the clamp.
M6SXM
EM-7979 Rev.7 P. 4 / 4
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
EXTERNAL VIEWS
■ FRONT VIEW (with the cover open) ■ SIDE VIEW
1
SW1
2345678
OFF
ON
SW1
Output Range Selectors
Status Indicator LED
Power LED
Configurator Jack
5678
1234
OUTPUT RANGING
The internal DIP switch setting is required to select output
types before setting a precise output range using PC Con-
figurator Software (model: M6CFG).
For detailed information on the PC configuration, refer to
the M6CFG users manual.
Table 1. DIP switch setting: Output type
Output
Type
SW
12345678
0 – 20 mA*1ON ON OFF OFF OFF OFF ON OFF
-5 – +5 V OFF OFF ON OFF ON OFF OFF ON
-10 – +10 V OFF OFF ON OFF OFF ON OFF ON
*1. For 0 – 1 mA range, set switches as in the table below.
Output
Range
SW
12345678
0 – 1 mA OFF OFF ON OFF OFF OFF ON OFF
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Confirm that the wire insulation tubes are not caught in
the clamp.
3) Check DIP switch setting.
4) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
5) Input: Check that the input signal is within 0 – 100% of
the full-scale.
If the potentiometer or its extension wires are broken,
the output goes over 100% (below 0% with downscale
protection) due to the burnout function. Confirm the sta-
tus indicator LED pattern and check leadwires in such a
case.
6) Output: Check that the load resistance meets the de-
scribed specifications.
STATUS INDICATOR LED
The transmitter is provided with a status indicator LED
which blinks in different patterns indicating various oper-
ating status.
The following figure indicates typical patterns.
Normal operating mode
TRANSMITTER STATUS
ON
OFF
LED ON-OFF PATTERNS
Burnout mode
Abnormal operating mode
80 milliseconds
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit using the PC Configurator
Software (model: M6CFG).
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.

Other MG Transmitter manuals

MG KWRS2 User manual

MG

MG KWRS2 User manual

MG M6NWVS User manual

MG

MG M6NWVS User manual

MG 10AC User manual

MG

MG 10AC User manual

MG 18JPA User manual

MG

MG 18JPA User manual

MG M3-UNIT Series User manual

MG

MG M3-UNIT Series User manual

MG Mini-M M2VF3 User manual

MG

MG Mini-M M2VF3 User manual

MG Mini-M M2EXV User manual

MG

MG Mini-M M2EXV User manual

MG BCT User manual

MG

MG BCT User manual

MG M6NVF User manual

MG

MG M6NVF User manual

MG M3-UNIT Series User manual

MG

MG M3-UNIT Series User manual

MG Mini-M M2CA User manual

MG

MG Mini-M M2CA User manual

MG M6DCTC User manual

MG

MG M6DCTC User manual

MG M3SVS User manual

MG

MG M3SVS User manual

MG M6SWVS User manual

MG

MG M6SWVS User manual

MG 10JRE User manual

MG

MG 10JRE User manual

MG W5LCS User manual

MG

MG W5LCS User manual

MG 10RS User manual

MG

MG 10RS User manual

MG SVF User manual

MG

MG SVF User manual

MG 10MS User manual

MG

MG 10MS User manual

MG FRT User manual

MG

MG FRT User manual

MG HR User manual

MG

MG HR User manual

MG W5VS User manual

MG

MG W5VS User manual

MG BR User manual

MG

MG BR User manual

MG W5TS User manual

MG

MG W5TS User manual

Popular Transmitter manuals by other brands

Logic3 IP163 instruction manual

Logic3

Logic3 IP163 instruction manual

Honeywell ST 3000 user manual

Honeywell

Honeywell ST 3000 user manual

UPM WT440H owner's manual

UPM

UPM WT440H owner's manual

HK Instruments DPT-Dual-MOD Series installation instructions

HK Instruments

HK Instruments DPT-Dual-MOD Series installation instructions

Kenwood FFINELINE RFU-6100 user manual

Kenwood

Kenwood FFINELINE RFU-6100 user manual

Partner OT-110 user manual

Partner

Partner OT-110 user manual

Emerson Rosemount Analytical HART SMART 5081C-HT instruction sheet

Emerson

Emerson Rosemount Analytical HART SMART 5081C-HT instruction sheet

Kramer F-121UK user manual

Kramer

Kramer F-121UK user manual

Eldat secwave RT42 Startup guide

Eldat

Eldat secwave RT42 Startup guide

Siemens SITRANS LR560 operating instructions

Siemens

Siemens SITRANS LR560 operating instructions

Semtech TS8000 Flash Series user manual

Semtech

Semtech TS8000 Flash Series user manual

Hyundai FMT 193 instruction manual

Hyundai

Hyundai FMT 193 instruction manual

PR electronics 4116 manual

PR electronics

PR electronics 4116 manual

Erone 024A Series manual

Erone

Erone 024A Series manual

RKI Instruments 65-2422RK-05 Operator's manual

RKI Instruments

RKI Instruments 65-2422RK-05 Operator's manual

M-system Mini-M M2XM2 instruction manual

M-system

M-system Mini-M M2XM2 instruction manual

Tekkeon myTune IA1000 user guide

Tekkeon

Tekkeon myTune IA1000 user guide

Kramer TP-551N user manual

Kramer

Kramer TP-551N user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.