MULTISPAN UTC-1202 User manual

TC
+
RTD
-
!
L
N
1
2
3
4
5
6
7
-
+
O/P
S.S.R
RELAY-1
RELAY-2
100
250V AC
~
50/60 Hz
4VA
NC
NO
NO
NC
C
C
8
9
10
11
12
13
14
17 8 9
12
1314
10
11
1617181920 15
23456
NC NC
C C
NO NO
TC
+
-
+
-
RELAY-1 RELAY-2
100
250V AC
~
50/60 Hz
4VA
!
LN
O/P
S.S.R RTD
PID /TP/ ON-OFF (selectable)
2 relay, 1 C/O contact, 230V AC, 5A ; 1 SSR,12V DC, 30mA DC
www.multispanindia.com
Page - 1
UTC-1202,2202
Note:
1) If Sensor Connection is reversed, Display will show “ ” message.SRE
2) If Sensor is not connected, Display will show message.Open
3) Every time the instrument is turned ON, Following pattern will be displayed
J: 0 to 600°C / K: 0 to 1200°C /
PT-100: -99 to 400ºC /PT.1: -99.0 to 400.0°C
Output
Power Supply
Protection Level
Operating Relative
(As per request)
Temperature Humidity
100 to 250V AC, 50 / 60 Hz, Approx 4VA
IP-65(Front side) AS per IS/IEC 60529:2001
0°C To 55°C Up to 95% RH Non Condensing
Model
Display
Size(HXWXD)
Panel Cutout
Input
Temperature
Range
Control Action
UTC 1202
96 X 96 X 50 mm
68 X 68 mm
92 X 92 mm
72 X 72 X 85 mm
UPPER:- 4 Digit 7 seg 0.70”,red LED Display
LOWER:- 4 Digit 7 seg 0.50”,green LED Display
UTC 2202
J, K, PT-100 (selectable)
Technical Specification
Connection Diagram
OPERATING MANUAL
PID TEMPERATURE CONTROLLER
UTC-121P,221P & 421P
Technical Specification
Connection Diagram
OPERATING MANUAL
PID TEMPERATURE CONTROLLER
UTC-1202, 2202
All digit segment will be turned ON for 3 sec
Previous or default sensor input will be displayed for 2 sec
Process Value
Set Value
POWER ON
8
888
8888
34
234
j
INpt
ENTSET
UTC 1202
TUNE
ºC
PV
SV
32 4
235
R1
R2
SET
ENT
UTC 2202
R1
R2
TUNE
PV
SV
ºC
32 4
235
IF T1MD=OFF
IF T2MD=OFF
IF RELATIVE (-50°C To +50°C)
IF R1MD=OFF
IF R2MD=OFF
www.multispanindia.com
Page - 2
Set Value
Set Point-1
Set Point-2
Password Message
Press key for 3 sec to
enter Password
SET
Process Value
Input ( J / K / Pt.1 / Pt100 )
Control Action (PID/ON-OFF/TP)
Password Message
P TP T 1.
T P
O N O F
K
SET
Press key
ENT
Set Point Low Limit
Set Point High Limit
HEAT, COOL, H-AL,
L-AL, I-AL, O-AL, OFF
HEAT, COOL, H-AL,
L-AL, I-AL, O-AL, E-AL, OFF
OFF-SET
TO ENTER BASIC
CONFIGURATION
SETTING, ENTER “73”
6) Orange color LED glows during auto tuning mode.
1) Press key to go parameter setting.
SET
3) Press key to save change in setting
ENT
4) Press key for 6 sec to start/stop PID AUTO TUNING
5) Press + key for 3 sec to go to factory setting mode.
2) Press or key to change value or to select option.
Basic Configuration
Set Point Setting
Key Operation
UTC-1202,2202
34
234
set1
234
set2
255
pass
50
pass
73
INPT
j
CTRL
PID
OFST
0
SLL
0
SHL
R1MD
tIUT
t2md
s2md
tIMD
r2md
t2ut
end
600
HEAT
HOUR
almt
indu
SOHT
E-AL
E-AL
NO
Press key
SET
Press key
SET
SOKT,SKRG,SKPS,ALMT,ONDL,OFF
SEC/MIN/HOUR
SEC/MIN/HOUR
IF R1/R2 MD=OFF
Save / No
SOKT,SKRG,SKPS,ALMT,ONDL,OFF
INDIVIDUAL/RELATIVE
Press key to
Save & Exit
ENT
Factory Setting
FACTORY SETTING
PARAMETER
IT
CT ( For PID)
PB 2
OFFSET
TIME-1
TIME-2
PB
DT
MR
HYSTERESIS-1
HYSTERESIS-2
VALUES
300
15 SEC.
20.0
75
0°C
5°C
08
0°C
3°C
3°C
6 SEC
6 SEC
SR.
2
4
CT 2
6
1
3
5
7
8
9
10
11
12
Y E S
ENT
ENT
yes : press key to apply factory set
values as shown in table.
nO : press key to escape
from factory setting.
n O
Press + key
for 3 sec
F C S T
1 2 3 4
1 2 3 4
Off-set correction
4 Sec to 99 Sec.
1 to 999 Sec/MIN/HR
1 to 999 Sec/MIN/HR
1 to 999 Sec/MIN/HR
1 to 999 Sec/MIN/HR
-20.0°C to +20.0°C
4-99 Sec
-20°C to +20°C
Time 1
CT 4 sec to 99 sec 4 sec to 99 sec
IT
000 to 9999
000 to 9999
Hysteresis 0.1°C to 50.0°C
1°C to 50°C
MR
PB 2
CT 2
Time 2
-9.0 to +9.0
2.0 to 20.0
-9 to +9
2 to 20
DT 000 to 9999 000 to 9999
PB
Sr.
1
2
3
4
5
6
7
8
9
10
11
000 to 999.9 000 to 999.9
Parameter Range for PT.1 sensor
Range for J, K, PT100
SET SET SET
www.multispanindia.com
Page - 3
Password Message
IF PID SELECTED IF ON-OFF SELECTED IF TP SELECTED
SET
TO ENTER CONTROL
PARAMETER
SETTING, ENTER “37”
Control Parameter
UTC-1202,2202
PID ONOF TP
PARA PARA PARA
pass
37
Pb
20 0.
HYS1
3
PB2
5
TIM1
3
CT2
8
HYS2
3
MR
0
HYS2
3
TIM2
3
TIM1
6
TIM2
6
It
300
DT
75
TIM1
6
CT
hys2
MR
TIM2
15
3
0
6
Press key
to Save & Exit
ENT
Press key to
Save & Exit
ENT
Press key to
Save & Exit
ENT
Press key
SET
Press key
SET
Press key
SET
Manual Reset
Proportional
Band
Integral
Time
Derivative
Time
Cycle Time
PID
Parameters ON-OFF
Parameters
TP
Parameters
Hysteresis
IF T1MD = SOAK
or SKPS or SKRG
IF T2MD = OFF
IF R2MD = OFF
or E-AL
IF R1MD = OFF
IF T2MD = OFF
or E-AL
IF R2MD = OFF
IF T1MD = OFF
IF T1MD = SOAK
or SKPS or SKRG
or E-AL
IF R2MD = OFF
IF T2MD = OFF
PID AUTO-TUNING
Press key for 6 sec to start/stop
PID auto-tuning
PV
SV
1
234
1234
www.multispanindia.comPage - 4
All safety related codifications, symbols and instructions that appear in this operating manual
or on the equipment must be strictly followed to ensure the safety of the operating personnel as
well as the instrument.
If all the equipment is not handled in a manner specified by the manufacturer, it might impair the
protection provided by the equipment .
Product improvement and upgrade is a constant procedure. So for more updated operating information and support,
Please contact our helpline : +91-9978991474/82 or Email at mark[email protected] Ver: 01-2017
=> Read complete instructions prior to installation and operation of the unit.
WARNING : Risk of electric shock.
3) Cable used for connection to power source, must have a cross section of 1mm or greater. These wires
should have insulations capacity made of at least 1.5kV.
2) To reduce electro magnetic interference, use wire with adequate rating and twists of the same of equal size shall
be made with shortest connection.
4) When extending the thermocouple lead wires, always use thermocouple compensation wires for wiring for the RTD
type, use a wiring material with a small lead resistance (5 max per line)and no resistance differentials amongΩ
three wires should be present.
1) To prevent the risk of electric shock power supply to the equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is being supplied.
5) A better anti-noise effect can be expected by using standard power supply cable for the instrument.
1) This equipment, being built-in-type, normally becomes a part of main control panel and such in case the
terminals do not remain accessible to the end user after installation and internal wiring.
2) Do not allow pieces of metal, wire clippings, or fine metallic fillings from installation to enter the product
or else it may lead to a safety hazard that may in turn endanger life or cause electrical shock to the operator.
3) Circuit breaker or mains switch must be installed between power source and supply terminal to
facilitate power ‘ON’ or ‘OFF’ function. However this mains switch or circuit breaker must be
installed at convenient place normally accessible to the operator.
4) Use and store the instrument within the specified ambient temperature and humidity ranges as
mentioned in this manual.
Warning Guidelines
Safety Precautions
Installation Guidelines
Mechanical Installation
Maintenance
1) Prepare the panel cutout with proper dimensions as show above.
2) Fit the unit into the panel with the help of clamp given.
3) The equipment in its installed state must not come in close proximity to any heating source,
caustic vapors, oils steam, or other unwanted process by products.
4) Use the specified size of crimp terminal (M3.5 screws) to wire the terminal block. Tightening the
screws on the terminal block using the tightening torque of the range of 1.2 N.m.
5) Do not connect anything to unused terminals.
1) The equipment should be cleaned regularly to avoid blockage of ventilating parts.
2) Clean the equipment with a clean soft cloth. Do not use isopropyl alcohol or any other cleaning agent.
3) Fusible resistor must not be replaced by operator.
2
UTC-1202, 2202
95mm - 3.75 inches
85mm - 3.34 inches
136mm - 5.35 inches
120mm - 4.72 inches
B
B
A
A
F
E
MODEL A
96mm 96mm 92mm 92mm 3mm 50mm
BC
D E
F
DIMENSIONS
MODEL A
72mm 72mm 68mm 68mm 3mm 85mm
BC
D E
F
DIMENSIONS
C
C
D
D
E
F
SET
ENT
UTC 2202
R1
R2
TUNE
PV
SV
ºC
32 4
235
ENTSET
UTC 1202
TUNE
ºC
PV
SV
32 4
235
R1
R2

This manual suits for next models

1

Other MULTISPAN Temperature Controllers manuals

MULTISPAN UTC-2200G User manual

MULTISPAN

MULTISPAN UTC-2200G User manual

MULTISPAN UTC-321P User manual

MULTISPAN

MULTISPAN UTC-321P User manual

MULTISPAN PTC-4202A-M1 User manual

MULTISPAN

MULTISPAN PTC-4202A-M1 User manual

MULTISPAN UTC-4202G User manual

MULTISPAN

MULTISPAN UTC-4202G User manual

MULTISPAN UTC-214 User manual

MULTISPAN

MULTISPAN UTC-214 User manual

MULTISPAN TC-19 User manual

MULTISPAN

MULTISPAN TC-19 User manual

MULTISPAN UTC-2202 User manual

MULTISPAN

MULTISPAN UTC-2202 User manual

MULTISPAN UTC-421P User manual

MULTISPAN

MULTISPAN UTC-421P User manual

MULTISPAN TC-221P User manual

MULTISPAN

MULTISPAN TC-221P User manual

MULTISPAN TC-49P User manual

MULTISPAN

MULTISPAN TC-49P User manual

MULTISPAN UTC-221G User manual

MULTISPAN

MULTISPAN UTC-221G User manual

MULTISPAN UTC-1202G User manual

MULTISPAN

MULTISPAN UTC-1202G User manual

MULTISPAN TC-49 User manual

MULTISPAN

MULTISPAN TC-49 User manual

MULTISPAN TC-29P User manual

MULTISPAN

MULTISPAN TC-29P User manual

MULTISPAN TC-49P User manual

MULTISPAN

MULTISPAN TC-49P User manual

MULTISPAN UTC-114 User manual

MULTISPAN

MULTISPAN UTC-114 User manual

MULTISPAN UTC-121P User manual

MULTISPAN

MULTISPAN UTC-121P User manual

MULTISPAN TC-49 User manual

MULTISPAN

MULTISPAN TC-49 User manual

MULTISPAN UTC-121P User manual

MULTISPAN

MULTISPAN UTC-121P User manual

MULTISPAN UTC-423 User manual

MULTISPAN

MULTISPAN UTC-423 User manual

MULTISPAN UTC-113P User manual

MULTISPAN

MULTISPAN UTC-113P User manual

MULTISPAN UTC-122 User manual

MULTISPAN

MULTISPAN UTC-122 User manual

MULTISPAN UTC-421G User manual

MULTISPAN

MULTISPAN UTC-421G User manual

MULTISPAN UTC-4203 User manual

MULTISPAN

MULTISPAN UTC-4203 User manual

Popular Temperature Controllers manuals by other brands

Aegis Pavilion Control 410 Data brochure

Aegis

Aegis Pavilion Control 410 Data brochure

TREND T/PI installation instructions

TREND

TREND T/PI installation instructions

Oregon Scientific THGR328NH user manual

Oregon Scientific

Oregon Scientific THGR328NH user manual

Automarion24 TC6702 operating instructions

Automarion24

Automarion24 TC6702 operating instructions

Ekinex 71 Series Applications manual

Ekinex

Ekinex 71 Series Applications manual

Kiwi Lora Alliance Member LAS-603V1 user manual

Kiwi

Kiwi Lora Alliance Member LAS-603V1 user manual

Danfoss ECL Comfort 310 installation guide

Danfoss

Danfoss ECL Comfort 310 installation guide

Franke ZAQUA020 Installation and operating instructions

Franke

Franke ZAQUA020 Installation and operating instructions

Data Harvest 1100 quick start guide

Data Harvest

Data Harvest 1100 quick start guide

RKC INSTRUMENT RB700 manual

RKC INSTRUMENT

RKC INSTRUMENT RB700 manual

Uponor Climate Control Zoning System installation guide

Uponor

Uponor Climate Control Zoning System installation guide

Linear Technology DC1792A manual

Linear Technology

Linear Technology DC1792A manual

ELKATHERM FTRFB-280 Series manual

ELKATHERM

ELKATHERM FTRFB-280 Series manual

Thermon TC 816 Operation manual

Thermon

Thermon TC 816 Operation manual

TCNet Boiler Controller User and service manual

TCNet

TCNet Boiler Controller User and service manual

BriskHeat LYNX Quick start instruction manual

BriskHeat

BriskHeat LYNX Quick start instruction manual

Auber Instruments SWA-2441B instruction manual

Auber Instruments

Auber Instruments SWA-2441B instruction manual

Alula RE605 quick start guide

Alula

Alula RE605 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.