GENERAL
These luminaires are used where emergency
light is needed. Each luminaire must be
permanently connected to mains power supply.
In normal operation the power indicator lights
and the charge indicator blinks to show that the
batteries are in charging condition. In case of a
mains power supply failure the power and the
charge indicators turns off and the luminaire
will light the spot lamps automatically in
emergency mode. When the mains power
supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 3.
OPERATION
When the device is powered from the mains, the
charge indicator blinks and confirms the
charging of the batteries. When the batteries
are charged, it lights constantly. If it does not
light, probably, the batteries are disconnected.
If it does not light and the batteries are
connected, then contact the technician. As long
as the charge indicator blinks, the batteries of
the luminaire are charging and in this period,
any autonomy test must be avoided. When the
charging circle is complete, the indicator lights
continuously (it can be used as an indication of a
power interruption). The batteries charging is
done by a 3 stages technological advanced
procedure, to ensure the appropriate and full
charging of the batteries. The power indicator
confirms the proper connection to the mains. The
TEST button, has a dual use. If pressed instantlly
while the device is connected to the mains, the
device simulates the power interruption, by
lighting the lamps for 3''. In this way, we can
control the driver circuit of the lamps and the
lamps as indicated in paragraph 3 in the text
below.
Dimming option
When the voltage is interrup ted,with
corresponding pressings of the button, we can
choose the illumination of 100%, 50%, 33% or
turned off, either to increase the autonomy time
or not to consume the battery power
unnecessarily. This option is canceled when the
network is restored.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only.
2. The device must be connected to the mains
Page 1 from 3 923029010_09_013
Thank you for your trust in our products
Olympia Electronics - European manufacturer
ABS/PC, PC
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Pb)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
24h
Power indicator, battery charge indicator, TEST button
From overcharge and deep discharge
IP65
5 to 40 C
o
Up to 95%
3 years (1 year for the battery)
180 min
1620lm
White LEDs
3760gr.
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
GRL-29/WP
220-240V AC/50-60Hz
12V/7Ah
14.4W/16VA
307 x 100 x 350 mm
``POWER LIGHT`` SERIES FOR WATERPROOF NON MAINTAINED EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS (for LED MODULE Specifications see page 2)