
GENERAL
o
These luminaires are used indoors (ta 40 C) where emergency
light is needed. Each luminaire must be permanently connected
to mains power supply. In normal operation the power indicator
lights and the charge indicator blinks to show that the batteries
are in charging condition. In case of a mains power supply
failure the power and the charge indicators turns off and the
luminaire will light the spot lamps automatically in emergency
mode. When the mains power supply is restored the device
turns to normal operation.
INSTALLATION
To install the luminaire follow the installation instructions οn page
3.
OPERATION
When the device is powered from the mains, the charge
indicator blinks and confirms the charging of the batteries. When
the batteries are charged, it lights constantly. If it does not light,
probably, the batteries are disconnected. If it does not light and
the batteries are connected, then contact the technician. As long
as the charge indicator blinks, the batteries of the luminaire are
charging and in this period, any autonomy test must be avoided.
When the charging circle is complete, the indicator lights
continuously (it can be used as an indication of a power
interruption). The batteries charging is done by a 3 stages
technological advanced procedure, to ensure the appropriate
and full charging of the batteries. The power indicator confirms
the proper connection to the mains. The TEST button, has a dual
use. If pressed instantlly while the device is connected to the
mains, the device simulates the power interruption, by lighting
the lamps for 3''. In this way, we can control the driver circuit of
the lamps and the lamps as indicated in paragraph 3 in the text
below.
DIMMING OPTION
When the voltage is interrupted, with corresponding pressings of
the button, we can choose the illumination of 100%, 50%, 33% or
turned off, either to increase the autonomy time or not to consume
the battery power unnecessarily. This option is canceled when the
network is restored.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized
personnel only.
2. The device must be connected to the
mains power supply through a fuse
dependent by the total amount of the line’s
power load.
3. It is suggested to check every month the
indication LED for battery charging, and by
pushing instantly the TEST button to check
the emergency circuit and the lamps. If the
luminaire does not light
4. It is suggested to check every 6 months
the minimum autononous duration by
disconnecting the mains power supply.
Count the time that the lamps light and in
case of less time than the minimum
autonomous duration the batteries must be
replaced. If the measured time is
considerably less than the minimum
autonomous duration
The replacement of the battery and the
light source must be done using parts of
the same type, by the manufacturer or by a
competent person.
5.
t i
in battery recycling
points. Do not incinerate.
Battery replacement.
It can be done only by a competent person and after the mains
interruption.
1. Follow the step 2 of the installation procedure.
2. Disconnect the cables and remove the old battery.
contact the
installer.
contact the installer.
In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery’s connector.
6. I s not allowed to discard batteries in to common trash
bins, they must be discarded only
Page 1 from 3
``POWER LIGHT`` SERIES FOR NON MAINTAINED EMERGENCY LUMINAIRES
923029009_09_012
Thank you for your trust in our products
Olympia Electronics - European manufacturer
ABS/PC, PC
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Pb)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
24h
Power indicator, battery charge indicator, TEST button
From overcharge and deep discharge
IP42
5 to 40 C
o
Up to 95%
3 years (1 year for the battery)
180 min90 min
1620lm 790lm
White LEDs
3560gr.2080gr.
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
220-240V AC/50-60Hz
12V/7Ah6V/4Ah
14.4W/16VA5.6W/7.5VA
302 x 94 x 345 mm.
TECHNICAL CHARACTERISTICS (for LED MODULE Specifications see page 2)
GRL-21GRL-29