6Multipoint Temperature Controller E5ZE
■Characteristics
Note: 1. The measurement accuracy of the E5ZE used with a thermocouple B at 400°C or 750°F max. is not guaranteed. The following
measurement accuracy values are applied to the E5ZE.
K and T at −100°C max. and U: ±3°C ±1 digit max.
K and T at −100°F max. and U: ±5.4°F ±1 digit max.
R, S, and W at 200°C max., and B at 1,000°C max.: ±4°C ±1 digit max.
R, S, and W at 400°F max., and B at 1,800°F max.: ±7.2°F ±1 digit max.
2. The measurement accuracy of the E5ZE used with any thermocouple is 1°C/°F. The thermocouple can be used under the following
temperature ranges to increase the measurement accuracy to as high as 0.1°C/°F.
K thermocouple: 0.0 °C to 1,300.0 °C, 0.0 °F to 2,300.0 °F
T or U thermocouple: 0.0 °C to 400.0 °C, 0.0 °F to 700.0 °F
N thermocouple: 400.0 °C to 1,300.0 °C, 700.0 °F to 2,300.0 °F
J, E, L, or PLII thermocouple: Any temperature
3. To ensure EMC conformance, refer to Wiring for Conformance to the EMC Directives on page 16.
Measurement accuracy (see note) Thermocouple:
(±0.3% of the process value or ±2°C, whichever greater) ±1 digit max.
(±0.3% of the process value or ±3.6°F, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(±0.3% of the process value or ±0.8°C, whichever greater) ±1 digit max.
(±0.3% of the process value or ±1.5°F, whichever greater) ±1 digit max.
Hysteresis 0.0°C/°F to 99.9°C/°F for ON/OFF control only (in units of 0.1°C/°F)
Cooling coefficient 0.0 to 10.0 (in units of 0.1)
Proportional band 0.0°C/°F to 999.9°C/°F (in units of 0.1°C/°F)
Cooling side: Cooling coefficient x Proportional band
Integral (reset) time 0 to 3,999 s (in units of 1 s) (for both heating and cooling)
Derivative (rate) time 0 to 3,999 s (in units of 1 s) (for both heating and cooling)
Control period Heating side:1 to 99 s (in units of 1 s)
Cooling side: 1 to 99 s (in units of 1 s)
Sampling period Approx. 200 ms for 8 control points
Dead band/overlap band −999°C/°F to 999°C/°F (in units of 1°C/°F)
Alarm output setting range −999°C/°F to 9999°C/°F, 0 to 9999°C/°F (upper- and lower-limit alarm) (in units of 1°C/°F)
−999.9°C/°F to 9999.9°C/°F, 0.0 to 9999.9°C/°F (upper- and lower-limit alarm) (in units of 0.1°C/°F)
Fuzzy strength 0% to 99% (in units of 1%)
Fuzzy scale 1 0.2°C/°F to 999.9°C/°F (in units of 0.1°C/°F)
Fuzzy scale 2 0.02°C/s or °F/s to 99.99°C/s or °F/s (in units of 0.01°C/s or °F/s)
Set value backup Lithium battery
Set value backup period 10 years min. at room temperature
Insulation resistance 20 MΩmin. between the FG terminal and all analog input terminals (at 500 VDC)
Dielectric strength A leakage current of 1 mA AC max. with 500 VAC for 1 minutes between the FG terminal and all analog
input terminals
Vibration resistance Malfunction: 10 to 55 Hz, 10 m/s2(1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s2(2G) for 2 hrs each in X, Y, and Z directions
Shock resistance Malfunction: 150 m/s2(15.3G), 3 times each in 6 directions
Destruction: 200 m/s2(20.4G), 3 times each in 6 directions
Ambient temperature Operating: −10°C to 55°C (with no icing or condensation)
Storage: −25°C to 65°C (with no icing or condensation)
Ambient humidity Operating: 35% to 85%
Storage: 35% to 95%
Dimensions Without casing: 169.5 x 192 x 58 mm max.
With casing: 173.5 x 200 x 65 mm max.
Degree of protection IP00
Weight Without casing: 900 g max.
With casing: 1,700 g max.
EMC Emission Enclosure: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4:2 kV power-line (level 3)
Approved standards Conforms to EN50081-2, EN50082-2 (see note 3)