CX-702 , CX-702V
PASSIVE INFRARED DETECTOR
CX-702 / CX-702V
- Dual Purpose Lens:Selectable ”WIDE ANGLE” and
“LONG RANGE” detection patterns
- Double Conductive Shielding of the pyroelectric element
Extremely High Light and RFI Immunity (Patent listed)
- Multifocus Optics Design (Patent listed)
- LED On/Off Switch
- Sealed Optics
- Easy Installation
FEATURES
OPTION
CA-1W : Wall Mount Bracket : adjustable ±45°(Horizontally), 0-20°(Vertically downwards)
CA-2C : Ceiling Bracket : adjustable ±45°(Horizontally), 0-20°(Vertically downwards)
1.INSTALLATION HINTS
2.DETECTION AREA
Avoid Curtain,Screen,etc.
blocking detection area.
Avoid vapor or high humidity
that can cause condensation.
Avoid direct sunlight. Do not install outdoors.Avoid mounting detector where
movement of Fans or Air
Conditioning Fans can be detected.
8.TROUBLE SHOOTING
NOTE
These units are designed to detect movement of an intruder and activate
an alarm control panel.
Being only part of a complete alarm system,we cannot accept
responsibility for any damages or other consequences resulting from an
intrusion.
These products conform to the EMC Directive 89/336 EEC.
Dimensions : inches (mm)
9.SPECIFICATIONS
CX-702V Only
- Alarm Memory
- LED Remote Control Terminal
STANDARD ALARM MEMORY
3.94(100)
5.51 (140)
2.72 (69)
No.59-0951-2 0201-29
*Specifications and design are subject to change without prior notice.
CX-702V
8mA(normal) / 16mA(max.) at 12VDC
See Section7-3.
See Section7-1.
Model
Current draw
Alarm Memory
D.L.terminal
When damage has occured to the
product, i.e. water logged, abnormal
things inside product, overheating
or smoking, strange smells etc.,
WARNING
Never repair or modify
product. It may cause
accident, fire hazard or
electric shock.
WARNING
CAUTION
Mount securely.
A falling product
may cause injury.
PROBLEM
LED does not light.
LED lights even
though no person
within area.
LED lights but
signal is not sent.
LED continues to light
PROBABLE CAUSE
Improper power supply voltage
(disconnection,low voltage).
Improper detection area.
LED switch is OFF.
Improper polarity to detector.
Moving object within area (curtain, wall hanging, etc.).
Temperature of object within area changing rapidly
(heater, air conditioning, etc.).
Relay contact is stuck or damaged due to overloading.
Faulty wiring.
Poor connection of alarm memory.
Wrong control voltage from panel.
REMEDY
Correct supply voltage to 9.5 - 16V DC.
See Section 5.
See Section 2.
Turn on the switch.
Switch positive and negative at terminal.
Remove the souces from the detection area.
Remove object from the detection area.
Check load of output.
The unit needs repair or replacement.
Wire correctly.
Reconnect wire.
Must be 0-1V DC(grounded) See Section 7-3.
1 2 3 4 5
6 7 8
*The CX-702 is UL Listed per UL639,
Intrusion-Detection Units.
*The CX-702V has not been
investigated by UL.
(CX-702 Only)
N219
**ATTENTION**
The specified detection area can be achieved by mounting the unit at a height of 8ft.(2.4m). Mounting at a lower or higher height may reduce the area of coverage.
CX-702
8mA (normal) / 11mA (max.) at 12VDC
Model
Detection method
Coverage
Detection zones
Mounting height
Sensitivity
Detectable speed
Power input
Alarm period
Alarm output
Tamper switch
Pulse count
Warm-up period
LED indicator
RF interference
Operating temperature
Environment humidity
Weight
CX-702 / CX-702V
Passive infrared
Wide Angle 85°wide
Long Range
70ft. × 70ft. 150ft. × 8ft.
(21m × 21m) (45m × 2.4m)
68 zones 22 zones
5 - 12ft.(1.5 - 3.6m)
3°F at 2ft./sec., 8ft. mounting height
(1.6°C at 0.6m/sec., 2.4m mounting height)
1- 5ft. / sec. (0.3 - 1.5m/sec.)
9.5 - 16VDC
Approx. 2.5 sec.
N.C. 28VDC 0.2A max.
N.C. Opens when cover is removed.
28VDC 0.1A max.
Approx. 20 sec. 2 or 4
Approx. 1 min.
Alarm condition
No alarm 30V/m
-4°F - +122°F(-20°C - +50°C)
95% max.
7.0oz (200g)
Model
Current draw
immediately stop using product and contact your supplier.
Otherwise, continued use in such condition may cause
electric shock or fire hazard.