Penn A52 Series User manual

1
Refer to the QuickLIT website for the most up-to-date version of this document.
A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
Application
The A52x Series Refrigeration Controller with Adaptive Defrost provides refrigerated space control and defrost
control for medium and low temperature refrigeration applications.
The A525 Controller has five integral line-voltage, dry-contact relays to control the compressor, defrost heater or
solenoid, evaporator fans, and user-provided alarm devices. The controller can control resistive heat, hot-gas
bypass, or passive defrost. The controller can also control two-speed evaporator fans. The A524 Controller has
four integral line-voltage relays and controls the same devices as the A525 Controller. The LO-SPD AUX relay is
not available on the A524 Controller, which controls a single speed evaporator fan only.
The adaptive defrost feature allows the controller to adjust the defrost schedule to the minimum number of defrost
intervals required to maintain peak efficiency, save energy, and maintain consistent space temperature. The A52x
Controller
has an IP65 enclosure with holes in the enclosure base for wall-surface mounting. An optional DIN rail
mount kit (
Part No.
BKT524-1K)
is also available.
Refer to the A52x Series Refrigeration Controller with Adaptive Defrost Technical Bulletin (LIT-12012405) for more
details on setting up, operating, and troubleshooting the A52x Controller. You can access and download the A52x
Controller Technical Bulletin from QuickLIT.
Parts Included
Each A52x Series Controller includes two Johnson Controls/PENN® A99B Series Temperature Sensors. See
Sensor Wiring on page 6, Table 12 on page 11, and refer to the A99B Series Temperature Sensors Product/
Technical Bulletin (LIT-125186) for more detailed installation procedures and technical specifications.
IMPORTANT: Use of this product is subject to and constitutes your agreement to the End User License
Agreement set forth at www.johnsoncontrols.com/buildings/legal/digital Part No. 24-07664-03310
IMPORTANT: Use this A52x Series Refrigeration Controller only as an operating control. Where failure or
malfunction of the A52x Controller could lead to personal injury or property damage to the controlled equipment
or other property, additional precautions must be designed into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect
against failure or malfunction of the A52x Controller.
IMPORTANT : Utiliser ce A52x Series Refrigeration Controller uniquement en tant que dispositif de contrôle de
fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du A52x Régulateur risque de provoquer des
blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de
contrôle doit intégrer des dispositifs de protection supplémentaires. Veiller dans ce cas à intégrer de façon
permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de
sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de
dysfonctionnement du A52x Régulateur.
A52x Series Refrigeration Controller with Adaptive Defrost
Installation Instructions
A524/A525
Part No. 24-07664-03310 Rev. C
Issued April 2018

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
2
Dimensions
Mounting
Mounting Considerations
Observe the following A52x Controller location and mounting guidelines:
• Mount the controller on a flat surface.
• Ensure that the mounting surface can support the controller assembly, mounting hardware, and any
user-supplied panel or enclosure.
• Ensure that the controller is in the proper orientation for easy wiring, setup, and viewing.
• Allow enough space to connect and route wires, view the LCD, and use the touchpad.
• Identify the appropriate mounting hardware.
• Mount the controller in locations free of corrosive vapors and observe the ambient operating conditions listed in
the Technical Specifications on page 10 for both the A52x Controller and the A99B Sensors.
• Do not mount the controller on surfaces that are prone to vibration.
• Do not mount the controller in a location where high-voltage relays, motor starters, other sources of
electromagnetic emissions, or strong radio frequency may cause Electro-Magnetic Interference (EMI).
• Do not install the controller in airtight enclosures.
• Do not install heat generating devices with the controller in an enclosure that may cause the ambient
temperature to exceed 60°C (140°F).
Figure 1: A52x Refrigeration Control with IP65 Enclosure Dimensions, mm (in.)

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
3
Wall Mounting
To mount the A52x Controller on a wall or other flat surface, complete the following steps:
1. Loosen the four spring-loaded cover screws to open the controller cover. Be careful not to damage the
controller’s interior components.
2. Attach an appropriate fastener onto the wall or other flat surface.
3. Position the keyhole slot on the rear of the enclosure base over the fastener. Ensure that the controller hangs
securely on the fastener.
4. Mark the location for the mounting screws using the four holes on the corners of the enclosure base, and
remove the keyhole slot fastener from the wall surface.
5. Mount the controller using four screws (M4 [#8] panhead screw; 12 mm [0.5 in.] or longer).
6. Tighten the screws securely. Use shims to prevent warping the enclosure when mounting the controller on an
uneven surface.
7. Close the front cover and tighten the spring-loaded cover screws to 0.9–1.1 N·m (8–10 in·lbs) to seal the cover.
Table 1: A52x Refrigeration Control Wall-Surface Mounting
Callout Description
1 Spring-loaded cover screw on the controller cover
2 Keyhole slot on the rear of the enclosure base
3 Mounting screw hole on the enclosure base
Figure 2: A52x Refrigeration Control Wall-Surface Mounting

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
4
DIN Rail Mounting
An optional DIN Rail mount kit (Product Code Number, BKT524-1K)is available for the A52x Controller. The DIN
rail clip assembly attaches to the five holes on the back of the enclosure base. Refer to the installation instructions
included with the DIN rail kit for DIN rail mounting procedures.
Conduit Fitting Section
Conduit Plug Removal and Fitting
To remove the conduit plug and insert the liquid tight fitting, complete the following steps:
1. Clip the conduit rib using a cutting pliers.
2. Place a flat blade screwdriver at the edge of the knockout. Gently tap with a hammer to carefully remove the
conduit plug.
3. To maintain the IP65 moisture protection rating, select an appropriate water tight conduit connector.
Wiring
See Figure 4 on page 5 and Table 2 on page 6 for electrical termination locations, terminal labels, and wiring
information for low-voltage terminations.
See Figure 5 on page 7 and Table on page 8 for electrical termination locations terminal labels, and wiring
information for high-voltage terminations. See Table 5 on page 8 to Table 9 on page 9 for the electrical rating for the
high-voltage relays.
Risk of Electric Shock.
Disconnect or isolate all power supplies before making electrical connections. More than one disconnection or
isolation may be required to completely de-energize equipment. Contact with components carrying hazardous
voltage can cause electric shock and may result in severe personal injury or death.
Figure 3: Conduit Plug Removal and Liquid Tight Fitting Selection

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
5
Low-Voltage Wiring
Figure 4 on page 5 and Table 2 on page 6 provide information about the low-voltage wiring terminal blocks, wiring
terminal labels, and recommended wire sizes
Figure 4: A52x Controller Low-Voltage Terminal Block Connections
Risque de décharge électrique.
Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique. Plusieurs isolations et
débranchements sont peut-être nécessaires pour-couper entièrement l'alimentation de l'équipement. Tout contact
avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de
provoquer des blessures graves, voire mortelles.
IMPORTANT: Use copper conductors only. Make all wiring in accordance with local, national, and regional
regulations.
IMPORTANT: Do not exceed the A52x Controller electrical ratings. Exceeding controller electrical ratings can
result in permanent damage to the controller and void any warranty.
IMPORTANT: Run all low-voltage wiring and cables separate from all high-voltage wiring and route wires per
NEC or local electrical code requirements. Shielded cable is recommended for low-voltage cables that are
exposed to high electromagnetic or radio frequency noise.
IMPORTANT: Electrostatic discharge can damage control components. Use proper electrostatic discharge
precautions during installation, setup, and servicing to avoid damaging the controller.
IMPORTANT: Do not connect supply power to the controller before finishing wiring and checking all wiring
connections. Short circuits or improperly connected wires can result in damage to the controller and void any
warranty.

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
6
Sensor Wiring
See Table 3 on page 7 for information about wire gauge and maximum sensor wire length. See Table 12 and
Table 13 on page 11 for the sensor technical specifications.
Observe the following guidelines when you wire sensors to the A52x Controller:
• Sensor leads are not color coded or polarity-specific; you can connect either of the two sensor leads to the Sn1
or Sn2 terminal and a C terminal.
• Select only the sensor that is designed to operate in the ambient operating range that your A52x Controller is
intended to monitor and control.
• Keep the sensor leads as short as possible in your application. The additional resistance in long sensor cables
can create an offset between the actual temperature and the displayed temperature. Solder or butt splice
connections are recommended.
Use 0.30 mm2 (22 AWG), stranded-wires and twisted-leads cable with a cable shield for extending sensor cable
runs.
Table 2: A52x Controller Low-Voltage Terminal Blocks, Terminals, and Wire Sizes
Terminal
Block Label
Terminal
Label
Description, Function, and Requirements Recommended
Wire Sizes
RS485
MODBUS
A + The RS485 Modbus communications terminal block provides a
restricted connection to the Modbus connections on an optional
Precision Superheat Controller (PSHC). Do not connect any other
Modbus device to these terminals.
0.20 to 0.30 mm2
(26 to 22 AWG)
Stranded wires and
twisted-leads cable
B -
REF RS485 Modbus signal common or reference
ANALOG
INPUT/OUTPUT
Sn1 The main space temperature sensor. Connect either lead from the
sensor to Sn1. Connect the other lead to a Common (C) terminal.
Note: Sensors for A52x Controller are not polarity sensitive.
0.30 to 1.50 mm2
(22 to 16 AWG)
Stranded wires and
twisted-leads cable
Sn2 Evaporator temperature sensor. Connect either lead from the
sensor to Sn2. Connect the other lead to a C terminal.
Note: Sensors for A52x Controller are not polarity sensitive.
Sn3 Not available
UI 4 Universal Input 4 can be configured as a 0–10 VDC analog input
or dry contact binary input. Connect a 0 to 10 VDC input or binary
input to the UI4 (+) terminal and a C (common/-) on the low voltage
terminal block.
UI 5 Universal Input 5 can be configured as a 0–10 VDC analog input
or dry contact binary input. Connect a 0 to 10 VDC input or binary
input to the UI5 (+) terminal and a C (common/-) on the low voltage
terminal block.
C Three low-voltage common terminals
All low-voltage C terminals are connected together.
AO1 Note: Analog Output 1 (AO1) is not supported in the A525. Make
no connection to this terminal. The A524 Controller does not
include an analog output and does not have an AO1 terminal
block.

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
7
1. At the listed cable lengths, there is less than 0.6°C (1°F) error between the temperature sensed at the A99B sensor and the
temperature displayed on the LCD.
High-Voltage Wiring
Figure 5 on page 7 and Table 4 on page 8 describe the high-voltage wiring terminal blocks, wiring terminal labels,
and wire sizes. See Table 5 on page 8 to Table 9 on page 9 for relay electrical ratings.
Table 3: Maximum Recommended Sensor Cable Lengths and Wire Sizes
Wire Gauge Maximum Sensor Cable Length 1
1.3 mm2(16 AWG) 150 m (500 ft)
0.82 mm2(18 AWG)100 m (300 ft)
0.52 mm2(20 AWG) 60 m (200 ft)
0.33 mm2(22 AWG)40 m (125 ft)
IMPORTANT: When connecting sensors with shielded cable to a control, connect the cable shield drain lead to
one of the C (common) terminals on the input sensor terminal block. Do not connect the shield at any other point
along the cable. Isolate and insulate the shield drain at the sensor end of the cable. Connecting a cable shield at
more than one point can enable transient currents to flow through the sensor cable shield, which can cause
erratic control operation.
Figure 5: A52x Controller High Voltage Terminal Block Connections

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
8
Relay Electrical Ratings
Table 5 on page 8 to Table 9 on page 9 provide the electrical ratings for the control relays in the A52x Controller.
See Table 11 on page 11 for the relay’s duty cycle ratings.
Table 4: A52x Controller High-Voltage Terminal Blocks, Terminals, and Wire Sizes
Terminal
Block Label
Terminal
Voltages
Description, Function, and Requirements Recommended
Wire Sizes
90-240 VAC L1 Two terminals for supply power connection to the A525 Controller.
Requires 90 to 240 VAC; 15 VA, (0.25 A maximum). 0.75 to 2.50 mm2
(18 to 14 AWG)
L2/N
GND Earth ground connection terminal
Compressor Two terminals for line-voltage, single-pole, single-throw (SPST), dry-
contact relay to control compressor 1.50 to 6.0 mm2
(16 to 10 AWG)
Alarm L1/LC The common (LC), normally-open (LNO), normally-close (LNC)
terminals for line-voltage, single-pole, double-throw (SPDT), dry-
contact relay to control (user-supplied) alarm devices.
0.30 to 2.50 mm2
(22 to 14 AWG)
LNC
L2/N/LNO
LO-SPD
AUX
The A525 Controller includes two terminals for line-voltage, SPST,
dry-contact relay to control an auxiliary device such as a user-
provided alarm device or the low-speed on two-speed evaporator
fans. The A524 Controller does not include this relay and terminal
block.
0.30 to 2.50 mm2
(22 to 14 AWG)
HI-SPD Two terminals for line-voltage, SPST, dry-contact relay to control
single-speed evaporator fans or the high-speed on two-speed
evaporator fans.
0.75 to 2.50 mm2
(18 to 14 AWG)
Defrost Two terminals for line-voltage, SPST, dry-contact relay to control
resistive defrost heater or bypass defrost solenoid. 1.5 to 6.0 mm2
(16 to 10 AWG)
HVBIN Two line-voltage binary input terminals for use with the line-voltage
defrost temperature termination switch. These terminals require an
external power source to provide 120 to 240 VAC, 50/60 Hz
activation power when the external, user-supplied defrost
termination switch closes.
0.30 to 1.50 mm2
(22 to 16 AWG)
Table 5: SPST Compressor Relay Electrical Ratings
Agency and File UL 60730 EN 60730
Applied AC Voltage at 50/60 Hz 24 VAC 120 VAC 240 VAC 240 VAC
Horsepower -- 1 HP 1 HP 1 HP
Full Load Amperes -- 16 A 8 A 8 A
Locked Rotor Amperes -- 96 A 48 A 48 A
Resistive Amperes 10 A -- -- --
Pilot Duty VA 125 VA at 24 to 240 VAC
Table 6: SPDT Alarm Relay Electrical Ratings
Agency and File UL 60730 EN 60730
Applied AC Voltage at 50/60 Hz 24 VAC 120 VAC 240 VAC 240 VAC
Horsepower (LC/LNO and LC/LNC) -- 1/2 HP 1/2 HP 1/2 HP

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
9
Repair Information
Do not attempt to repair the A52x Controller. In case of a defective or improperly functioning controller, contact your
nearest authorized Johnson Controls/PENN Distributor or Sales Representative. When contacting your Johnson
Controls/PENN Distributor, have the model number of the controller available. This number can be found on the
label inside the cover of the controller.
Cleaning Information
Remove any loose debris from the controller. Use a soft cloth with a detergent solution to wipe the outside surface.
Rinse the cloth with clean water and wipe the controller until clean. Dry the controller with a soft cloth.
Full Load Amperes (LC/LNO and LC/LNC) -- 9.8 A 4.9 A 4.9 A
Locked Rotor Amperes (LC/LNO and LC/LNC) -- 58.8 A 29.4 A 29.4 A
Resistive Amperes (LC/LNO and LC/LNC) 10 A 10 A 10 A 10 A
Pilot Duty VA (LC/LNO and LC/LNC) 125 VA at 24 to 240 VAC
Table 7: SPST Low Speed Fan or Auxiliary (LO-SPD AUX) Relay Electrical Ratings 1
Agency and File UL 60730 EN 60730
Applied AC Voltage at 50/60 Hz 24 VAC 120 VAC 240 VAC 240 VAC
Horsepower -- 1/2 HP 1/2 HP 1/2 HP
Full Load Amperes -- 9.8 A 4.9 A 4.9 A
Locked Rotor Amperes -- 58.8 A 29.4 A 29.4 A
Resistive Amperes 10 A 10 A 10 A 10 A
Pilot Duty VA 125 VA at 24 to 240 VAC
1. Included on the A525 Controller but not on the A524 Controller.
Table 8: SPST High Speed Fan (HI-SPD) Relay Electrical Ratings
Agency and File UL 60730 EN 60730
Applied AC Voltage at 50/60 Hz 24 VAC 120 VAC 240 VAC 240 VAC
Horsepower -- 1/2 HP 1/2 HP 1/2 HP
Full Load Amperes -- 9.8 A 4.9 A 4.9 A
Locked Rotor Amperes -- 58.8 A 29.4 A 29.4 A
Resistive Amperes 10 A 10 A 10 A 10 A
Pilot Duty VA 125 VA at 24 to 240 VAC
Table 9: SPST Defrost Relay Electrical Ratings
Agency and File UL 60730 EN 60730
Applied AC Voltage at 50/60 Hz 24 VAC 120 VAC 240 VAC 240 VAC1
Resistive Amperes 10 A 24 A124 A124 A1
Pilot Duty VA 125 VA at 24 to 240 VAC
1. Rated for 24 A at temperatures up to 45°C (113°F). From 45C° to 60C° (113F° to 140F°), the Ampere rating decreases from
24 A to 15 A at a rate of 0.6 A per 1°C. The A525 Controller is not rated for use in ambient conditions above 60°C (140°F).
Table 6: SPDT Alarm Relay Electrical Ratings
Agency and File UL 60730 EN 60730

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
10
Notes:
• Do not use abrasive cleaning powders
• Do not use abrasive cleaning pads or brushes.
• Do not use solvents or cleaning solutions that can damage plastic.
Ordering Information
Table 10 on page 10 contains information about the A52x Controller accessories. For more information about A99B
Temperature Sensors, refer to the A99B Series Temperature Sensors Product/Technical Bulletin (LIT-125186) or
contact your nearest Johnson Controls/PENN distributor or sales representative.
Technical Specifications
Table 10: A52x Controller Accessories
Product Code Description
BKT287-1R 305 mm (12 in.) section of 35 mm DIN rail
BKT524-1K Bracket for mounting A52x Controller to 35 mm DIN rail, includes five mounting screws
A52x Refrigeration Controller with Adaptive Defrost
Product A524 / A525
Power Consumption 1.8 VA maximum
Supply Power 84 VAC to 260 VAC, 50/60 HZ, 10 VA maximum
Ambient Conditions Operating: -30C° to 60C° (-22F° to 140F°), 0 to 95% RH non-condensing
Shipping and Storage: -40C° to 85C° (-40F° to 185F°), 0 to 95% RH non-condensing
Temperature Sensing
Range
-40C° to 50C° (-40F° to 122F°)
Input Signal (Sn1 and
Sn2)
A99B PTC temperature sensors or
TS-6340K-F00 NTC temperature sensor
Input Signal (UI4 and UI5) 0–10 VDC input for leak detector status or dry contact binary input with a switch wired between
U14 or U15 and C
HVBIN Signal 120 VAC or 240 VAC
Sensor Offset Range ± 3ºC or ± 5ºF
RS485 MODBUS Max. distance is 100 ft., 9.6k baud is the default but 19.2k is also supported
External USB Use a standard USB flash drive to extract HACCP data or upgrade firmware revision for future
upgrades
Enclosure IP65 watertight, corrosion-resistant, high-impact thermoplastic
Dimensions (H x W x D) 196.8 mm (7.75 in.) x 190.5 mm (7.5 in.) x 82.6 cm (3.25 in.)
Weight 1.1 kg (2.4 lb)
Compliance United States: cULus Listed; UL60730-1, UL60730-2-9, File SA516;
FCC Compliant to CFR47, Part 15, Subpart B, Class B limits
Canada: cULus Listed; CAN/CSA-E60730-1:15, CAN/CSA-E60730-2-9:15, File SA516;
Industry Canada (IC) compliant to Canadian ICES-003, Class B limits
Europe: CE Mark – Johnson Controls declares that this product is in compliance with the
essential requirements and other relevant provisions of the EMC Directive and Low Voltage
Directive; RoHS Directive
Australia and New Zealand: RCM Mark, Australia/NZ emissions compliant

A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
11
1. When any A99B Series Temperature Sensor or NTC Temperature Sensor is connected to the A52x Controller, the range of
the displayed temperature values is restricted from -40°C to 60°C (-40°F to 140°F).
Table 11: UL Conformity Declaration Information
Information Description
Purpose of Control Sensing control/operating control
Construction of Control Electronic independently mounted control
Number of Cycles Compressor relay: 100,000 cycles
Defrost relay: 30,000 cycles
Evaporator fan relays: 30,000 cycles
Alarm relay: 8,000 cycles
Method of Mounting Control Four mounting screws or optional DIN rail mounting kit
Type 1C or Type 2C Action Micro-interruption
Heat and Fire Resistance Category D
Rated Impulse Voltage 4000 V
Ball Pressure Temperature 125°C (257°F)
Cover Screw Torque Requirements
Instruction
To maintain Type IP65 rating, tighten enclosure cover screws to 0.9–1.1 N·m (8–
10 in·lb)
Table 12: A99B Type PTC Temperature Sensors
Ambient Sensing and
Operating Conditions 1
Type A99BA and A99BB: -40C° to 100C° (-40F° to 212F°) 0 to 100% RH, condensing
Type A99BC: -40C° to 120C° (-40F° to 248F°) 0 to 100% RH, condensing
Reference Resistance 1,035 ohms at 25°C (77°F) and 855 ohms at 0°C (32°F)
Accuracy 0.5°C (0.9°F) between -15C° and 57C° (5F° and 167F°). Refer to the A99B Series
Temperature Sensors Product/Technical Bulletin (LIT-125186) for accuracy rating
outside of this temperature range.
Sensor Construction Probe: stainless steel (50 mm x 6.0 mm); Cable length: A99Bx-200 (2 m); A99Bx-300
(3 m); A99Bx-500 (5 m)
Sensor Cable Sheath Type A99BA: shielded PVC cable
Type A99BB: PVC cable
Type A99BC: high temperature silicon cable
Wire Gauge 22 AWG (0.33 mm2)
Ambient Storage Conditions Type A99BA and A99BB: -40C° to 105C° (-40F° to 221F°); 0 to 100% RH, condensing
Type A99BC: -40C° to 130C° (-40F° to 266F°); 0 to 100% RH, condensing
Shipping Weight 41 g (1.4 oz) for A99B sensor with 2 m (6 1/2 ft) cable
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
Table 13: TS6340K-F00 NTC Temperature Sensor
Ambient Sensing and
Operating Conditions 1
-40C° to 100C° (-40F° to 212F°); 0 to 100% RH, condensing
Reference Resistance 10,000 ohms at 25°C (77°F)
Sensor Construction Probe: stainless steel (50 mm x 6.0 mm); Cable length: 1.5 m
Sensor Cable Sheath PVC cable

® Johnson Controls and PENN are registered trademarks of Johnson Controls in the
United States of America and/or other countries. All other trademarks used herein are the property
of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved.
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
Published in U.S.A. www.johnsoncontrols.com
A52x Series Refrigeration Controller with Adaptive Defrost Installation Instructions
12
North American Emissions Compliance
United States
Canada
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Other manuals for A52 Series
1
This manual suits for next models
2
Table of contents
Other Penn Controllers manuals