Penn P216 User manual

These controllers are designed for speed variation of single
phase motors, especially for fan speed control on air cooled
condensers. Head pressure control of a refrigeration system,
through speed variation of the fan on an air-cooled condenser,
results in optimum performance throughout the year.
Using a pressure transducer as the input device to the fan
speed controller, gives the most direct and fastest response
to pressure variations in the refrigerant system. The controller
varies the supply voltage to the motor from 20% to 100%
over the proportional band using the phase cutting principle.
If the pressure drops below the adjusted setpoint minus the
proportional band, the output to the motor is zero volt or the
adjusted min. speed setting. This provides speed variation of
permanent split capacitor or shaded pole motors which do not
draw more than 12 A (rms) full load current.
The controller used for dual pressure input varies the fan speed
by directly sensing the pressure changes of two separate
refrigerant circuits. The setpoint of each pressure transducer
can be separately adjusted. The controller selects the input with
the greatest cooling demand to control the fan speed.
The transducers can be used in non-corrosive refrigerant
systems.
The motor manufacturer should have approved his product for
this speed control principle. It is recommended to conrm with
the electric motor manufacturer, that the motor can be used
with a controller, using the phase cutting principle for speed
variation.
You can also provide a copy of this P216 product data sheet to
the motor manufacturer/supplier for review.
Features
• The new benchmark in standard FSC
• Easy to install and easy to operate
• Output range: 0,5 to 12 Amp (1 phase)
• Input 0-10 Vdc
• Including 0-50 bar pressure transducer P499VCS-405C
• Heatpump mode
• Reverse operation mode
• Master / Slave mode
• Fixed pressure ranges for direct replacement (P215)
• Setpoint and min speed potmeters
PB_P216_11 2016
P216
Condenser fan speed controller
Product bulletin

PB_P216_11 2016
2
Dimensions (mm)
165
178
76
66
Installation
The P216 can be used for single or dual pressure input.
In the case of dual input the controller selects the input with the greater cooling demand to control the fan speed.
There are four pressure ranges:
• 4 to 10 bar
• 8 to 14 bar
• 14 to 24 bar
• 22 to 42 bar

PB_P216_11 2016
3
Wiring
WARNING: Risk of electric shock.
Disconnect or isolate all power supplies before
making electrical connections. More than one
disconnect or isolation may be required to
completely de-energize equipment. Contact with components
carrying hazardous voltage can cause electric shock and may
result in severe personal injury or death.
IMPORTANT: Do not connect supply power to the P216
Series controller before finishing wiring and checking all wiring
connections. Short circuits or improperly connected wires can
result in damage to the P216 series controller and void any
warranty.
IMPORTANT: Do not exceed the P216 Series Fan Speed
Controller electrical ratings. Exceeding P216 Series controller
electrical ratings can result in permanent damage to the P216
Series controller and void any warranty.
IMPORTANT: Use copper conductors only. Make all wiring in
accordance with local, national, and regional regulations.
IMPORTANT: Electrostatic discharge can damage P216
controller components. Use proper Electrostatic Discharge
(ESD) precautions during installation and servicing to avoid
damaging P216 components.
• Ensure that the wires between the P216 Series
controller and the fan motor do not exceed 15 m.
• Wires connected to the line-voltage terminal block must
be 3.31 mm2(12 AWG) or smaller.
• Low-voltage wires must be less than 30 m.
Description
A DIP switch will be used to select one of 4 different
pressure ranges. There is one potentiometer to manually
adjust the setpoint.
• There is one potentiometer to manually adjust the
minimum speed.
• A green LED will indicate that power is applied.
• Two 3 position screw terminal blocks will be used to
connect the 50 bar transducers.
• A 3 position screw terminal block will be used to select
HP or reverse modes.
Contacts between HP and C will run the fan at full speed.
Contacts between REV and C will increase the fan speed
as pressure decreases.
• Adjustable 4 to 10 bar setpoint, prop band xed at 2.0 bar
• Adjustable 8 to 14 bar setpoint, prop band xed at 2.5 bar
• Adjustable 14 to 24 bar setpoint, prop band xed at 4.0 bar
LED
M1 L1
L2/N
L2/N
HP C REV
V P2 C
V P1 C
20% 100%
-
+
Figure 1
CAUTION
The P216 is intended to control equipment under
normal operating conditions. Where failure or
malfunction of the P216 could lead to an abnormal
operating condition that could cause personal injury or
damage to the equipment or other property, other devices
(limit or safety controls) or systems (alarm or supervisory
systems) intended to warn of or protect against failure or
malfunction of the P216 must be incorporated into and
maintained as part of the control system.
EMC
The controller does have a built-in suppression lter
and meets all required EC directives. Please note that
when two or more EMC compliant components are built
together the total system may not be compliant. To make
the total system compliant is the responsibility of the
producer.
Note:More motors can be wired in parallel, provided that
the total current will not exceed 12 A rms.
Input connections
The input can be connected as indicated in Figure 1.
If the distance between the transducer and the controller
exceeds 30 metres, shielded cable has to be used.
Heatpump
and reverse action
terminal
Power supply
and motor terminal
Earth ground
connection
Two pressure
transducers inputs
Setpoint
Min speed
DIP switch block

PB_P216_11 2016
4
DIP switch settings and wiring diagram
Min speed switch
ON = Motor never stops, always runs at min speed or
greater, depending on conditions.
OFF = Minimum speed feature is disabled.
Motor shuts completely off at low pressure
P216 operation
using P499VCS-405C transducers
SW1 SW2 SW3 Mode
Setpoint range
CCW - CW
(BAR)
Proportional band
(BAR)
OFF OFF OFF Master 4 - 10 2,0
OFF ON OFF Master 8 - 14 2,5
ON OFF OFF Master 14 - 24 4,0
ON ON OFF Master 22 - 42 5,0
P216 operation
in slave mode
SW1 SW2 SW3 Mode
Setpoint range
CCW - CW
(Vdc)
Proportional band
(BAR)
OFF OFF ON Slave 2 - 10 Vdc (See Note 1)
OFF ON ON Slave 1 - 5 Vdc
Note 1: The proportional band in slave mode extends from 0 Vdc to the setpoint voltage
TB1
M1 L1 L2/N L2/N
VAC
When switch 3 is set to ON, the slave mode is selected and the setpoint potentiometer denes the input voltage level that
causes the motor to run at full speed.
For example:
• If the 2–10 Vdc setpoint range is selected and the setpoint potentiometer is adjusted completely to "+", then the motor
will run at full speed when Vin = 10 Vdc.
• If the setpoint potentiometer is adjusted midway between "-" and "+", then the motor will run at full speed when Vin = 6,0 Vdc
(see Figure 3).
1 2 3 4
ON
Power supply
208 - 240 Vac 50/60 Hz
Fan-motor

PB_P216_11 2016
5
Normal operation example using a 230 V supply
Output voltage vs input pressure
16 Bar
220 V
46 V
1 2 3 4
ON
20% 100%
-
+
0 V
20 Bar
Figure 2
0 – 10 Vdc slave operation example using 230 V supply
Output vs input voltage
6,0 Vdc
220 V
230 V*0,2 = 46 V
1 2 3 4
ON
20% 100%
-
+
0 V
10,0 Vdc
+-
V P1 C
Figure 3
Note
Set switches 1–3 as shown to select a
14-24 Bar setpoint range with a 4 Bar
proportional band.
Adjust the setpoint potentiometer to
20 Bar (which is 60% rotation from
the "-" or CCW end of the setpoint
potentiometer).
Adjust the minimum speed potentiometer
completely CCW (to set the minimum
speed to 20% of 230 V or 46 V).
Setting switch 4 to ON causes the
motor to always run at minimum speed
or greater.
Note 1
If min speed is set to 40%, then output
turns off at 230 V*0,4 = 92 VAC when
input voltage drops to 6,0 V* 0,4 = 2,4 Vdc
DIP switch block
Min speed 20%
Setpoint 60% from “-”
Output to motor
(VAC)
Min. speed
Input (Pressure - Bar)
Setpoint
Proportional
band
DIP switch block
Min speed
20%
Setpoint
at midscale
Proportional band
Setpoint
Output to motor
(VAC)
6,0 V*0,2 = 1,2 Vdc
20% min speed
Switch 4 = OFF
Input (Voltage)
See "Note 1"
DC voltage
connection
0 - 10 Vdc
Control signal

PB_P216_11 2016
6
P216 series controllers are designed to reference either
one or two Johnson Controls P499 electronic pressure
transducers to monitor condenser pressure.
On P216 series controller applications that use two P499
transducers, the P216 series controller always references
the transducer that is sensing the highest pressure.
IMPORTANT
Operate the P216 only in combination with one or
two P499-VCS-405C pressure transmitters.
Only P499 models that have a 0-10 Vdc output signal can
be used with the P216 control.
Wire connection Terminal
Red V
Black C
White P
P499 electronic pressure transducers
P216 performance using high efciency motors
Current rating based on DI percent
Maximum Amps %DI
12.00 0
11.43 5
10.91 10
10.43 15
10.00 20
9.60 25
9.23 30
8.89 35
8.57 40
8.28 45
8.00 50
7.74 55
Note:High efciency motors must comply with ERP 2015.
%Di is stated in the fan motor specications and indicates the value of extra current that the motor is consuming at
medium speed.
For example:
%DI = 55 means that a 5A motor consumes a 2,75 A more current so 7,75 A at inrush and up to medium speed.
This means that the P216 is limited to 7,75 A, so it is not possible to connect 2 motors in parallel.
For a fan motor with %DI = 0, the P216 can deliver 12 A maximum.

Technical specication
Product type P216EEA-2K / P216EEA-101C
Power supply 208 - 240 VAC, 50/60 Hz
Pressure range
Adjustable 4 to 10 bar setpoint, prop band fixed at 2.0 bar
Adjustable 8 to 14 bar setpoint, prop band fixed at 2.5 bar
Adjustable 14 to 24 bar setpoint, prop band fixed at 4.0 bar
Adjustable 22 to 42 bar setpoint, prop band fixed at 5.0 bar
Pressure transducer P499VCS-405C pressure transducer included with 0- 50 bar range
Input signal 0 – 10 Vdc
Control action Direct or reverse mode
Maximum current 12 Amp
Minimum current 0,5 Amp
Protection class IP54
Ambient operating conditions -40 °C to 60 °C
Storage temperature -40 °C to 85 °C
Dimensions (H x W x D) 159 x 177 x 70 mm
Weight 1 kg
MTTR 20 years
Conformity
Johnson Controls International plc declares that these products are in compliance with the
essential requirements and other relevant provisions of the EMC Directive and
Low Voltage Directive.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult
the local Johnson Controls office. Johnson Controls Internation plc shall not be liable for damages resulting from misapplication or misuse of its products.
PB_P216_11 2016
www.johnsoncontrols.com
Building Efciency
Headquarters: Milwaukee, Wisconsin, USA
Branch Officies: Principal Cities World-wide
Metasys®and Johnson Controls®are registered trademarks of Johnson Controls International plc.
All other marks herein are the marks of their respective owners.
© Copyright 2016 Johnson Controls International plc. All rights reserved. Any unauthorized use or copying is strictly prohibited.
Table of contents
Other Penn Controllers manuals

Penn
Penn TC3203 User manual

Penn
Penn A421ABC-03C User manual

Penn
Penn TC3B23 User manual

Penn
Penn P47 Series User manual

Penn
Penn System 450 Series User manual

Penn
Penn MR5 Series Service manual

Penn
Penn P70 Series User manual

Penn
Penn TC3201 User manual

Penn
Penn P78 Series User manual

Penn
Penn TC3223 User manual