PR PREASY 4222 User manual

Programmable displays with a wide se-
lection of inputs and outputs for display of temperature,
volume and weight, etc. Feature linearisation, scaling,
and difference measurement functions for programming
via PReset software.
Interfaces for analogue and digital
signals as well as HART®signals between sensors / I/P
converters / frequency signals and control systems in Ex
zone 0, 1 & 2 and for some modules in zone 20, 21 & 22.
Galvanic isolators for analogue and digital
signals as well as HART®signals. A wide product range
with both loop-powered and universal isolators featuring
linearisation, inversion, and scaling of output signals.
PC or front programmable modules with
universal options for input, output and supply. This range
offers a number of advanced features such as process
calibration, linearisation and auto-diagnosis.
A wide selection of transmitters for DIN
form B mounting and DIN rail modules with analogue
and digital bus communication ranging from application-
specific to universal transmitters.
Displays
Temperature
Isolation
Ex interfaces
Universal
DK
UK
FR
DE
Side 1
Page 25
Page 49
Seite 73
SIGNALS THE BEST
4222
Universal
I/f Converter
No. 4222V100-IN (0845)
From ser. no.060867001

UNIVERSEL I/f KONVERTER
PREASY 4222
INDHOLDSFORTEGNELSE
Advarsler ............................................................................ 2
Sikkerhedsregler................................................................. 3
Overensstemmelseserklæring............................................ 5
Afmontering af SYSTEM 4000 ........................................... 6
Avancerede features .......................................................... 7
Anvendelse......................................................................... 7
Teknisk karakteristik........................................................... 7
PR 4501 display- / programmeringsfront .......................... 8
Applikationer ...................................................................... 9
Bestillingsnumre................................................................. 10
Elektriske specifikationer ................................................... 10
Konfigurering af følerfejlsdetektering ................................. 13
Displayvisning på 4501:
Display uden for område................................................ 13
Grænser for følerfejlsdetektering ................................... 14
Grænser for signalbehandling........................................ 14
Fejlvisninger.................................................................... 14
Tilslutninger ........................................................................ 15
Blokdiagram ....................................................................... 16
Programmering / betjening af trykknapper........................ 17
Rutediagram....................................................................... 20
Rutediagram, avancerede indstillinger (ADV.SET).............. 23
Rullende hjælpetekster i displaylinie 3............................... 24
1

SIGNATURFORKLARING
Trekant med udråbstegn: Advarsel / krav.
Hændelser der kan føre til livstruende situationer.
CE-mærket er det synlige tegn på modulets overensstemmelse med EU-
direktivernes krav.
Dobbelt isolation er symbolet for, at modulet overholder ekstra krav til
isolation.
SIKKERHEDSREGLER
DEFINITIONER:
Farlige spændinger er defineret som områderne: 75...1500 Volt DC og 50...1000
Volt AC.
Teknikere er kvalificerede personer, som er uddannet eller oplært til at kunne
udføre installation, betjening eller evt. fejlfinding både teknisk og sikkerhedsmæs-
sigt forsvarligt.
Operatører er personer, som under normal drift med produktet skal indstille og
betjene produktets trykknapper eller potentiometre, og som er gjort bekendt med
indholdet af denne manual.
MODTAGELSE OG UDPAKNING:
Udpak modulet uden at beskadige dette, og sørg for, at manualen altid følger
modulet og er tilgængelig. Indpakningen bør følge modulet, indtil dette er mon-
teret på blivende plads.
Kontrollér ved modtagelsen, at modultypen svarer til den bestilte.
MILJØFORHOLD:
Undgå direkte sollys, kraftigt støv eller varme, mekaniske rystelser og stød, og
udsæt ikke modulet for regn eller kraftig fugt. Om nødvendigt skal opvarmning,
ud over de opgivne grænser for omgivelsestemperatur, forhindres ved hjælp af
ventilation.
Alle moduler hører til Installationskategori II, Forureningsgrad 1 og Isolations-
klasse II.
INSTALLATION:
Modulet må kun tilsluttes af teknikere, som er bekendte med de tekniske udtryk,
advarsler og instruktioner i manualen, og som vil følge disse.
Hvis der er tvivl om modulets rette håndtering, skal der rettes henvendelse til den
lokale forhandler eller alternativt direkte til:
32
ADVARSEL
SYSTEM 4000 skal monteres på DIN-skinne efter DIN 46277.
ADVARSEL
Dette modul er beregnet for tilslutning til livsfarlige elektriske
spændinger. Hvis denne advarsel ignoreres, kan det føre til alvor-
lig legemsbeskadigelse eller mekanisk ødelæggelse.
For at undgå faren for elektriske stød og brand skal manualens
sikkerhedsregler overholdes, og vejledningerne skal følges.
Specifikationerne må ikke overskrides, og modulet må kun
benyttes som beskrevet i det følgende. Manualen skal studeres
omhyggeligt, før modulet tages i brug. Kun kvalificeret personale
(teknikere) må installere dette modul. Hvis modulet ikke benyttes
som beskrevet i denne manual, så forringes modulets beskyt-
telsesforanstaltninger.
ADVARSEL
Der må ikke tilsluttes farlig spænding til modulet, før dette er fast-
monteret, og følgende operationer bør kun udføres på modulet i
spændingsløs tilstand og under ESD-sikre forhold:
Installation, ledningsmontage og -demontage.
Fejlfinding på modulet.
Reparation af modulet og udskiftning af sikringer må kun
foretages af PR electronics A/S.
ADVARSEL
Modulets frontplade må ikke åbnes, da dette vil medføre skade
på stikforbindelsen til display- / programmeringsfronten PR 4501.
Modulet indeholder ingen DIP-switche eller jumpere.
FARLIG
SPÆNDING
GENERELT
INSTAL-
LATION

OVERENSSTEMMELSESERKLÆRING
Som producent erklærer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hermed at følgende produkt:
Type: 4222
Navn: Universel I/f konverter
er i overensstemmelse med følgende direktiver og standarder:
EMC-direktivet 2004/108/EF og senere tilføjelser
EN 61326-1
For specifikation af det acceptable EMC-niveau henvises til modulets
elektriske specifikationer.
Lavspændingsdirektivet 2006/95/EF og senere tilføjelser
EN 61010-1
Rønde, 4. november 2008 Peter Rasmussen
Producentens underskrift
5
PR electronics A/S, Lerbakken 10, 8410 Rønde,
Danmark, tlf: +45 86 37 26 77.
Installation og tilslutning af modulet skal følge landets gældende regler for instal-
lation af elektrisk materiel bl.a. med hensyn til ledningstværsnit, for-sikring og
placering.
Beskrivelse af indgang / udgang og forsyningsforbindelser findes på blokdia-
grammet og sideskiltet.
For moduler, som er permanent tilsluttet farlig spænding, gælder:
For-sikringens maksimale størrelse er 10 A, og den skal sammen med en
afbryder placeres let tilgængeligt og tæt ved modulet. Afbryderen skal
mærkes således, at der ikke er tvivl om, at den afbryder spændingen
til modulet.
Produktionsår fremgår af de to første cifre i serienummeret.
UL-INSTALLATIONSKRAV:
Brug kun 60/75°C kobberledninger.
Må kun anvendes i forureningsgrad 2 eller bedre.
Max. omgivelsestemperatur................... 60°C
Max. ledningskvadrat............................. AWG 26-14
UL fil-nummer ........................................ E231911
KALIBRERING OG JUSTERING:
Under kalibrering og justering skal måling og tilslutning af eksterne spændinger
udføres i henhold til denne manual, og teknikeren skal benytte sikkerhedsmæs-
sigt korrekte værktøjer og instrumenter.
BETJENING UNDER NORMAL DRIFT:
Operatører må kun indstille eller betjene modulerne, når disse er fast installeret
på forsvarlig måde i tavler el. lignende, så betjeningen ikke medfører fare for liv
eller materiel. Dvs., at der ikke er berøringsfare, og at modulet er placeret, så det
er let at betjene.
RENGØRING:
Modulet må, i spændingsløs tilstand, rengøres med en klud let fugtet med destil-
leret vand.
ANSVAR:
I det omfang instruktionerne i denne manual ikke er nøje overholdt, vil kunden
ikke kunne rette noget krav, som ellers måtte eksistere i henhold til den indgåede
salgsaftale, mod PR electronics A/S.
4

UNIVERSEL I/f KONVERTER
PREASY 4222
• Indgang for RTD, TC, Ohm, potentiometer, mA og V
• Frekvensudgang NPN, PNP og TTL
• Genererer frekvenser fra 0,001...25000 Hz
• 2-trådsforsyning > 16 V
• Universel forsyning med AC eller DC
Avancerede features:
• Programmerbar via aftagelig displayfront (4501), proceskalibrering, signal-
simulering, passwordbeskyttelse, fejldiagnosticering og valg af hjælpetekster
på flere sprog.
Anvendelse:
• Lineariseret elektronisk temperaturmåling med modstandsføler eller termoele-
mentføler.
• Omsætning af lineær modstandsændring til frekvenssignal, f.eks. fra ventiler,
spjæld eller lineære bevægelser med påmonteret potentiometer.
• Spændingsforsyning og signalisolator for 2-trådstransmittere.
• Styring af procesforløb med frekvenssignal til f.eks. PLC eller procescomputer.
• Galvanisk adskillelse og konvertering af analoge signaler til frekvenssignaler.
Teknisk karakteristik:
• Med påmonteret display- / programmeringsfront kan alle driftsparametre tilpas-
ses enhver applikation. Elektroniske hardwareswitche betyder, at modulet ikke
skal åbnes for indstilling af DIP-switche.
• Grøn LED i front indikerer normal drift.
• Der er løbende sikkerhedscheck af gemte data.
• 3-port 2,3 kVAC galvanisk isolation.
7
AFMONTERING AF SYSTEM 4000
Husk først at demontere tilslutningsklemmerne med farlig spænding.
Billede 1:
Modulet frigøres fra DIN-skinnen ved
at løfte i den nederste lås.
6

33
32
31
+
-
+
-
44
43
42
41
24
23
22
21
PR 4501 DISPLAY- / PROGRAMMERINGSFRONT
Funktionalitet:
Den enkle PReasy menustruktur og de forklarende hjælpe-
tekster leder dig automatisk gennem opsætningen, og
gør produktet meget enkelt at anvende. Se beskrivelse
af funktioner og opsætningsmuligheder under afsnittet
”Progammering / betjening af trykknapper”.
Anvendelse:
• Kommunikationsinterface til ændring af driftsparametre i 4222.
• Kan flyttes fra en 4222 til en anden 4222 og downloade den første konverters
opsætning til efterfølgende konvertere.
• Som fastmonteret display til visualisering af procesdata og status.
Teknisk karakteristik:
• Fire liniers LCD-display; linie 1 (5,57 mm høj) viser indgangssignal, linie 2 (3,33
mm høj) viser enheder - UNIT. Linie 3 kan skifte mellem digital udgangsværdi
og skalering (kHz, Hz, mHz, P/m, P/h, P/d) eller vise TAG-nr. Linie 4 viser ten-
densvisning for indgangssignal og status for kommunikation.
• Programmeringsadgang kan forhindres ved indkodning af et password.
Passwordet gemmes i konverteren, så sikkerheden mod uønskede ændringer
er så høj som muligt.
Montage / installation:
• Klikkes på fronten af 4222.
98
Applikationer
Indgangssignaler:
Strøm
Spæn-
ding
Poten-
tiometer RTD og lin.R TC
Forbindelse, ledere
Udgangssignaler:
Forsyning:
21,6...253 VAC
eller
19,2...300 VDC
PNP, +24 V
Frekvensudgang
NPN, 24 V
Udg. Gnd.
TTL, 5 V

Hjælpespændinger:
2-trådsforsyning (klemme 44...43) .............. 25...16 VDC / 0...20 mA
Ledningskvadrat (max.)............................... 1 x 2,5 mm2flerkoret ledning
Klemskruetilspændingsmoment.................. 0,5 Nm
Relativ luftfugtighed .................................... < 95% RH (ikke kond.)
Mål, uden displayfront (HxBxD) .................. 109 x 23,5 x 104 mm
Mål, med displayfront (HxBxD) ................... 109 x 23,5 x 116 mm
Kapslingsklasse (kabinet / klemmer)........... IP50 / IP20
Vægt............................................................ 155 g / 170 g med 4501
RTD-, lineær modstands- og potentiometerindgang:
Indgang for RTD-typer:
Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000
Kabelmodstand pr. leder, RTD (max.) ......... 50 Ω
Følerstrøm, RTD.......................................... Nom. 0,2 mA
Virkning af følerkabelmodstand
(3- / 4-leder), RTD ....................................... < 0,002 Ω/ Ω
Følerfejlsdetektering, RTD........................... Ja
Kortslutningsdetektering, RTD .................... < 15 Ω
11
BESTILLINGSNUMRE:
4222 = Universel I/f konverter
4501 = Display- / programmeringsfront
Elektriske specifikationer:
Specifikationsområde ................................ -20 til +60°C
Fælles specifikationer:
Forsyningsspænding, universel................... 21,6...253 VAC, 50...60 Hz eller
19,2...300 VDC
Max. forbrug................................................ ≤2,5 W
Sikring ......................................................... 400 mA T / 250 VAC
Isolationsspænding, test / drift ................... 2,3 kVAC / 250 VAC
Kommunikationsinterface............................ Programmeringsfront 4501
Signal- / støjforhold..................................... Min. 60 dB (0...100 kHz)
Reaktionstid (0...90%, 100...10%), programmerbar:
Temperaturindgang................................. 1...60 s
mA- / V-indgang...................................... 0,4...60 s
Kalibreringstemperatur................................ 20...28°C
Nøjagtighed, størst af generelle og basisværdier:
10
EMC-immunitetspåvirkning............................ < ±0,5% af span
Udvidet EMC-immunitet:
NAMUR NE 21, A-kriterium, gniststøj............ < ±1% af span
Indgangs-
type Min.
værdi Max.
værdi Standard
Pt100
Ni100
Lin. R
Potentiometer
-200°C
-60°C
0Ω
10 Ω
+850°C
+250°C
10000 Ω
100 kΩ
IEC60751
DIN 43760
-
-
Basisværdier
Indgangstype Basis-
nøjagtighed Temperatur-
koefficient
mA ≤±4 µA ≤±0,4 µA / °C
Volt ≤±20 µV ≤±2 µV / °C
Pt100 ≤±0,2°C ≤±0,01°C / °C
Lin. R ≤±0,1 Ω≤±0,01 Ω/ °C
Potentiometer ≤±0,1 Ω≤±0,01 Ω/ °C
TC-type:
E, J, K, L, N, T, U ≤±1°C ≤±0,05°C / °C
TC-type: B, R, S,
W3, W5, LR ≤±2°C ≤±0,2°C / °C
Generelle værdier
Indgangstype Absolut
nøjagtighed Temperatur-
koefficient
Alle ≤±0,1% af span ≤±0,01% af span / °C

PNP-udgang:
Iout max. ...................................................... 30 mA
Vout .............................................................. 24 VDC ±10%
Cout.............................................................. 10 nF
Rout typ........................................................ 20 Ω
Elektromekanisk tæller................................ 24 VDC / 135 mA / 20 ms / ≤ 10Hz
NPN-udgang:
Isink max. ..................................................... 150 mA
Isink max. peak ............................................ 300 mA
Ekstern spænding (klemme 23), max. ........ 55 VDC
Cout.............................................................. 10 nF
Rout typ........................................................ 10 Ω
TTL-udgang:
Isink/source max............................................. 15 mA
Isink/source peak............................................ 100 mA
Vout .............................................................. 5 V ±5%
Cout.............................................................. 10 nF
Rout typ........................................................ 55 Ω
Følerfejlsdetektering
Programmerbar ........................................... 0...26250 Hz
Overholdte myndighedskrav: Standard:
EMC 2004/108/EF....................................... EN 61326-1
LVD 2006/95/EF .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508
Af span = af det aktuelt valgte område
Konfigurering af følerfejlsdetektering:
Displayvisning på 4501:
Display uden for område:
13
TC-indgang:
Koldt loddestedskomp. (CJC)
via internt monteret føler......................... < ±1,0 °C
Følerfejlsdetektering, alle TC-typer............. Ja
Følerfejlsstrøm:
under detektering.................................... Nom. 2 µA
ellers........................................................ 0 µA
Strømindgang:
Måleområde ................................................ -1...25 mA
Programmerbare måleområder ................... 0...20 og 4...20 mA
Indgangsmodstand ..................................... Nom. 20 Ω+ PTC 50 Ω
Følerfejlsdetektering:
strømsløjfebrud 4...20 mA....................... Ja
Spændingsindgang:
Måleområde ................................................ -20 mV...12 VDC
Programmerbare måleområder ................... 0...1 / 0,2...1 / 0...2,5 / 0,5...2,5 /
0...5 / 1...5 / 0...10 og 2...10 VDC
Indgangsmodstand ..................................... Nom. 10 MΩ
Udgang:
Frekvensudgang:
Frekvensområde.......................................... 0...25000 Hz
Min. frekvens (span) .................................... 0,001 Hz
Duty cycle (0...25000 Hz) ............................ 50% eller
Programmerbar impulstid (f ≤500 Hz)........ 1...1000 ms (max. 90% duty cycle)
12
Type Min.
værdi Max.
værdi Standard
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
+400°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
-200°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
Modul: Konfiguration Følerfejlsdetektering:
4222 OUT.ERR=NO OFF
Ellers: ON
Display under min.- / over max.-visning (-1999, 9999):
Indgang Område
Blinkende
visning Grænse
Alle Alle -1999 Displayværdi <-1999
9999 Displayværdi >9999

21 22 23 24 21 22 23 24 21 22 23 24
+
-
41 42 44
43
41 42 44
43 41 42 44
43
+
-
41 42 44
43
42 44
43
41
+
-Tx
41 42 44
43
+
-
41 42 44
43
41 42 44
43
41 42 44
43
31 32 33
14 15
Grænser for følerfejlsdetektering:
Grænser for signalbehandling:
Fejlvisninger:
Uden for område visning (IN.LO, IN.HI):
Ved overskridelse af A/D-konverterens eller polynomiets gyldige område.
Indgang Område Visning Grænse
VOLT
0...1 V / 0,2...1 V IN.LO < -25 mV
IN.HI > 1,2 V
0...2,5 / 0,5...2,5 / 0...5 V / 1...5 V /
0...10 V / 2...10 V
IN.LO < -25 mV
IN.HI > 12 V
CURR 0...20 mA / 4...20 mA IN.LO < -1,05 mA
IN.HI > 25,05 mA
LIN.R
0...800 ΩIN.LO < 0 Ω
IN.HI > 1075 Ω
0...10 kΩIN.LO < 0 Ω
IN.HI < 110 kΩ
POTM Min. visning = 0%, Max. visning = 100% IN.LO < -0,5 %
IN.HI > 100,5 %
TEMP TC / RTD IN.LO < temperaturområde -2°C
IN.HI > temperaturområde +2°C
Følerfejlsdetektering (SE.BR, SE.SH):
Indgang Område Visning Grænse
CURR Strømsløjfebrud (4...20 mA) SE.BR <= 3,6 mA; > = 21 mA
POTM Alle, SE.BR på alle 3-ledere SE.BR > ca. 126 kΩ
LIN.R 0...800 ΩSE.BR > ca. 875 Ω
0...10 kΩSE.BR > ca. 11 kΩ
TEMP
TC SE.BR > ca. 750 kΩ/ (1,25 V)
RTD: 2-, 3- og 4-leder
Ingen SE.SH for Pt10, Pt20 og Pt50
SE.BR > ca. 15 kΩ
SE.SH < ca. 15 Ω
Visning ved hardwarefejl
Fejlsøgning Visning Årsag
Test af intern CJC-sensor CJ.ER CJC-sensor defekt eller tem-
peratur uden for område
Checksum test af den aktuelle konfiguration i FLASH FL.ER Fejl i FLASH
Test af 4501 / 4222 kommunikation NO.CO Fejl i stikforbindelse
Check om indgangssignal passer med indgangskonfiguration IN.ER 1) Fejlniveauer på indgang
Check om gemt konfiguration i 4501 passer med modul TY.ER Konfiguration er ikke 4222
! Alle fejlvisninger i display blinker 1 gang pr. sekund samt suppleres med tilhørende hjælpetekst.
1) Fejlen resettes ved at slukke og tænde for modulet.
TILSLUTNINGER:
Indgange:
Udgange:
Forsyning:
RTD, 3- / 4-leder
Modstand,
3- / 4-leder Potentiometer Strøm2-Trådstransmitter
Spænding
NPNTTL
Gnd.+5 V Gnd. +
PNP
Gnd. +24 V
RTD, 2-leder Modstand, 2-lederTC

CPU
CPU
EEPROM
A / D
PTC
CJC
0.2 mA
43
44
42
41
432
10 Ω
MUX
+
-
+
-
+
-
4 *4#
HIEJ
4222 21
22
23
31
33
24
PROGRAMMERING /
BETJENING AF TRYKKNAPPER
Dokumentation til rutediagram.
Generelt:
Når du skal konfigurere 4222, bliver du guidet igennem samtlige parametre og
kan vælge netop de indstillinger, der passer til applikationen. Til hver menu
findes en rullende hjælpetekst, som vises i displaylinie 3.
Konfigurationen udføres ved hjælp af de 3 taster:
forøger talværdien eller vælger næste parameter
formindsker talværdien eller vælger forrige parameter
accepterer valget og går til næste menu
Når konfigurationen er gennemført, returneres til normaltilstand 1.0.
Tryk og hold tasten nede for at gå til forrige menu eller normaltilstand (1.0)
uden at gemme de ændrede tal eller parametre.
Hvis ingen taster har været aktiveret i 1 minut, returnerer displayet til normal-
tilstand (1.0) uden at gemme de ændrede tal eller parametre.
Uddybende forklaringer:
Passwordbeskyttelse: Programmeringsadgang kan forhindres ved indkodning
af et password. Passwordet gemmes i konverteren, så sikkerheden mod uøn-
skede ændringer er så høj som muligt. Default password 2008 giver adgang til
alle programmeringsmenuer.
1716
BLOKDIAGRAM:
Potentiometer
2-trådstransmitter
Spænding
Strøm
RTD og lin.R,
leders
forbindelse
Forsyning
Forsyning
21,6...253 VAC eller
19,2...300 VDC
Gnd.
TC
Grøn
Gul
NPN
PNP, 24 V
TTL, 5 V
Frekvens-
generator

18 19
Signal- og følerfejlsinformation via displayfront 4501
Følerfejl (se grænser i skema) vises i display med SE.BR (sensor break) eller
SE.SH (sensor short). Signaler uden for det valgte område (ikke følerfejl, se
skema for grænser) vises i display som IN.LO (lavt indgangssignal) eller IN.HI
(højt indgangssignal). Fejlindikeringen vises i 3. linie i tekst, samtidig med at
baggrundsbelysningen blinker. 4. linie i displayet er en statuslinie, der viser
COM (blinkende bullet), som indikerer, om 4501 fungerer korrekt, og pil op/ned
der er tendensvisning på indgangssignalet.
Signal- og følerfejlsindikering uden displayfront
Status på enheden kan også aflæses på den grønne LED i fronten af modulet.
Grøn blinkende LED 13 Hz indikerer normal drift.
Grøn blinkende LED 1 Hz indikerer følerfejl.
Konstant grøn LED indikerer intern fejl.
Avancerede funktioner
Enheden giver adgang til en række avancerede funktioner, der nås ved at svare
”yes” til punktet” adv.set”.
Display setup: Her kan man justere kontrast og baggrundsbelysning. Opsætning
af TAG-nummer med 6 alfanumeriske karakterer. Valg af funktionsvisning i
linie 3 på displayet, der vælges mellem visning af digital udgang og visning af
TAG-nummer.
2-punkts proceskalibrering: Enheden kan proceskalibreres til et aktuelt ind-
gangssignal i 2 punkter. Der påtrykkes et lavt indgangssignal (ikke nødvendig-
vis 0%), og den aktuelle værdi angives. Herefter påtrykkes et højt signal (ikke
nødvendigvis 100%), og den aktuelle værdi angives. Såfremt man siger ja til
at bruge kalibreringen, vil enheden herefter arbejde i henhold til denne nye
justering. Siger man senere nej i dette punkt eller vælger en anden indgangs-
signaltype, går enheden tilbage til fabrikskalibreringen.
Processimulerings-funktion: Vælger man ja til punktet ”EN.SIM”, er det muligt
med piltasterne at simulere et indgangssignal og dermed styre udgangssigna-
let op og ned. Når man afslutter punktet med , går enheden tilbage til normal
mode igen.
Password: Her kan vælges et password mellem 0000 og 9999 til beskyt-
telse mod uautoriserede ændringer. Enheden leveres default uden password.
Såfremt man er kommet til at låse enheden med et password, man derefter har
glemt, kan man altid åbne menuen med password 2008.
Sprog: Der kan i menuen ”lang.setup” vælges mellem 7 forskellige sprogvarianter
af hjælpetekster, der fremkommer i menuen. Der kan vælges mellem UK, DE,
FR, IT, ES, SE og DK.
Autodiagnosticering
Enheden foretager en avanceret autodiagnosticering af det interne kredsløb.
Følgende fejlmuligheder kan vises via displayfronten 4501.
CJ.ER – CJC-føler defekt eller CJC-temperatur uden for område
FL.ER – Fejl i Flash
NO.CO – Fejl i stikforbindelserne
IN.ER – Fejlniveauer på indgang
TY.ER – Konfigurationen i 4501 stemmer ikke overens med denne produkttype
Valg af units
Efter valg af indgangssignaltype kan man vælge, hvilke procesenheder der skal
vises i displayet (se skema). Ved valg af temperaturindgang vises procesvær-
dien altid i Celsius eller Fahrenheit. Vælges i menupunktet ”UNIT” efter valg af
temperaturindgang.

Power up
. 115
2SP
,-
!41#2
2SP
,-
7#1
4-*2
',27.#
2SP
4-*2
"3
*',
.-2+
2#+.
4 ,%#
2SP
"3
',27.#
2SP
' ,%#
2SP
*',
',27.#
2SP
5
"-,,#"
2SP
5
5
5
.-2+
',27.#
2SP
2#+.
',27.#
2SP
2SP]
2SP
.P
1#,1-
2SP
.P
,'
2"
7#1
!41#2
2SP
,E
1#,1-
2SP
2"
1#,1-
2SP
.P27.#
2SP
5
"-,,#"
2SP
5
5
5
,E27.#
2SP]
5
"-,,#"
2SP
5
5
5
2")
2"27.#
2SP
2"Z2"#2"(2")
2"*2",2" 2"1
2"22"32"52"5
2"*N
!'1.*-
2SP
!#".
2SP
3,'2
2SP
j"
I
NLI
]QJEPO
!'1.&'
2SP
1.1
&U
-33,
2SP
&U
LI
LD
L@
BIEJ
2SP
BI=S
2SP
"32-$$
2SP
-27.#
2SP
!"
LNCL
1.0
j"
3,'2
2SP
j"
j$
j"
j$
>=N
?I
BP
BPD
BPIEJ
BPO
C
C=HD
C=HIEJ
%5
DL
D.=
&U
EJ
EJD
EJIEJ
EJO
'LO
)
G
GC
G&U
G(
G.=
G4
G5
G5D
*
*D
*IEJ
*O
I
ID
IIEJ
IO
IO;
I
ID
IIEJ
I
I>=N
IEHO
IEJ
II
IIO
IIO;
IKH
+.=
I4
+5
+5D
,
-DI
L@=T
LD
LIEJ
.=
L&
NLI
O
1
P
PD
Q
QI
Q1
4
5
5D
T@
9>H=JG:
.IEJ
2SP
.
2SP
-33,
.I=S
2SP
"32-$$
2SP
-27.#
2SP
!"
LNCL
P.3*1#
2SP
P.3*1#
2SP
!"
!"
B&U
2120
1.0 = Normaltilstand.
Linie 1 viser ind-
gangssignal.
Linie 2 viser en-
heder - 3,'2
Ved at holde og
samtidig skifter
visning i linie 3
mellem f-QP og
2 %
Linie 4 viser status
for kommunikation.
1.1 = Kun hvis beskyttet
med password.
1.2 = Gælder ikke for
indgangssignaler:
0...20 mA og
spænding.
1.3 = Kun hvis indgangs-
signaler er tempe-
ratur.
RUTEDIAGRAM
Hvis ingen taster har været aktiveret i 1 minut, returnerer displayet til nor-
maltilstanden 1.0 uden at gemme eventuelle konfigurationsændringer.
Forøgelse af værdi / vælg næste parameter
Formindskelse af værdi / vælg forrige parameter
Accepter valget og gå til næste menu
Holde går til forrige menu / returnerer til 1.0 uden at gemme
Fortsættes på siden
Rutediagram ADV.SET
Valgbare3,'2
Fortsættes næste side

1 4#
+#+- 7
2SP
1 4#
*- !
+#+
1#23.
2SP
+#+
!'1.
" *
1'+
. 11
* ,%
!'1.
1#23.
2SP
"-,2
2SP
*'%&2
2SP
2 %,-
2SP]
B-32
*',#
2SP
2 %
B-32
" *
1#23.
2SP
7#1
" **-
2SP
7#1
,-
j"
2SP
]
,-
7#1
" *&'
2SP
7#1
,-
j"
2SP
]
,-
7#1
31#" *
2SP
7#1
,-
1'+
1#23.
2SP
7#1
#,1'+
2SP
7#1
,-
j"
2SP
]
,-
. 11
1#23.
2SP
7#1
#,. 11
2SP
7#1
,-
,#5. 1
2SP
* ,%
1#23.
2SP
3)
* ,%3
2SP
!#!)
#1$
'21#
3)
2.0
,-
B#
2SP
7#1
-32#
2SP
7#1
,-
#1.
2SP
B#
2SP
-32&'
2SP
]
-32*-
2SP
]
1.2
1.2
7#1
-32#
2SP
7#1
,-
,-
,-
1.3 1.3
22 23
RUTEDIAGRAM
avancerede indstillinger (ADV.SET)
Til normaltilstand 1.0
2.0 I undermenuen simulering (SIM) skal tryk-
kes for at returnere til normaltilstand 1.0
1.2 = Gælder ikke for
indgangssignaler:
0...20 mA og
spænding.
1.3 = Kun hvis indgangs-
signaler er tempe-
ratur.
Til normaltilstand 1.0
Fortsat fra forrige side

24 25
[01]
[02]
[03]
[04]
[05]
[06]
[07]
[08]
[09]
[10]
[11]
[12]
[13]
[14]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
[40]
[41]
[42]
[43]
[44]
[45]
[46]
[47]
[48]
[49]
[50]
[51]
[52]
[54]
[55]
[59]
[60]
[61]
[62]
Angiv korrekt password
Gå til avanceret opsætningsmenu?
Vælg temperaturindgang
Vælg potentiometerindgang
Vælg lineær modstandsindgang
Vælg strømindgang
Vælg spændingsindgang
Vælg 0.0-1 V indgangsområde
Vælg 0.2-1 V indgangsområde
Vælg 0-2.5 V indgangsområde
Vælg 0.5-2.5 V indgangsområde
Vælg 0-5 V indgangsområde
Vælg 1-5 V indgangsområde
Vælg 0-10 V indgangsområde
Vælg 2-10 V indgangsområde
Vælg 0-20 mA indgangsområde
Vælg 4-20 mA indgangsområde
Vælg 2-leder følertilslutning
Vælg 3-leder følertilslutning
Vælg 4-leder følertilslutning
Indstil 0% modstandsværdi
Indstil 100% modstandsværdi
Vælg Celsius som temperaturenhed
Vælg Fahrenheit som temperaturenhed
Vælg TC-følertype
Vælg Ni-følertype
Vælg Pt-følertype
Vælg displayenheder
Vælg kommaplacering
Indstil displayvisning lav
Indstil displayvisning høj
Vælg Pt10 som følertype
Vælg Pt20 som følertype
Vælg Pt50 som følertype
Vælg Pt100 som følertype
Vælg Pt200 som følertype
Vælg Pt250 som følertype
Vælg Pt300 som følertype
Vælg Pt400 som følertype
Vælg Pt500 som følertype
Vælg Pt1000 som følertype
Vælg Ni50 som følertype
Vælg Ni100 som følertype
Vælg Ni120 som følertype
Vælg Ni1000 som følertype
Vælg TC-B som følertype
Vælg TC-E som følertype
Vælg TC-J som følertype
Vælg TC-K som følertype
Vælg TC-L som følertype
Vælg TC-N som følertype
Vælg TC-R som følertype
Vælg TC-S som følertype
Vælg TC-T som følertype
Vælg TC-U som følertype
Vælg TC-W3 som følertype
Vælg TC-W5 som følertype
Vælg TC-Lr som følertype
Rullende hjælpetekster i displaylinie 3
Vælg 50% duty cycle udgang
Vælg programmerbar impulstid
Vælg Hz som udgangstype
Vælg impulser/minut som udgangsenhed
Vælg impulser/time som udgangsenhed
Vælg impulser/dag som udgangsenhed
Indstil udgangsfrekvens for 0% indgang
Indstil udgangsfrekvens for 100% indgang
Indstil nedre cut-off frekvens
Indstil impulstid i millisekunder
Ingen følerfejlsaktion - udefineret status ved fejl
Udsend specifik frekvens ved fejl på indgang?
Indstil udgangsfrekvens ved fejl på indgang
Indstil udgangens reaktionstid i sekunder
Indstil temperatur for frekvensudgang lav
Indstil temperatur for frekvensudgang høj
Gå til indstillinger for sprog
Gå til password-indstilling
Gå til simuleringstilstand
Udfør proceskalibrering
Gå til displayopsætning
Udfør memory-operationer
Overfør gemt opsætning til modul
Gem modulopsætning i displayfront
Juster LCD-kontrast
Juster LCD-baggrundsbelysning
Skriv en TAG - max. 6 karakterer
Udgangsfrekvens vises i displaylinie 3
TAG vises i displaylinie 3
Kalibrer indgang lav til procesværdi?
Kalibrer indgang høj til procesværdi?
Aktiver simuleringsmode
Indstil simuler indgangsværdi
Aktiver passwordbeskyttelse?
Angiv nyt password
Vælg sprog
Brug proceskalibreringsværdier?
Indstil værdi for lavt kalibreringspunkt
Indstil værdi for højt kalibreringspunkt
UNIVERSAL I/f CONVERTER
PREASY 4222
CONTENTS
Warnings ............................................................................ 26
Safety instructions.............................................................. 27
Declaration of Conformity .................................................. 29
How to dismantle SYSTEM 4000....................................... 30
Advanced features ............................................................. 31
Application ......................................................................... 31
Technical characteristics.................................................... 31
PR 4501 display / programming front................................ 32
Applications........................................................................ 33
Order codes ....................................................................... 34
Electrical specifications...................................................... 34
Configuration of sensor error detection............................. 37
Display readout on the 4501:
Display outside range..................................................... 37
Sensor error detection limits.......................................... 38
Signal conditioning limits ............................................... 38
Error indications ............................................................. 38
Connections ....................................................................... 39
Block diagram .................................................................... 40
Configuration / operating the function keys ...................... 41
Routing diagram................................................................. 44
Routing diagram, advanced settings (ADV.SET)................ 47
Scrolling help text in display line 3 .................................... 48
25

26 27
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Warning / demand.
Potentially lethal situations.
The CE mark proves the compliance of the module with
the essential requirements of the directives.
The double insulation symbol shows that the module
is protected by double or reinforced insulation.
SAFETY INSTRUCTIONS
DEFINITIONS:
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and
50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and
also troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust
and operate the knobs or potentiometers during normal operation.
RECEIPT AND UNPACKING:
Unpack the module without damaging it and make sure that the manual always
follows the module and is always available. The packing should always follow the
module until this has been permanently mounted.
Check at the receipt of the module whether the type corresponds to the one
ordered.
ENVIRONMENT:
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
All modules fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
MOUNTING:
Only technicians who are familiar with the technical terms, warnings, and
instructions in the manual and who are able to follow these should connect the
module.
Should there be any doubt as to the correct handling of the module, please
contact your local distributor or, alternatively,
2726
WARNING
SYSTEM 4000 must be mounted on a DIN rail according to DIN
46277.
WARNING!
This module is designed for connection to hazardous electric
voltages. Ignoring this warning can result in severe personal
injury or mechanical damage. To avoid the risk of electric shock
and fire, the safety instructions of this manual must be observed
and the guidelines followed. The specifications must not be
exceeded, and the module must only be applied as described
in the following. Prior to the commissioning of the module, this
manual must be examined carefully. Only qualified personnel
(technicians) should install this module. If the equipment is used
in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
WARNING!
Until the module is fixed, do not connect hazardous voltages to
the module.
The following operations should only be carried out on a
disconnected module and under ESD safe conditions:
General mounting, connection and disconnection of wires.
Troubleshooting the module.
Repair of the module and replacement of circuit breakers
must be done by PR electronics A/S only.
WARNING
Do not open the front plate of the module as this will cause
damage to the connector for the display / programming front PR
4501. This module contains no DIP-switches or jumpers.
HAZARD-
OUS
VOLTAGE
GENERAL
INSTAL-
LATION

28 29
DECLARATION OF CONFORMITY
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hereby declares that the following product:
Type: 4222
Navn: Universal I/f converter
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the module.
The Low Voltage Directive 2006/95/EC and later amendments
EN 61010-1
Rønde, 4 November 2008 Peter Rasmussen
Manufacturer’s signature
29
PR electronics A/S, Lerbakken 10, DK-8410 Rønde, Denmark,
tel: +45 86 37 26 77.
Mounting and connection of the module should comply with national legislation
for mounting of electric materials, i.a. wire cross section, protective fuse, and
location. Descriptions of input / output and supply connections are shown in the
block diagram and side label.
The following apply to fixed hazardous voltages-connected modules:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the module. The
power switch should be marked with a label indicating that it will switch
off the voltage to the module.
Year of manufacture can be taken from the first two digits in the serial number.
UL INSTALLATION REQUIREMENTS:
Use 60/75°C copper conducters only.
For use only in pollution degree 2 or better.
Max. ambient temperature..................... 60°C
Max. wire size......................................... AWG 26-14
UL file number........................................ E231911
CALIBRATION AND ADJUSTMENT:
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
NORMAL OPERATION:
Operators are only allowed to adjust and operate modules that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means
there is no electrical shock hazard, and the module is easily accessible.
CLEANING:
When disconnected, the module may be cleaned with a cloth moistened with
distilled water.
LIABILITY:
To the extent that the instructions in this manual are not strictly observed, the
customer cannot advance a demand against PR electronics A/S that would
otherwise exist according to the concluded sales agreement.
28

30 31
UNIVERSAL I/f CONVERTER
PREASY 4222
• Input for RTD, TC, Ohm, potentiometer, mA and V
• Frequency output NPN, PNP and TTL
• Generates frequencies from 0.001...25000 Hz
• 2-wire supply > 16 V
• Universal AC or DC supply
Advanced features:
• Programmable by way of detachable display front (4501), process calibration,
signal simulation, password protection, error diagnostics and help text available
in several languages.
Application:
• Linearised, electronic temperature measurement with RTD or TC sensor.
• Conversion of linear resistance variation to a frequency signal, e.g. from solenoids
and butterfly valves or linear movements with attached potentiometer.
• Power supply and signal isolator for 2-wire transmitters.
• Process control by way of a frequency signal transmitted to e.g. a PLC or a
process computer.
• Galvanic separation and conversion of analogue signals to frequency signals.
Technical characteristics:
• When 4222 is used in combination with the 4501 display / programming front,
all operational parameters can be modified to suit any application. As the 4222
is designed with electronic hardware switches, it is not necessary to open the
module for setting of DIP-switches.
• A green front LED indicates normal operation.
• Continuous check of vital stored data for safety reasons.
• 3-port 2.3 kVAC galvanic isolation.
31
HOW TO DISMANTLE SYSTEM 4000
First, remember to demount the connectors with hazardous voltages.
Picture 1:
Detach the module from the DIN rail
by lifting the bottom lock.
30

+
-
+
-
44
43
42
41
24
23
22
21
33
32
31
32 33
PR 4501 DISPLAY / PROGRAMMING FRONT
Functionality:
The simple and easily understandable PReasy menu
structure and the explanatory help texts guide you
effortlessly and automatically through the configuration
steps, thus making the product very easy to use. Functions
and configuration options are described in the section
”Configuration / operating the function keys”.
Application:
• Communications interface for modification of operational parameters in 4222.
• Can be moved from one 4222 module to another and download the configuration
of the first converter to subsequent converters.
• Fixed display for readout of process data and status.
Technical characteristics:
• LCD display with 4 lines; line 1 (H = 5.57 mm) shows input signal, line 2
(H = 3.33 mm) shows units. Line 3 alternates between digital output value and
scaling (kHz, Hz, mHz, P/m, P/h, P/d) or shows TAG no. Line 4 shows tendency
readout for the input signal and communication status.
• Programming access can be blocked by assigning a password. The password
is saved in the converter in order to ensure a high degree of protection against
unauthorised modifications to the configuration.
Mounting / installation:
• Click 4501 onto the front of 4222.
3332
Applications
Input signals:
Current
Volt-
age RTD and lin. R TC
Connection, wires
Output signals:
Supply:
21.6...253 VAC
or
19.2...300 VDC
PNP, +24 V
Frequency output
TTL, 5 V
NPN, 24 V
Out. Gnd.
Poten-
tiometer

34 35
Auxiliary supplies:
2-wire supply (terminal 44...43)................... 25...16 VDC / 0...20 mA
Max. wire size.............................................. 1 x 2.5 mm2stranded wire
Screw terminal torque................................. 0.5 Nm
Relative humidity......................................... < 95% RH (non-cond.)
Dimensions, without display front (HxBxD).. 109 x 23.5 x 104 mm
Dimensions, with display front (HxBxD)...... 109 x 23.5 x 116 mm
Protection degree (enclosure / terminals) ... IP50 / IP20
Weight ......................................................... 155 g / 170 g with 4501
RTD, linear resistance and potentiometer input:
Input for RTD types:
Pt10, Pt20, Pt50, Pt100, Pt200, Pt250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.), RTD........ 50 Ω
Sensor current, RTD.................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire), RTD......................................... < 0.002 Ω/ Ω
Sensor error detection, RTD ....................... Yes
Short circuit detection, RTD........................ < 15 Ω
35
ORDER CODES:
4222 = Universal I/f converter
4501 = Display / programming front
Electrical specifications:
Specifications range.................................... -20°C to +60°C
Common specifications:
Supply voltage, universal ............................ 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Max. consumption ...................................... ≤2.5 W
Fuse............................................................. 400 mA SB / 250 VAC
Isolation voltage, test / operation ............... 2.3 kVAC / 250 VAC
Communications interface .......................... Programming front 4501
Signal / noise ratio ...................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%), programmable:
Temperature input................................... 1...60 s
mA / V input............................................ 0,4...60 s
Calibration temperature .............................. 20...28°C
Accuracy, the greater of the general and basic values:
34
EMC immunity influence ................................ < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst .................. < ±1% of span
Input
type Min.
value Max.
value Standard
Pt100
Ni100
Lin. resistance
Potentiometer
-200°C
-60°C
0Ω
10 Ω
+850°C
+250°C
10000 Ω
100 kΩ
IEC60751
DIN 43760
-
-
Basic values
Input
type Basic
accuracy Temperature
coefficient
mA ≤±4 µA ≤±0.4 µA / °C
Volt ≤±20 µV ≤±2 µV / °C
Pt100 ≤±0.2°C ≤±0.01°C / °C
Linear resistance ≤±0.1 Ω≤±0.01 Ω/ °C
Potentiometer ≤±0.1 Ω≤±0.01 Ω/ °C
TC type:
E, J, K, L, N, T, U ≤±1°C ≤±0.05°C / °C
TC type: B, R, S,
W3, W5, LR ≤±2°C ≤±0.2°C / °C
General values
Input
type Absolute
accuracy Temperature
coefficient
All ≤±0.1% of span ≤±0.01% of span / °C

36 37
PNP output:
Iout max. ...................................................... 30 mA
Vout .............................................................. 24 VDC ±10%
Cout.............................................................. 10 nF
Rout typ........................................................ 20 Ω
Electromechanical counter.......................... 24 V / 135 mA / 20 ms / ≤10 Hz
NPN output:
Isink max. ..................................................... 150 mA
Isink max. peak ............................................ 300 mA
External voltage (terminal 23) max.............. 55 VDC
Cout.............................................................. 10 nF
Rout typ........................................................ 10 Ω
TTL output:
Isink/source max............................................. 15 mA
Isink/source peak............................................ 100 mA
Vout .............................................................. 5 V ±5%
Cout.............................................................. 10 nF
Rout typ........................................................ 55 Ω
Sensor error detection:
Programmable............................................. 0...26250 Hz
Observed authority requirements: Standard:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC.......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508
of span = of the currently selected measurement range
Configuration of sensor error detection:
Display readout on the 4501:
Display outside range:
37
TC input:
Cold junction compensation (CJC)
via internally mounted sensor .................< ±1.0 °C
Sensor error detection, all TC types ........... Yes
Sensor error current:
when detecting ....................................... Nom. 2 µA
else.......................................................... 0 µA
Current input:
Measurement range .................................... -1...25 mA
Programmable measurement ranges.......... 0...20 and 4...20 mA
Input resistance........................................... Nom. 20 Ω+ PTC 50 Ω
Sensor error detection:
loop break 4...20 mA............................... Yes
Voltage input:
Measurement range .................................... -20 mV...12 VDC
Programmable measurement ranges.......... 0...1 / 0.2...1 / 0...2.5 / 0.5...2.5 /
0...5 / 1...5 / 0...10 and 2...10 VDC
Input resistance........................................... Nom. 10 MΩ
Output:
Frequency output:
Frequency range ......................................... 0...25000 Hz
Min. frequency (span).................................. 0.001 Hz
Duty cycle (0...25000 Hz) ............................ 50% or
Programmable pulse time (f ≤ 500 Hz)........ 1...1000 ms (max. 90% duty cycle)
36
Type Min.
value Max.
value Standard
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
+400°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
-200°C
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
Module: Configuration Sensor error detection:
4222 OUT.ERR=NO OFF
Else: ON
Display readout below min. / above max. (-1999, 9999):
Input Range
Flashing
readout Limit
All All -1999 Display readout <-1999
9999 Display readout >9999