UP 0,UP 1, UP 2,UP 2.4,UP 2.5 5
•withrelativehumidity5to100 %,including thecondensation of upto0,025kgwatercontentper1kgof
dry, at abovestated temperature...........................................................................................AB 1*+AB 5*
•withelevationup to2000 m, withbarometricpressurerange from86 kPaup to108 kPa................AC 1*
•withexposuretointensivewater jets(IPx6)........................................................................................AD 6*
•withshallow immersion –(protectionenclosureIPx7) ....................................................................AD 7*
•withstrong dustiness–withapossibilityofinfluences ofinflammable,non-conducted and non-
explosivedust; the middlelayerofdust;the dustdrop morethan 350 butnotmorethan 1000mg/m2
per day(productswithprotection enclosureofIP6x).......................................................................AE 6*
•withatmosphericoccurrence ofcorrosiveandpollution media(withhigh degree ofatmosphere
corrosiveaggressiveness); important presence ofcorrosivepollution ............................................AF 2*
•withpermanentexposureofbigamountofcorroding orcontaminatedchemicalandsaltfogin
execution for seaenvironment, fog sewage water disposalplant andsomechemicalplant..........AF 4*
•withapossibilityofinfluences ofmechanicalstress:
•mediumsinusoidvibrationswithfrequencyinrange from10up to150 Hz, withshift amplitudeof
0,15 mmforf<fpand acceleration amplitude 19,6m/s2for f>fp(transition frequencyfpisfrom57 up
to62Hz)..........................................................................................................................................AH 2*
•mediumimpacts, shocksand vibrations.......................................................................................AG 2*
•withserious danger ofplantsand mouldgrowing...............................................................................AK 2*
•withserious danger ofanimaloccurrence(insects, birds, small animals)...........................................AL2*
•withdetrimentalinfluenceofradiation:
•ofstraycurrent withintensityofmagneticfield(director alternate, ofmainsfrequency) up to
400A.m-1 .....................................................................................................................................AM 2-2*
•ofsunradiationwithintensity> 500 and < 700W/m2................................................................. AN 2*
•witheffectsofmediumseismicactivitywithacceleration > 300 Gal< 600 Gal.................................AP 3*
•withdirect endanger bystorm.............................................................................................................AQ 2*
•withquickairmovement and strong wind................................................................................AR 3, AS3*
•stand on aconductivebottom)............................................................................................................BC 3*
•without anydanger mediawithobject ...............................................................................................BE 1*
*Markingin accordance with IEC 60364-1, IEC 60 364-5-51 and IEC60 364-5-55 within validedition
1.6.3Powersupplyand dutycycle
Powersupply:
electricmotor...........24 VAC/DC; 120 VAC, 230resp.220 VAC; 3x400resp. 3x380 resp. 3x415 VACresp.
120 VAC ±10%.,
control...........................................................................................................24 VACresp. 220-240 VAC±10%
Powersupplyfrequency.............................................................................................. 50 Hz, or60**Hz ±2 %
** Operating time willincrease 1,2 times, and torquewilldecrease 1,2 times
Dutycycle -according to EN/IEC 60034-1, 8:
EAUPX.X are designedfor remotecontrol:
•short-time operation S2-10min
•intermitted operation S4-25%, max. 90 cyclesperhour
EAwith controller are designed for automatic regulation:
•intermitted operation S4-25%, 90 up to 1200 cyclesperhour
Note:
1. Dutycycle consist of load type, load factorand switching rate.
2. Once EAisconnected to the externalcontrollerunit, also use itasa controlEAwhere the max. load torgue
reachesthe0.7 multiple of the maximum loading torgue forremote operatedEAUPX.Xwithremote control.
1.7Packing, transport,storing and unpacking
Surfaceswithout surface treatment are treatedbyconservation preparation MOGUL LV2-3before
packaging .
Conservation isnotnecessaryifthe following storage conditionsare compliedwith:
• Storage temperature: -10 to +50 °C
• Relativeairhumiditymax.80 %