Reliable F1FR 300 QREC Manual

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 167 March 2019
Bulletin 167 March 2019
Model F1FR 300 QREC CCP
300 psi (20,7 bar) Rated
Concealed Quick Response
Extended Coverage Sprinkler
300 psi (20,7 bar) Rated
Concealed Quick Response
Extended Coverage Sprinkler
to 20’ x 20’ (6.0m x 6.0m)
Features
1. Quick response performance.
2. Push on, thread off, sturdy convenient
cover plate.
3. Factory assembled sprinkler and
cup, shipped complete with protec-
tive cap.
4. Sprinkler assembly and cover plate
separately packaged.
5. Two Versions:
• ½” (13mm) Adjustment
• 5
/
16” (8mm) Adjustment
6. Rugged damage resistant assembly.
No exposed thermal element.
7. Utilizes the Model F1FR-300 QREC
Pendent Sprinkler.
8. Aesthetic ceiling profile.
9. Standard finishes in white painted or
chrome plated. Other color-painted
and specialty finishes available.
For Model F1FR-300 QREC CCP ½” K 5.6 (80) Sprinkler
Types refer to Bulletin 030 for technical specifications
and approvals.
Product Description
The Reliable Model F1FR-300 QREC Quick Response Ex-
tended Coverage Concealed Sprinkler is an attractive, low
profile concealed sprinkler assembly. This sprinkler assembly
utilizes a Model F1FR-300 QREC pendent sprinkler in a Model
CCP cup and push-on thread-off cover plate assembly. The cup
is securely factory threaded on the sprinkler’s inlet end. The as-
sembly is shipped with a protective cap. The sprinkler and cup
are easily installed into the sprinkler fitting using the Model GFR2
Sprinkler Wrench. The cover plate assembly is attached to the
sprinkler cup using a flexible tooth threaded engagement. The
cover plate is attached to the skirt using 135°F (57°C) ordinary
temperature classification solder.
When the ceiling temperature rises, the solder holding the
cover plate melts, allowing the release of this part and thus ex-
posing the Model F1FR-300 QREC sprinkler inside to the rising
ambient temperature.
The Model F1FR-300 QREC automatic sprinkler utilizes a 3.0
mm frangible glass bulb. This sprinkler has demonstrated re-
sponse times in laboratory tests which are five times faster than
standard response sprinklers. This quick response enables the
Model F1FR-300 QREC sprinkler to apply water to a fire faster
than standard sprinklers of the same temperature rating.
Technical Data:
Nominal
Orifice
Thread
Size
K Factor
Approval
Organizations
Sprinkler
Ident.
Number
(SIN)
US Metric
17
/
32” (20mm) ¾” (R¾) 8.0 115.3 1,2,3 R5942
Thread
Size Model
Temp. Rating Max.
Ceiling
Temp.
Bulb
Color
Sprinkler Cover
¾” NPT
(R¾)
F1FR-300
QREC
135°F
57°C
135°F
57°C
100°F
38°C Orange
¾” NPT
(R¾)
F1FR-300
QREC
155°F
68°C
135°F
57°C
100°F
38°C Red
Coverage Area
Flow Rate
gpm (L/m)
Pressure
psi (bar) Max. Enclosure Area Width x
Length
ft. x ft. (m x m)
K=8.0
(Metric 115.3)
26 (98.4)
33 (125.0)
40 (151.4)
10.6 (0,7)
17.0 (1,2)
25.0 (1,7)
16 x 16 (4.9 x 4.9)
18 x 18 (5.5 x 5.5)
20 x 20(1) (6.0 x 6.0)(1)
(1) 135°F (57°C) Only
The temperature rating of the sprinkler is identified by the
color of the glass bulb.
Application and Installation
The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 03/19 P/N 9999970173
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Model F1FR-300 QREC Concealed Sprinklers use 135°F
(57°C) or 155°F (68°C) Model F1FR-300 QREC Pendent Sprin-
klers with a threaded Model CCP cup which is factory attached
to the sprinkler. The assembly is completed by the installation of
the attractive, low profile, 135°F (57°C) rated cover plate assem-
bly. The cover plate and sprinkler cup are joined using a flex-
ible tooth threaded engagement. A choice of two cover plate
assemblies provides either ½” (13mm) or 5
/
16” (8mm) of cover
adjustment.
Do not install these sprinklers in ceilings which have positive
pressure in the space above.
The ¾” NPT (R¾) sprinkler cup is factory attached to the Mod-
el F1FR QREC Sprinkler. A Teflon*-based thread sealant should
be applied to the sprinkler threads only.
After a 25
/
8 inch (67mm) diameter hole is cut in the ceiling,
the sprinkler is easily installed with the Model GFR2 Wrench.
When installing a sprinkler, the protective cap is removed and
the wrench is positioned into the sprinkler/cup assembly until
the two wrench faces engage the wrenching flats on the Model
F1FR QREC Sprinkler. The sprinkler is then tightened into the
pipe fitting. When inserting or removing the wrench from the
sprinkler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER. The cover plate assembly is then
pressed into the cup. Final adjustment is made by turning the
he ceiling surface. Cover plate removal requires turning in the
counter clockwise direction.
After installation, inspect all sprinklers to ensure that there is
a gap between the cover plate and ceiling and that the four
cup slots are open and free from any air flow impediment to the
space above.
Concealed cover plate/cup assemblies are listed only for use
with specific sprinklers. The use of any other concealed cover
plate/cup assembly with the Model F1FR-300 QREC Pendent
Sprinkler or the use of the Model CCP concealed cover plate
assembly on any sprinkler with which it is not specifically listed
may prevent good fire protection and will void all guarantees,
warranties, listings and approvals.
Maintenance
Model F1FR-300 QREC Concealed Sprinklers should be in-
spected and the sprinkler system maintained in accordance
with NFPA 25. Do not clean sprinklers with soap and water, am-
monia or any other cleaning fluids. Remove dust by using a soft
brush or gentle vacuuming. Remove any sprinkler cover plate
assembly which has been painted (other than factory applied)
or damaged in any way. A stock of spare sprinklers should be
maintained to allow quick replacement of damaged or operated
sprinklers. Prior to installation, sprinklers should be maintained
in the original cartons and packaging until used to minimize the
potential for damage to sprinklers that would cause improper
operation or non-operation.
Approval Organizations
* DuPont Registered Trademark.
1. Underwriters Laboratories, Inc.
(UL)
2. Underwriters’ Laboratories of
Canada (ULC)
3. NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic and Open.
Quick Response Extended Cover-
age Sprinklers.
Ordering Information
Specify:
1. Sprinkler Model:
F1FR-300 QREC Pendent
17
/
32” (20mm) Orifice, ¾” NPT
(R¾).
2. Sprinkler Temp. Rating:
135°F (57°C) (1) or 155°F (68°C).
3. Cover plate Model: CCP
4. Cover plate thread size:
¾” NPT (R¾).
5. Cover plate temp. rating:
135°F (57°C).
6. Cover plate adjustment:
Either ½” (13mm) or 5
/
16” (8mm)
(approximate adjustment).
7. Cover plate finish.
(1)135°F (57°C) required for
20’ x 20’ (6.0m x 6.0m).
Installation Wrench
Model GFR2 Sprinkler Wrench
Installation Aid
A protective cap is included for
use during installation.
Cover Plate Finishes(1)
Standard Finishes
Chrome
White
Special Application Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
(1) Other finishes and colors are
available on special order.
Consult factory for details.
Note: Paint or any other coatings
applied over the factory finish will
void all approvals and warranties.

Other Reliable Irrigation System manuals

Reliable GFR VELO–ECOH Manual

Reliable

Reliable GFR VELO–ECOH Manual

Reliable F4FR User manual

Reliable

Reliable F4FR User manual

Reliable Non-Ferrous Concealer User manual

Reliable

Reliable Non-Ferrous Concealer User manual

Reliable F1FR56-300 QREC Series Manual

Reliable

Reliable F1FR56-300 QREC Series Manual

Reliable G4-300 User manual

Reliable

Reliable G4-300 User manual

Reliable F156 EC Series User manual

Reliable

Reliable F156 EC Series User manual

Reliable N25 User manual

Reliable

Reliable N25 User manual

Reliable JL-14 Manual

Reliable

Reliable JL-14 Manual

Reliable DD56-6 Manual

Reliable

Reliable DD56-6 Manual

Reliable F1-56-300 Series User manual

Reliable

Reliable F1-56-300 Series User manual

Reliable F1FR56 User manual

Reliable

Reliable F1FR56 User manual

Reliable F156 Series Manual

Reliable

Reliable F156 Series Manual

Reliable G User manual

Reliable

Reliable G User manual

Reliable F1-SS Series User manual

Reliable

Reliable F1-SS Series User manual

Reliable DH80 Dry User manual

Reliable

Reliable DH80 Dry User manual

Reliable F1 Res 30 LL User manual

Reliable

Reliable F1 Res 30 LL User manual

Reliable F156 Series Manual

Reliable

Reliable F156 Series Manual

Reliable G6-80 Manual

Reliable

Reliable G6-80 Manual

Reliable F3QR80 Dry Pendent Operator's manual

Reliable

Reliable F3QR80 Dry Pendent Operator's manual

Reliable F1FR56 Manual

Reliable

Reliable F1FR56 Manual

Reliable G6-80 User manual

Reliable

Reliable G6-80 User manual

Reliable XL Manual

Reliable

Reliable XL Manual

Reliable DH56 Dry User manual

Reliable

Reliable DH56 Dry User manual

Reliable F1S5 Series Manual

Reliable

Reliable F1S5 Series Manual

Popular Irrigation System manuals by other brands

Autopot easy2grow 100 Set-up guidelines

Autopot

Autopot easy2grow 100 Set-up guidelines

Baccara G75 user manual

Baccara

Baccara G75 user manual

Amadas Reel Rain Traveler Series manual

Amadas

Amadas Reel Rain Traveler Series manual

Tyco CHEC manual

Tyco

Tyco CHEC manual

Tyco RAPID RESPONSE Series quick start guide

Tyco

Tyco RAPID RESPONSE Series quick start guide

Tyco EC-11 Series user manual

Tyco

Tyco EC-11 Series user manual

Gardena T 100 operating instructions

Gardena

Gardena T 100 operating instructions

AQUAJOE AJ-ISGD Original instructions

AQUAJOE

AQUAJOE AJ-ISGD Original instructions

Victaulic FireLock I-800 installation manual

Victaulic

Victaulic FireLock I-800 installation manual

Viking MICROFAST VK354 Technical data

Viking

Viking MICROFAST VK354 Technical data

DIG 8855-1GB quick start guide

DIG

DIG 8855-1GB quick start guide

Tyco FASTFLEX YN25 manual

Tyco

Tyco FASTFLEX YN25 manual

Eden 94095EDAMZ manual

Eden

Eden 94095EDAMZ manual

HYDRO-RAIN ORBIT SPRINKLER SYSTEM DESIGNER installation guide

HYDRO-RAIN

HYDRO-RAIN ORBIT SPRINKLER SYSTEM DESIGNER installation guide

WOOX R4238 quick start guide

WOOX

WOOX R4238 quick start guide

Tyco Fire Product Star Pulsar S160 instruction manual

Tyco Fire Product

Tyco Fire Product Star Pulsar S160 instruction manual

Rain Bird 25PJDA troubleshooting guide

Rain Bird

Rain Bird 25PJDA troubleshooting guide

Toro TWRS user guide

Toro

Toro TWRS user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.